10.4.10 Inverter compressor drive error diagnosis and solution(P4)
Error Code
P4
Malfunction decision
conditions
An abnormal inverter compressor drive is detected by a special
detection circuit, including communication signal detection,
voltage detection, compressor rotation speed signal detection
and so on.
Supposed causes
Wiring mistake; IPM malfunction;
Outdoor fan ass’y faulty
Compressor malfunction; Outdoor PCB faulty
Trouble shooting:
Check if the wiring between main
PCB and compressor connected by
error and if the wires and connectors
are broken?
Correct the connection or replace
the wires and connectors.
Yes
No
IPM continuity check. Check if the
IPM terminal resistance values are
uniform. Refer to page 64.
Replace the IPM board or replace the
main PCB if the IPM board and main
PCB are integrated together.
No
Check if the outdoor fan runs
properly or the outdoor unit
ventilation is good.
Yes
No
please refer to the below remark, check whether the
resistance of the fan motor is normal. If not, replace
the fan motor.
Yes
Check if the compressor resistance
values are uniform .Refer to page 63.
No
Replace the compressor.
Yes
Replace the outdoor main PCB if the
main PCB and IPM are separate.
Remark
:
1) DA1215-H1-I models: Measure the
black
pin and
red
pin of the motor connector, the resistance should be
around
50
Ω
at 20
℃
(68
℉
)
2) DA1815-H2-I models: Measure the
black
pin and
red
pin of the motor connector, the resistance should be
around
84.5
Ω
at 20
℃
(68
℉
)
3) DA2415-H2-I models: Measure the
black
pin and
red
pin of the motor connector, the resistance should be
around
88.5
Ω
at 20
℃
(68
℉
)
Содержание DA1215-H1
Страница 7: ...5 2 2 Part names of Indoor Outdoor units ...
Страница 13: ...11 ...
Страница 16: ...14 6 Wiring Diagram 6 1 Indoor Unit 12000 BTU 115 VOLT 18000 BTU 220 VOLT 24000 BTU 220 VOLT ...
Страница 17: ...15 ...
Страница 18: ...16 6 2 Outdoor Unit DA1215 H1 O ...
Страница 19: ...17 DA1815 H2 O ...
Страница 20: ...18 DA2415 H2 O ...
Страница 21: ...19 For DA1215 H1 O ...
Страница 22: ...20 For DA1815 H2 O For DA2415 H2 O ...
Страница 23: ...21 ...
Страница 54: ...52 P U P V ...
Страница 55: ...53 P W P N ...