
54
10.4.8 Over voltage or too low voltage protection diagnosis and solution(P1)
Error Code
P1
Malfunction decision
conditions
An abnormal voltage rise or drop is detected by checking the
specified voltage detection circuit.
Supposed causes
●
Power supply problems.
●
System leakage or block
●
PCB faulty
Trouble shooting:
Check if the power supply is
normal.
Check if all the connections
and wires are good?
Disconnect the unit with power
supply and try to restart the unit
when power supply gets normal.
No
Yes
No
Correct the connections or replace
the wires.
Yes
Power on and when the unit is in
standby, check if the voltage
between P and N is around DC
310V or 340V or 380V? For different
kinds of units, the voltage differs.
Consult with technical engineer to
get definite value. Then start up the
unit, measure the voltage between
P and N. Is it in 220V~400V?
Replace outdoor main PCB.
Yes
No
Replace the IPM board if it is separate
with main PCB.
Remark:
Measure the DC voltage
between P and N port.
The normal value should
be around 310V.
Содержание DA1215-H1
Страница 7: ...5 2 2 Part names of Indoor Outdoor units ...
Страница 13: ...11 ...
Страница 16: ...14 6 Wiring Diagram 6 1 Indoor Unit 12000 BTU 115 VOLT 18000 BTU 220 VOLT 24000 BTU 220 VOLT ...
Страница 17: ...15 ...
Страница 18: ...16 6 2 Outdoor Unit DA1215 H1 O ...
Страница 19: ...17 DA1815 H2 O ...
Страница 20: ...18 DA2415 H2 O ...
Страница 21: ...19 For DA1215 H1 O ...
Страница 22: ...20 For DA1815 H2 O For DA2415 H2 O ...
Страница 23: ...21 ...
Страница 54: ...52 P U P V ...
Страница 55: ...53 P W P N ...