background image

60706-195

Page 7

0210-00

Notice the preceding tables give two (2) different units of measur-
ing fuel pressure.  The first is with a pressure gauge calibrated in
ounces per square inch.  The second and most accurate is the
use of a simple water manometer.  A manometer is calibrated in
inches of water column.

LP LIQUID WITHDRAWAL SYSTEMS

When installing a unit equipped the LP liquid withdrawal a
primary regulator is not required on the supply tank.   The supply
line is connected to a liquid withdrawal valve on the supply tank
and runs directly to the fuellock strainer mounted on the engine
generator set.  Normally a 3/8 to 1/2 inch copper line is accept-
able for this type of fuel installation.  You must be sure that the
valve you have connected to on the supply tank is in fact a liquid
supply valve and has a drop tube inside the tank that is pulling
fuel from the bottom of the supply tank.  Before starting the unit
you must confirm that you have a good liquid supply at the unit.
Engine generator sets equipped for liquid withdrawal will not
run properly when supplied with high pressure vapor fuel.

LUBRICATION

Before starting the engine, check the oil level in the crankcase. If
it is low, refill to the full mark with the proper weight/grade of oil as
recommended by the engine manufacturer’s maintenance
instructions.  The necessity of using the correct oil, and keeping
the crankcase full cannot be over emphasized.  Failure to use the
proper oil and keep the crankcase properly filled will cause
excessive engine wear and shorten its useful life.

COOLANT

Before starting the engine, check the coolant level in radiator. If it
is low, refill as specified in the engine manufacturer’s mainte-
nance instructions.  The radiator should be filled to about 1 inch
below the filler neck. For additional information on engine coolant
requirements see engine manufacturer’s maintenance instruc-
tions.

INSTALLING THE BATTERY

****  CAUTION  ****

In the following battery installation procedure, check to be sure
the selector switch remains in the “stop” position. This should be
your last step before initial start-up.

A customer supplied twelve-volt battery is required to complete
the installation.  Installation of the highest CCA rated battery,
within the correct BCI group, will increase cold weather starting
performance.  Gel batteries should not be used with the battery
tender installed in the generator enclosure.

MINIMUM

Model

Voltage

BCI Group CCA Rating

PSS30

  12

24

650

PSS40

  12

24

650

Installation and servicing of batteries must be performed or
supervised only by personnel knowledgeable of batteries and the
required precautions.  Keep unauthorized personnel away from
batteries.

When installing or replacing batteries, use the proper group/size
starting battery.  The battery should be a Maintenance Free lead
acid design.  Deep cycle batteries will not  work for this applica-
tion.

CAUTION – PERSONAL DANGER

CAUTION - NEVER dispose of a battery in a fire. The battery is
capable of exploding.

CAUTION - DO NOT open or mutilate the battery.  Released
electrolyte is known to be harmful to the skin and eyes and to be
very toxic.

These engine generator sets are all NEGATIVE ground.  Be very
careful not to connect the battery in reverse polarity, as this may
short circuit the battery charging system on the engine.

CAUTION – A battery presents a risk of electrical shock and high
short circuit current. The following precautions must be observed
when working with batteries.

1.

Remove watches, rings and other metal objects.

2.

Use tools with insulated handles.

3.

Check both the battery cable ends and the battery posts to be
sure they are free of corrosion.

4.

Always connect the battery positive cable first and then
connect the battery negative cable.  When removing the
battery cables from the battery reverse the procedure,
disconnect the negative cable first and then the positive
cable.

5.

Be sure all connections are tight and coat the terminals and
cable end with dialectic grease.

WARNING – The electrolyte is a diluted sulfuric acid that is
harmful to the skin and eyes.  It is electrically conductive and
corrosive.  The following precautions must always be taken.

*

Always wear full eye protection and protective clothing.

*

Where electrolyte contacts the skin, wash off immediately
with water.

*

If electrolyte contacts the eyes, flush thoroughly and immedi
ately with water and seek immediate medical attention.

*

Spilled electrolyte is to be washed down with an acid neutral
izing agent.  A common practice is to use a solution of one
pound of bicarbonate of soda (baking soda) to one gallon of
water.  The bicarbonate of soda solution is to be added until
the evidence of reaction, foaming, has ceased.  The resulting
liquid is to be flushed with water and the area dried.

DANGER – Explosive Fire Risk

*

Never smoke when near batteries.

*

Do not cause a flame or spark in the battery area.

*

Always discharge static electricity from your body before
touching batteries by first touching a grounded metal surface.

SERVICING BATTERIES

Batteries used on these units may over time lose water.  This is
especially true if you are using a trickle charger to maintain your
battery.  When refilling the battery with water use only distilled
water.  Tap water will shorten the service life of the battery.

Содержание Winco PSS30/B

Страница 1: ...PACKAGE STANDBY SYSTEMS INSTALLATION AND OPERATIONS MANUAL PSS30 B PSS40 E ...

Страница 2: ...ined SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries Read and understand all instructions in the manual before starting and operating the generator set USING THIS MANUAL Congratulations on your choice of a Winco generator set You have selected a high quality precision engineered generator...

Страница 3: ...d electrician or contractor The installation must comply with all national state and local codes g Always make sure unit is disabled before placing your hands anywhere near the fan belts alternator or water hoses IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTION This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries...

Страница 4: ...der liquid cooled engine equipped to run on L P N G fuel The engine operates at 1800 rpm and frequency regulation is maintained by the electronic governor within 5 cycles variation from no load to rated load The 30 000 watt 30kW generator is a single bearing direct drive rotating field design The generator is connected to the engine flywheel via flexible drive disks The engine generator is mounted...

Страница 5: ...temperature monitoring over crank protection ECU specific protection elements and diagnostic reporting Metered engine parameters include oil pressure coolant A Liquid Crystal Display The backlit 64 by 128 pixel LCD serves as the local information source for metering alarms pre alarms and protective functions Display operation is maintained at 20 C An optional LCD heater maintains display operation...

Страница 6: ... setting or resetting the system clock 1 Press K right key for initial set or K left to back up up down to choose menu item and time date element to be changed 2 Press L Edit to access change mode to enter Password OP as follows 2a Press K up to select O 2b Press K right to move cursor 2c Press K up to select P 2d Press L Edit to begin change mode 3 Press K up or down to choose year 4 Press L Edit...

Страница 7: ...e engine s requirements and assist in making you aware of the decisions you must make In no case should the instructions or information provided be interpreted to conflict with any local state or national codes If in doubt always consult your local fire marshal or gas supplier WARNING FIRE HAZARD All fuel runs should be installed by a licensed fuel supplier The engine manufacturer has established ...

Страница 8: ...installed from the secondary regula tor to the generator set WARNING PERSONAL DANGER Do not use galvanized pipe in fuel line runs The galvanized coating can become eroded and flake off causing possible obstructions in the regulator or fuel valve The results could range from inoperative engine start to hazardous fuel leaks Size of pipe normally required for generators operating on NG LP up to 25 fe...

Страница 9: ... performed or supervised only by personnel knowledgeable of batteries and the required precautions Keep unauthorized personnel away from batteries When installing or replacing batteries use the proper group size starting battery The battery should be a Maintenance Free lead acid design Deep cycle batteries will not work for this applica tion CAUTION PERSONAL DANGER CAUTION NEVER dispose of a batte...

Страница 10: ...re to do so can cause damage to the engine control module in the generator set All connections must be clean and tight Check the electrolyte fluid in the battery periodically to be sure it is above the plates Never allow the battery to remain in a discharged condition CONNECTING THE BATTERY CHARGER BLOCKHEATER A two stage battery tender is provided on all standby generators This battery tender cha...

Страница 11: ...lt Terminal Block This terminal block is provide for the 120 volt 15 amp feed from customers distrubution panel for the block heater and the trickle charger WARNING A main line circuit breaker has been provided inside the genera tor housing During all wiring installations make sure the breaker is in the off position and the generator operation switch is in the off position WARNING EQUIPMENT DAMAGE...

Страница 12: ... will not start and run without either the jumper installed or a remote N C switch installed G Fuel Select Toggle Switch This SWITCH allows you to change the engine from one fuel to the other See Changing the Fuel Type for additional information H Remote Display Panel Interface Terminals These interface terminals are prewired to allow for the connection of a Basler RDP 110 remote display This disp...

Страница 13: ...e generator terminals in the Automatic Transfer Switch The voltage between the G1 and the G3 terminals should be the same as it was on the generator front panel The voltage should also be checked between the hot terminals G1 and G3 and the G N to be certain of a balanced voltage output and a solid neutral connection The voltage between G1 and G N should be about 120 volts AC 277 on 480 units The s...

Страница 14: ... 3 Governor is defective 4 AC short in generator components ATS PANEL WILL NOT TRANSFER TO EMERGENCY SUPPLY GENERATOR 1 No AC generator output from generator 2 Defective transfer switch controller 3 Incorrect voltage or frequecy for the generator 4 Wiring error between generator and transfer switch 5 Defective mechinally switching solenoid in Automatic Transfer Switch 6 Improper phase rotating ATS...

Страница 15: ...60706 195 Page 13 0210 00 VOLTAGE REGULATOR WIRING THREE PHASE AND SINGLE PHASE ...

Страница 16: ...Page 14 0210 00 60706 195 THREE PHASE AC WIRING HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS ...

Страница 17: ...60706 195 Page 15 0210 00 THREE PHASE AC WIRING DELTA SINGLE PHASE AC WIRING SINGLE PHASE 120 240 VOLTS THREE PHASE DELTA 120 240 VOLTS ...

Страница 18: ...Page 16 0210 00 60706 195 DC SCHEMATIC ...

Страница 19: ...60706 195 Page 17 0210 00 PSS30 OUTLINE DRAWING AND WIRING ENTRANCE PSS40 OUTLINE DRAWING AND WIRING ENTRANCE DIMENSIONS ARE SUBJECT TO CHANGE ALWAYS OBTAIN A CERTIFIED DRAWING FOR CONSTRUCTION PURPOSES ...

Страница 20: ...se are limited to 12 months or 1000 hours which ever accurs first from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some states do not allow limitation on the duration of implied warranty and some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitations may not apply in every instance This warranty ...

Отзывы: