60706-195

Page 3

0210-00

temperature, battery voltage, speed, engine load, coolant level
(from ECU), ECU specific parameters, and run-time statistics.

All metering functions are displayed on the liquid crystal display.
The front panel display begins with the SUMMARY SCREEN.
Pressing the Right arrow key will open the MAIN MENU screen.
The MAIN MENU screen consists of METERING and SETTINGS

Summary Screen

Summary screen can be set to standard or scrolling. When set to
standard, only the following are displayed:

Generator Voltage

Generator Amperage

Generator Phase

Generator Frequency

Engine Oil Pressure

Engine Coolant Temperature

Engine Battery Voltage

FUNCTIONS
DGC-2020 Digital Genset Controllers perform the following
functions:

Generator Protection and Metering

Generator protection guards against over voltage, under voltage,
under frequency, and over frequency. Over current and phase
imbalance protection is available as an option at the time of
manufacture. Each generator protection function has an adjust-
able pickup and time delay setting. Metered generator param-
eters include voltage, current, real power (watts), apparent power
(VA), and power factor (PF).

Engine Protection and Metering

Engine protection features include oil pressure and coolant
temperature monitoring, over crank protection, ECU specific
protection elements, and diagnostic reporting.
Metered engine parameters include, oil pressure, coolant

A - Liquid Crystal Display. The backlit, 64 by 128 pixel LCD
serves as the local information source for metering, alarms, pre-
alarms, and protective functions. Display operation is maintained
at -20°C. An optional LCD heater maintains display operation at -
40°C.

B - Not in Auto Indicator. This red LED lights when the DGC-
2020 is not operating in Auto mode.

C - Alarm Indicator. This red LED lights continuously during
alarm conditions and flashes during pre-alarm conditions.

D - Supplying Load Indicator. This green LED lights when the
generator current is greater than EPS threshold current.

E - Alarm Silence Push-button. Pressing this button opens the
relay output programmed as the horn output.

F - Lamp Test Push-button. Pressing this button tests the DGC-
2020 indicators by exercising all LCD pixels and lighting all LEDs.

G - Auto Push-button and Mode Indicator. Pressing the Auto
button places the DGC-2020 in Auto mode. The green Auto mode
LED lights when Auto mode is active.

H - Off Push-button and Mode Indicator. Pressing this button
places the DGC-2020 in Off mode. The red Off mode LED lights
when the DGC-2020 is in Off mode.

I - Run Push-button and Mode Indicator. Pressing this button
places the DGC-2020 in Run mode. The green Run mode LED
lights when Run mode is active.

ENGINE CONTROL
MODULE
DGC-2020

Содержание Winco PSS30/B

Страница 1: ...PACKAGE STANDBY SYSTEMS INSTALLATION AND OPERATIONS MANUAL PSS30 B PSS40 E ...

Страница 2: ...ined SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries Read and understand all instructions in the manual before starting and operating the generator set USING THIS MANUAL Congratulations on your choice of a Winco generator set You have selected a high quality precision engineered generator...

Страница 3: ...d electrician or contractor The installation must comply with all national state and local codes g Always make sure unit is disabled before placing your hands anywhere near the fan belts alternator or water hoses IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTION This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries...

Страница 4: ...der liquid cooled engine equipped to run on L P N G fuel The engine operates at 1800 rpm and frequency regulation is maintained by the electronic governor within 5 cycles variation from no load to rated load The 30 000 watt 30kW generator is a single bearing direct drive rotating field design The generator is connected to the engine flywheel via flexible drive disks The engine generator is mounted...

Страница 5: ...temperature monitoring over crank protection ECU specific protection elements and diagnostic reporting Metered engine parameters include oil pressure coolant A Liquid Crystal Display The backlit 64 by 128 pixel LCD serves as the local information source for metering alarms pre alarms and protective functions Display operation is maintained at 20 C An optional LCD heater maintains display operation...

Страница 6: ... setting or resetting the system clock 1 Press K right key for initial set or K left to back up up down to choose menu item and time date element to be changed 2 Press L Edit to access change mode to enter Password OP as follows 2a Press K up to select O 2b Press K right to move cursor 2c Press K up to select P 2d Press L Edit to begin change mode 3 Press K up or down to choose year 4 Press L Edit...

Страница 7: ...e engine s requirements and assist in making you aware of the decisions you must make In no case should the instructions or information provided be interpreted to conflict with any local state or national codes If in doubt always consult your local fire marshal or gas supplier WARNING FIRE HAZARD All fuel runs should be installed by a licensed fuel supplier The engine manufacturer has established ...

Страница 8: ...installed from the secondary regula tor to the generator set WARNING PERSONAL DANGER Do not use galvanized pipe in fuel line runs The galvanized coating can become eroded and flake off causing possible obstructions in the regulator or fuel valve The results could range from inoperative engine start to hazardous fuel leaks Size of pipe normally required for generators operating on NG LP up to 25 fe...

Страница 9: ... performed or supervised only by personnel knowledgeable of batteries and the required precautions Keep unauthorized personnel away from batteries When installing or replacing batteries use the proper group size starting battery The battery should be a Maintenance Free lead acid design Deep cycle batteries will not work for this applica tion CAUTION PERSONAL DANGER CAUTION NEVER dispose of a batte...

Страница 10: ...re to do so can cause damage to the engine control module in the generator set All connections must be clean and tight Check the electrolyte fluid in the battery periodically to be sure it is above the plates Never allow the battery to remain in a discharged condition CONNECTING THE BATTERY CHARGER BLOCKHEATER A two stage battery tender is provided on all standby generators This battery tender cha...

Страница 11: ...lt Terminal Block This terminal block is provide for the 120 volt 15 amp feed from customers distrubution panel for the block heater and the trickle charger WARNING A main line circuit breaker has been provided inside the genera tor housing During all wiring installations make sure the breaker is in the off position and the generator operation switch is in the off position WARNING EQUIPMENT DAMAGE...

Страница 12: ... will not start and run without either the jumper installed or a remote N C switch installed G Fuel Select Toggle Switch This SWITCH allows you to change the engine from one fuel to the other See Changing the Fuel Type for additional information H Remote Display Panel Interface Terminals These interface terminals are prewired to allow for the connection of a Basler RDP 110 remote display This disp...

Страница 13: ...e generator terminals in the Automatic Transfer Switch The voltage between the G1 and the G3 terminals should be the same as it was on the generator front panel The voltage should also be checked between the hot terminals G1 and G3 and the G N to be certain of a balanced voltage output and a solid neutral connection The voltage between G1 and G N should be about 120 volts AC 277 on 480 units The s...

Страница 14: ... 3 Governor is defective 4 AC short in generator components ATS PANEL WILL NOT TRANSFER TO EMERGENCY SUPPLY GENERATOR 1 No AC generator output from generator 2 Defective transfer switch controller 3 Incorrect voltage or frequecy for the generator 4 Wiring error between generator and transfer switch 5 Defective mechinally switching solenoid in Automatic Transfer Switch 6 Improper phase rotating ATS...

Страница 15: ...60706 195 Page 13 0210 00 VOLTAGE REGULATOR WIRING THREE PHASE AND SINGLE PHASE ...

Страница 16: ...Page 14 0210 00 60706 195 THREE PHASE AC WIRING HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS ...

Страница 17: ...60706 195 Page 15 0210 00 THREE PHASE AC WIRING DELTA SINGLE PHASE AC WIRING SINGLE PHASE 120 240 VOLTS THREE PHASE DELTA 120 240 VOLTS ...

Страница 18: ...Page 16 0210 00 60706 195 DC SCHEMATIC ...

Страница 19: ...60706 195 Page 17 0210 00 PSS30 OUTLINE DRAWING AND WIRING ENTRANCE PSS40 OUTLINE DRAWING AND WIRING ENTRANCE DIMENSIONS ARE SUBJECT TO CHANGE ALWAYS OBTAIN A CERTIFIED DRAWING FOR CONSTRUCTION PURPOSES ...

Страница 20: ...se are limited to 12 months or 1000 hours which ever accurs first from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some states do not allow limitation on the duration of implied warranty and some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitations may not apply in every instance This warranty ...

Отзывы: