4. If there is a distribution internal to the cabinet and/or a panel
attached to the side of the UPS/Emergency Lighting Inverter,
check the power connections and exercise the breakers in
the cabinet.
iii. Batteries/Battery
Cabinet.
1. Check wiring for proper routing and damage, such as
chaffing and/or cutting. Relocate and /or repair and found
damaged wires.
2. Check the torque of each battery connection for 70in/lbs.
CAUTION:
DO NOT OVER TORQUE THESE CONNECTION AS SOME
BATTERIES HAVE LEAD POSTS AND THEY ARE VERY EASY TO
COMPRESS AND WILL CAUSE FAILURES IN THE FUTURE.
Note:
If Batteries are found to be leaking or fail the load test they should
be replaced. (Consult DSPM as to the status of your Battery Warranty)