Emergency Lighting Inverter Maintenance Manual
Date: 08/28/2020
complete self diagnostic capabilities and LED Monitoring
lighted environment
prior
to an emer-
gency.
The power supplies are able to do a 5 minute battery run the first of every month except for
New Year
’
s day when the test is for 90 minute. The testing can be enabled by going to the Auto-
run screen and selecting Yes or No with the Menu Forward or Menu Reverse button. When the
battery test happens the rectifier is turned off, and the batteries will sustain the load on the output.
If the voltage dips too low the test is terminated prematurely, and a entry is recorded in the alarm
log accordingly. Two minutes into the battery run test the voltage, power date, and time are
logged in the battery log. This is a feature that is standard in our power supplies.
Water Dots are placed on every shelf and door panel to indicate if moisture is present or has got
inside the unit. The Dots are originally white in color but will turn red when water is absorbed.
CABINET
Forced air cooling for maximum reliability
2.10.1.
2.10.2.
2.10.3.
2.11.1.
2.11.2. ECM
-
Environmental Circuit Module allows fixtures and lamps on the emergency circuit (s) to be
operated by normal switching and/or dimming devices in NON
-
emergency conditions
2.11.3. Dimming Panel Interface allows use with emergency lights
2.12.1.
2.12.2.
2.12.3.
2.12.4.
2.12.5. Maintenance contracts available