DSE7110 & DSE7120 Operator Manual
35
7.6
ELECTRICAL TRIP ALARMS
Electrical trips are latching and stop the Generator but in a controlled manner. On initiation of the electrical trip condition the
module will de-energise the ‘Close Generator’ Output to remove the load from the generator. Once this has occurred the
module will start the Cooling timer and allow the engine to cool off-load before shutting down the engine. The alarm must be
accepted and cleared, and the fault removed to reset the module.
Electrical trips are latching alarms and stop the Generator. Remove the fault then press Stop/Reset
to reset the module.
Digital Input A-D
Auxiliary Digital inputs can be user configured as Digital inputs and will display the relevant
icon.
Analogue Input A-C
Auxiliary Analogue inputs can be user configured as Digital inputs and will display the
relevant icon.