![DSE Genset DSEA109 PMG Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/dse/genset-dsea109-pmg/genset-dsea109-pmg_operators-manual_2534923009.webp)
Specifications
Page 9 of 60
057-295 ISSUE: 1
2 SPECIFICATIONS
2.1 TERMINAL SPECIFICATION
Connection Type
Description
Specifiction
CAN port
Terminal Block
Two-part connector. Male
part fitted to module.
Female part supplied in
module packing case.
Minimum Wire Size
0.25 mm
2
(AWG 24)
Maximum Wire Size
3.0 mm
2
(AWG 12)
Tightening Torque
(Wire Clamp)
0.5 Nm
(4.42 lbf.in)
Tightening Torque
(Connector to Connector)
0.5 Nm
(4.42 lbf.in)
All other connections
Spade Terminals
6.3 mm male spade
terminal fitted to module
2.2 PMG / AUXILIARY WINDING / SHUNT SUPPLY
NOTE: The DSEA109 AVR is suitable for alternators with PMG, Auxiliary Winding or Shunt
connections.
CAUTION!:
The source powering the AVR must have inrush protection if it’s internal
impedance is less than 3
Ω
. This is typically the case when using a bench power supply.
Failure to do so may result in the power source becoming damaged.
Parameter
Description
Arrangement
Single phase or phase to phase voltage.
Voltage
100 V AC to 270 V AC between terminals U, V & W
Frequency
40 Hz to 400 Hz.
2.3 GENERATOR VOLTAGE AND FREQUENCY SENSING
Parameter
Description
Arrangement
Single phase or phase to phase voltage.
Measurement Method
True RMS up to 11
th
harmonic.
Primary To Ground Resistance
>4 M
Ω from each phase to
A-
and
P2
(internally
connected).
Phase to Phase Resistance
600 k
Ω between terminals.
Voltage
15 V AC to 600 V AC between terminals.
Voltage Accuracy
±0.5 % of full scale.
Maximum Common Mode Voltage
500 V.
Frequency
40 Hz to 65 Hz.
Frequency Accuracy