Setup Procedure
057-295 ISSUE: 1
Page 22 of 60
Open
Stability Configuration
page that was previously
selected by the DIP switches.
Ensure the
Proportional
and
Integral
Preset Enable
options are checked and set the
Preset Range
of both
to 100 %. This allows Proportional control via the
module Pots.
Alternatively disabling the
Present Enables
allows the
Proportional
and
Integral
values to be adjusted using
the PC via the
SCADA | Commissioning Screen
section.
Set the
Derivative Set Point
to 0.
Set the
Maximum Duty Cycle
to 100 %. Leave all other
Excitation Output
values at default.
Leave the
Soft Start
values at default for the first start. If
an excessive voltage spike occurs on start up, reduce
the
Ramp Start Point
.
Choose the
Protections
tab and set
Start-up Fail Delay
to its maximum value. This prevents it interfering with
the setup process.
Preset Enable
remains ‘checked’
Preset Enable
remains ‘checked’