Introduction

2

1.4 Approvals

1.4.1 Industry Approvals

• UL 1610 Central Station Burglar Alarm Units
• UL 864 Standard for Control Units and Accessories for Fire Alarm

Systems

• CAN/ULC-S304-06 Signal Receiving Centre and Premises Burglar

Alarm Control Units

• CAN/ULC-S559-04 Equipment for Fire Signal Receiving Centres

and Systems

• EN60950-1:2001 Standard for Information Technology Equip-

ment.

• AS/NZS 60950:2000 Information Technology Equipment - Safety
• CISPR22 Information Technology Equipment - Radio Disturbance

Characteristics - Limits and Methods of Measurements

• EN50130-4 Immunity requirements for components of fire,

intruder and social alarm systems.

This equipment shall be installed in accordance with the require-
ments of NFPA72, NFPA70, UL827 and the authority having juris-
diction.
SG-System III with SG-DRL3-IP Line Card is ULC listed for active
communication channel security level A4 when used in conjunction
with T-Link TL250 and T-Link TL300 Internet/Intranet alarm commu-
nicators. For this type of application the supervision and encryption
features have to be enabled.
For ULC Installations the equipment shall be installed in accordance
with the requirements of ULC-S561 and ULC-S301 Standards and
the authority having jurisdiction.

UL864 Programming Requirements

1.5 Receiver Setup and Operation

DSC recommends testing the receiver before actual installation.
Becoming familiar with the connections and setup of the unit on the
workbench will make final installation more straightforward. The
following items are required:

• IEC Power supply cord

• One network hub or router

• One or more dialer or digital control panel and a T-LINK TL250/

TL300

1.

Unpack the components for the System III.

NOTE:

 Carefully unpack the receiver and inspect for shipping

damage. If there is any apparent damage, notify the carrier imme-
diately.

2.

Unscrew the front thumb screws and open the front
plates.

NOTE:

 Before inserting the CPM3, connect the ribbon cable from

the UIB3 board. Before inserting the PSC3 connect the LCD back-
light.

3.

Insert all the cards in the rack, in their appropriate position.
Refer to Figure 1-2 in the System III Installation Manual. 

Connect the ribbon cable of the front panel to the CPM3

before inserting it. Connect the backlight power connec-
tion to the PSC3 then insert the PSC3.

4.

Insert the PSU3 into the rack and fasten it properly.

5.

Connect an ethernet cable to the proper line card.

6.

Connect the main power (110V

AC

 or 220V

AC

) using a

standard computer IEC cable (not supplied).

7.

The LCD will power up and display internal troubles
(printer, computer, telephone line fault, network absent).
The SG-DRL3-IP Receiver will have the green LED ON if the
ethernet line is connected. If the LED is not on, make sure

the ethernet line is connected to the right port

.

NOTE:

 Internal diagnostics may require more than one minute

during the power up sequence.

8.

Send a signal from a control panel to the receiver. The sig-
nal will be displayed on the LCD. Press the [ACK] button to
silence the buzzer.

Table 1-1: UL864 Programming Requirements

NOTICE

 to Users, Installers, Authorities having Jurisdiction, and other involved parties

This product incorporates field programmable software. In order for the product to comply with the requirements in the

Standard for Control Units and Accessories for Fire Alarms Systems

, UL 864, certain programming features or

options must be limited to specific values or not used at all as indicated below.

Opt  #                   Program Option

Page

Permitted in UL 864? (Y/N)

Possible Settings

Settings Permitted (UL 864)

13-14
15-16

17
18
19
1A
1B

1C
1D

1E
1F

21
2B

TX ABSENT DEBOUNCE TIME  - - - - - - - 6
TX ABSENT RESTORE TIME - - - - - - - - - 6
MASK NETWORK PRESENT - - - - - - - - - 6
MASK NETWORK ABSENT- - - - - - - - - - 6
MASK TX RESTORAL  - - - - - - - - - - - - - 7
MASK TX FAILURE - - - - - - - - - - - - - - - 7
MASK TX SWAP- - - - - - - - - - - - - - - - - 7
MASK TX UNENCRYPTED  - - - - - - - - - - 7
MASK INVALID REPORT - - - - - - - - - - - 7
MASK UNKNOWN ACCOUNT - - - - - - - 7
MASK ACCOUNT EXCEEDED - - - - - - - - 7
MASK OPTION CHANGE  - - - - - - - - - - 7
BUSY OUT - - - - - - - - - - - - - - - - - - - - 8

N
N
N
N
N
N
N
N
N
N
N
N
N

1E - FFH (30-255)
1E - FFH (30-255)

ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF

00-05

05AH(90s)
05AH(90s)

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

00

Содержание Sur-Gard System III

Страница 1: ...d Installation Operating Manual version 2 2 WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufac...

Страница 2: ...this system as reliable as possible the system may fail to function as intended due to the failure of a component Inadequate Testing Most problems that would prevent an alarm system from operating as...

Страница 3: ...gle integrated product In this case the SOFTWARE PRODUCT may only be used with the HARDWARE as set forth in this EULA d Rental You may not rent lease or lend the SOFTWARE PRODUCT You may not make it a...

Страница 4: ...contact with burrs cooling fan or heatsinks which could cause damage to the insulation of conductors Holes in metal shall have smooth well rounded surfaces or shall be protected with bush ings The EXT...

Страница 5: ...TFTP Trivial File Transfer Protocol The T LINK Console v1 20 updates T LINK TL250 TL300 using TFTP session The T LINK accounts table and data encryption keys will be stored in the local database Refe...

Страница 6: ...M3 connect the ribbon cable from the UIB3 board Before inserting the PSC3 connect the LCD back light 3 Insert all the cards in the rack in their appropriate position Refer to Figure 1 2 in the System...

Страница 7: ...The ethernet communication lines must be connected first to an Approved acceptable to the local authorities type NID Network Interface Device before leaving the premises e g UL installations UL60950 L...

Страница 8: ...automation got the event successfully A NAK tells the CPM3 the computer automation got the messages but didn t understand it The line card will attempt to send the messages 25 times If after 25 attemp...

Страница 9: ...J45 connector A LINK plus ACTIVITY LED is also present on the board for diagnostics and troubleshooting The IP address of the SG DRL3 IP is programmable The ethernet port is used for system connection...

Страница 10: ...ult 01 Option 10 Line Card Number The Line Card Number provides a virtual identification code for each SG DRL3 IP module Hexadecimal numbers 01 to FE can be programmed in Option 01 to identify line ca...

Страница 11: ...ouble will not be reported Option 2A For Future Use Option 2B Busy Out The line card will stop acknowledging transmitter events under specific trouble conditions if Option 27 is programmed with the fo...

Страница 12: ...e option is set to 00 T Link transmitter account code will be sent to the output as 10 digits and panel account code will be sent as received For example if option 46 is set to 0x07 the following will...

Страница 13: ...ich up to 12 DRL3s 1 CPM3 1 PSC3 and 2 DC DC3s can be connected Furthermore 2 BP3s can be connected together to form a 2 shelf configuration for the System III receiver The BP3 also contains connec ti...

Страница 14: ...eceiver going temporarily off hook usually in an attempt to transfer the phone call Hot Swappable Refers to the ability to add or remove particular cards to or from the system without removing power I...

Страница 15: ...Receiver is sometimes used interchangeably with line card as it is the line card which actually receives the alarm in the MLR Ring One of the wires used on a phone line by convention this is red Round...

Страница 16: ...it s IP table for DVACS transmitters The first four digits represents the receiver and line number originally used on the SG DVL2A and are programmed as the first four digits of the T LINK account re...

Страница 17: ...rs IP and X is the transmitters account NA 001001 0000 NYB0001 001001 0000 NYB0002 O01000 0000 NYF0100 001000 0000 NYE0100 001000 0000 NYE0100 001001 0000 NNR IP IP IP IP 001001 0000 NNT IP IP IP IP 0...

Страница 18: ...1 1010 027 028 029 030 031 032 033 034 035 036 037 038 039 040 041 042 043 044 045 046 047 048 049 050 051 052 053 1B 1C 1D 1E 1F 20 21 22 23 24 25 26 27 28 29 2A 2B 2C 2D 2E 2F 30 31 32 33 34 35 0001...

Страница 19: ...T LINK TL300 12 Jul 2005 09 36 08 12 Jul 2005 09 36 06 01 03 SG 01 001 0092 E100 00 MEDICAL 000 12 Jul 2005 09 36 11 12 Jul 2005 09 36 09 01 03 SG 01 001 0092 R100 00 MEDICAL 000 From the same T LINK...

Страница 20: ...elephone Company For products approved after July 23 2001 the REN for this product is part of the product identifier that has the format US AAAEQ TXXXX The digits represented by are the REN without a...

Отзывы: