DSC PC510 Скачать руководство пользователя страница 12

10

PROGRAMMING SECTIONS

[1]

Zone Definitions

Enter four 2-digit numbers in this section to determine the operating characteristics of each zone.

Zone Definitions:  Digit 1

The first digit of each Zone Definition determines each zone’s audible alarm characteristics and response
speed.  When programmed as 

audible, the siren will sound on alarm; when programmed as silent, the siren will

not sound on alarm.  When silent alarms are used, Programmable Output Option [3] should be used to activate
a programmable output when an alarm is generated.  If silent alarms are not followed with a programmable
output activation, there will be no alarm indication.  Refer to Section [4] for information on programming the
programmable outputs.

Zone response times are factory set at 500 ms.  When programmed as 

fast, the zone response time will be

10 ms.  When programmed as

 slow, the zone response time will be 500 ms.

Zone Definitions:  Digit 2

Digit 2 determines the zone type as described below:

[0] Standard Delay:

     The Standard Delay Zone is normally used for Entry/Exit doors.  The Exit Delay starts when

the system is armed; the zone may be opened and closed during the delay without causing an alarm.  When
the Exit Delay expires, opening the zone will start the Entry Delay.  During the Entry Delay, the keypad buzzer
will sound to indicate that the system should be disarmed.  If the system is disarmed before the Entry Delay
expires, no alarm will be generated.  Entry and Exit Delay times may be independently programmed for 1
to 255 seconds in Section [2].

[1] Instant:

     Instant Zones are normally used for door and window contacts.  Instant Zones have the standard

Exit Delay, but will generate an 

instant alarm when opened after the Exit Delay expires.

[2] Interior:

     Interior Zones are normally used with interior motion detectors and have the standard Exit Delay.

The zone will also have the standard Entry Delay provided that a Delay Zone has been activated before the
Interior Zone.  If an Interior zone is tripped before a Delay zone, an alarm will be generated.

[3] Home-Away with Delay:

     Home-Away Zones operate similarly to Interior Zones with the following additional

feature:  if the system is armed and a Delay zone is not activated during the Exit Delay time, the Home-Away
zones will be automatically bypassed.  This feature allows the system to be armed with the Interior Zones
automatically bypassed so that the user may remain on the premises.

If a Delay Zone is activated during the Exit Delay, the Entry Delay will be applied to Home-Away with Delay
zones when the Exit Delay expires.  If a Home-Away with Delay zone is then activated, the Entry Delay will
be initiated.  If a Home-Away with Delay zone is activated during the Entry Delay, that zone will follow the
Entry Delay before generating an alarm if the system is not disarmed.

If the system is armed with the [

][9][Access Code] At-Home Arming Command, zones programmed as

Home-Away with Delay will remain bypassed until the system is disarmed.

[4] 24-Hour Steady-Alarm:

      24-Hour Steady-Alarm zones are active at all times and will sound an alarm even

if the system is disarmed.  When a 24-Hour Steady Alarm zone is activated, the bell or siren will sound with
a steady tone.  The alarm may be silenced by entering an Access Code on the keypad.  These zones may
be programmed as 

silent when a Programmable Output is enabled; refer to Programming Section [4] for

information on setting Programmable Output options.

[5] 24-Hour Pulsed-Alarm:

  

  

  

  

  24-Hour Pulsed-Alarm zones are active at all times and will sound an alarm even

if the system is disarmed.  When a 24-Hour Pulsed-Alarm zone is activated, the bell or siren will sound with
a pulsing tone.  The alarm may be silenced by entering an Access Code on the keypad.  

NOTE:

  24-Hour

Pulsed-Alarm zones should always be programmed as 

audible so the bell/siren output will be activated

when an alarm is generated.

firealarmresources.com

Содержание PC510

Страница 1: ...manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be carefully read PC51O Software Version 1 O firealarmresources com ...

Страница 2: ...firealarmresources com ...

Страница 3: ...ble Conditions 6 3 Display Alarm Memory 6 4 Bell Test 6 5 Master Code Program Access Codes 7 6 Door Chime On Off 7 7 Utility Output Command 7 8 Installer s Code Installer s Programming Command 7 9 Access Code At Home Arming 7 Keypad Zones 8 Adjusting the Keypad Sounder Tone and Backlighting 8 PROGRAMMING GUIDE 9 Section 5 Enabling System Functions 9 Resetting Programming to the Factory Default Set...

Страница 4: ...d of Line Resistor supervised Maximum zone loop resistance 100 ohms Bell Siren Output fused for 5A Bell Siren Alarms steady and pulsed alarms Programmable Output 50 mA with 9 options Auxiliary Power Output 800 mA with 40 VA transformer 500 mA with 20 VA transformer Maximum 3 Keypads per system and Keyswitch operation Required Battery 12 VDC 1 2 Ah provides 4 hours of stand by at 200 mA Auxiliary O...

Страница 5: ...l Disassemble the keypad by pressing gently on the locking tab found on the bottom of the unit With the tab disengaged pull the backplate from the keypad Prepare a hole in the wall at the desired location and pull the keypad wiring through the hole Hold the backplate in position and pull the wires through the large opening in the backplate Mount the backplate to the wall using the hardware provide...

Страница 6: ...ransformer should not be connected to an outlet that is controlled by a switch Battery Connection If the battery is connected in reverse the 5 A battery fuse will open and will need to be replaced The battery charging voltage is factory set and normally needs no adjustment If AC power is OFF and the battery voltage drops to approximately 9 5 V or lower the battery will be automatically disconnecte...

Страница 7: ...he Ready light is ON To arm the system enter a 4 digit Access Code As each digit is entered the keypad sounder will beep When the Access Code has been entered the Armed light will come ON and the keypad will beep 6 times If the Access Code has been entered incorrectly the keypad will sound a single long tone press the Key and enter the Access Code again When an Access Code has been entered and the...

Страница 8: ...l come ON Ensure that any zone displayed as being bypassed is intentionally bypassed Zone bypasses are automatically cancelled when the system is disarmed To Bypass Zones Enter 1 Access Code the System light will FLASH Enter the number of the zone to be bypassed the corresponding zone light will come ON to indicate that the zone is bypassed To remove a bypass enter the zone number and its zone lig...

Страница 9: ...ons on restoring the system s factory default programming 6 Door Chime On Off The Door Chime feature causes the keypad to beep whenever a Delay or Instant Zone is activated This feature is useful if the Entry Exit door or doors are out of view and the user desires an indication of when the door zones are opened and closed The Door Chime feature only functions when the system is disarmed To turn th...

Страница 10: ...ds to generate a P Key alarm This alarm may be programmed as either silent or audible refer to Programming Section 5 When programmed as audible the keypad will sound a series of short beeps once the system has accepted the alarm and the siren will sound a steady tone Refer to Programming Section 4 for information on programming one of the Programmable Outputs to be activated when this key is press...

Страница 11: ...ing For 2 digit numbers both digits must be programmed before pressing the Key Only the data entered before pressing the Key will be changed When all data for a section is completely entered the keypad sounder will beep several times to indicate that all expected data has been entered When a section is completely programmed enter the number of the next section to be programmed Section 5 Enabling S...

Страница 12: ...also have the standard Entry Delay provided that a Delay Zone has been activated before the Interior Zone If an Interior zone is tripped before a Delay zone an alarm will be generated 3 Home Away with Delay Home Away Zones operate similarly to Interior Zones with the following additional feature if the system is armed and a Delay zone is not activated during the Exit Delay time the Home Away zones...

Страница 13: ...it numbers in Section 4 The first number entered determines how the PGM1 terminal will operate the second number entered determines how the PGM2 terminal will operate Valid entries are from 1 to 9 do not enter 0 1 Utility Output When activated by entering 7 the PGM output switches to ground for 5 seconds and the keypad buzzer will sound 2 Keypad Sounder Follow Mode The PGM output switches to groun...

Страница 14: ...ttings Notes on P Key Operation If the P Key is programmed as a silent alarm it is suggested that one of the Programmable Outputs be programmed with Option 3 Option 4 or Option 8 so that an output is activated when the P Key is pressed The Programmable Output may be used to activate special lighting or a bell or siren other than the one connected to the control panel If the P Key is not to activat...

Страница 15: ...________________ Phone ________________________ Name ________________________________ Phone ________________________ ZONE INFORMATION Zone Type Protected Area 1 ____________________ _______________________________________________________ 2 ____________________ _______________________________________________________ 3 ____________________ _______________________________________________________ 4 __...

Страница 16: ... Output 1 7 activates PGM 2 Keypad sounder follow mode 3 Latched alarm 4 Steady Alarm P Key 5 24 Hour Pulsed Alarm F Key 6 PGM activates on A Key alarm 7 PGM activates on Trouble alarm 8 PGMactivatesonany F A or P Keyalarm 9 Arm Disarm Status 5 1st System Option Code Page 12 Default Zone Light ON Zone Light OFF OFF Zone Light 1 Momentary Keyswitch Arming Maintained Keyswitch Arming ON Zone Light 2...

Страница 17: ... NO NC NC END OF LINE RESISTOR 5600Ω 0 5W END OF LINE RESISTOR 5600Ω 0 5W EOL RESISTOR LOOPS USING NO NC DEVICES EOL RESISTOR LOOPS USING NC DEVICES ONLY TRANSFORMER 16VAC 20VA MIN DO NOT CONNECT TRANSFORMER TO SWITCHED RECEPTACLE RECOMMENDED TRANSFORMER BASLER ELECTRIC BE 116240CAA 0002 120VAC 60Hz GRN YEL BLK RED LOAD 50mA MAX LOAD 50mA MAX TO AUX TO AUX PROGRAMMABLE OUTPUT 2 PROGRAMMABLE OUTPUT...

Страница 18: ...and which may be revised from time to time will be charged for each unit repaired Products which Digital Security Controls Ltd determines not to be repairable will be replaced by the nearest equivalent product avail able at that time The current market price of the replacement prod uct will be charged for each replacement unit Digital Security Controls Ltd warrants the original purchaser that for ...

Страница 19: ...ly alert occupants of a fire for a number of reasons some of which follow The smoke detectors may have been improperly installed or positioned Smoke may not be able to reach the smoke detectors such as when the fire is in a chimney walls or roofs or on the other side of closed doors Smoke detectors may not detect smoke from fires on another level of the residence or building Every fire is differen...

Страница 20: ... 1997 2002 Digital Security Controls Ltd Toronto Canada Printed in Canada 29000864 R1 1 800 387 3630 firealarmresources com ...

Отзывы: