PROGRAMMING GUIDE

With the system disarmed, enter [

][8][Installer’s Code].  The system can only be programmed while it is

disarmed.  The default Installer’s Code is [0510].  The Installer’s Code should be changed after the system is
installed; refer to Programming Section [3].

When the Installer’s Programming Command is entered, the “Armed” light will be ON and the “System” light will
FLASH to indicate that the system is ready for programming.  

NOTE: 

If no key entry is made for 2 minutes, the

system will return to the “Ready” mode and the Installer’s Programming Command will have to be entered again.

With the “Armed” light ON and the “System” light flashing, enter a digit from 1 to 5 to select a Section to program.
Note that each section is programmed independently.

Once the section to be programmed is entered, the keypad will beep 3 times; the “Ready” light will come ON,
the “Armed” light will be OFF, and the “System” light will FLASH.  The system is now ready to accept data for
the selected section.

To change the first digit in a section, enter a new digit from the keypad.  If you wish to keep the first digit
unchanged, enter the same number.  After entering the first digit, enter the second digit by pressing a number
on the keypad.

After entering the data, press the [#] Key to return to the programming mode.  You may then enter another
Section for programming.  For 2-digit numbers, both digits must be programmed before pressing the [#] Key.
Only the data entered before pressing the [#] Key will be changed.

When all data for a section is completely entered, the keypad sounder will beep several times to indicate that
all expected data has been entered.  When a section is completely programmed, enter the number of the next
section to be programmed.

Section [5]: Enabling System Functions

Section [5] allows you to enable or disable various system functions.  Refer to the Programming Worksheet to
see which features are represented by the Zone Lights.  Press the number key corresponding to the desired
feature to turn the Zone Light ON or OFF.  When all selections have been made, press the [#] Key to save the
changes and return to the program mode.

Resetting Programming to the Factory Default Settings

The system may be reset to its factory default programming by following this procedure:

1

Remove all power, AC and battery, from the PC510

2

Remove all wiring connections from the PGM1 and Zone 1 terminals

3

Connect the PGM1 and Zone 1 terminals together

4

Apply power to the PC510 and wait for 10 seconds

5

After approximately 10 seconds, the keypad sounder will beep and Zone Light 1 will come ON

6

Remove all power, AC and battery, from the PC510

7

Remove the connection between the PGM1 and Zone 1 terminals

8

Re-connect original wiring to the PGM1 and Zone 1 terminals

9

Restore power to the PC510; the Programming Sections have now been restored to the factory default

settings

firealarmresources.com

Содержание PC510

Страница 1: ...manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be carefully read PC51O Software Version 1 O firealarmresources com ...

Страница 2: ...firealarmresources com ...

Страница 3: ...ble Conditions 6 3 Display Alarm Memory 6 4 Bell Test 6 5 Master Code Program Access Codes 7 6 Door Chime On Off 7 7 Utility Output Command 7 8 Installer s Code Installer s Programming Command 7 9 Access Code At Home Arming 7 Keypad Zones 8 Adjusting the Keypad Sounder Tone and Backlighting 8 PROGRAMMING GUIDE 9 Section 5 Enabling System Functions 9 Resetting Programming to the Factory Default Set...

Страница 4: ...d of Line Resistor supervised Maximum zone loop resistance 100 ohms Bell Siren Output fused for 5A Bell Siren Alarms steady and pulsed alarms Programmable Output 50 mA with 9 options Auxiliary Power Output 800 mA with 40 VA transformer 500 mA with 20 VA transformer Maximum 3 Keypads per system and Keyswitch operation Required Battery 12 VDC 1 2 Ah provides 4 hours of stand by at 200 mA Auxiliary O...

Страница 5: ...l Disassemble the keypad by pressing gently on the locking tab found on the bottom of the unit With the tab disengaged pull the backplate from the keypad Prepare a hole in the wall at the desired location and pull the keypad wiring through the hole Hold the backplate in position and pull the wires through the large opening in the backplate Mount the backplate to the wall using the hardware provide...

Страница 6: ...ransformer should not be connected to an outlet that is controlled by a switch Battery Connection If the battery is connected in reverse the 5 A battery fuse will open and will need to be replaced The battery charging voltage is factory set and normally needs no adjustment If AC power is OFF and the battery voltage drops to approximately 9 5 V or lower the battery will be automatically disconnecte...

Страница 7: ...he Ready light is ON To arm the system enter a 4 digit Access Code As each digit is entered the keypad sounder will beep When the Access Code has been entered the Armed light will come ON and the keypad will beep 6 times If the Access Code has been entered incorrectly the keypad will sound a single long tone press the Key and enter the Access Code again When an Access Code has been entered and the...

Страница 8: ...l come ON Ensure that any zone displayed as being bypassed is intentionally bypassed Zone bypasses are automatically cancelled when the system is disarmed To Bypass Zones Enter 1 Access Code the System light will FLASH Enter the number of the zone to be bypassed the corresponding zone light will come ON to indicate that the zone is bypassed To remove a bypass enter the zone number and its zone lig...

Страница 9: ...ons on restoring the system s factory default programming 6 Door Chime On Off The Door Chime feature causes the keypad to beep whenever a Delay or Instant Zone is activated This feature is useful if the Entry Exit door or doors are out of view and the user desires an indication of when the door zones are opened and closed The Door Chime feature only functions when the system is disarmed To turn th...

Страница 10: ...ds to generate a P Key alarm This alarm may be programmed as either silent or audible refer to Programming Section 5 When programmed as audible the keypad will sound a series of short beeps once the system has accepted the alarm and the siren will sound a steady tone Refer to Programming Section 4 for information on programming one of the Programmable Outputs to be activated when this key is press...

Страница 11: ...ing For 2 digit numbers both digits must be programmed before pressing the Key Only the data entered before pressing the Key will be changed When all data for a section is completely entered the keypad sounder will beep several times to indicate that all expected data has been entered When a section is completely programmed enter the number of the next section to be programmed Section 5 Enabling S...

Страница 12: ...also have the standard Entry Delay provided that a Delay Zone has been activated before the Interior Zone If an Interior zone is tripped before a Delay zone an alarm will be generated 3 Home Away with Delay Home Away Zones operate similarly to Interior Zones with the following additional feature if the system is armed and a Delay zone is not activated during the Exit Delay time the Home Away zones...

Страница 13: ...it numbers in Section 4 The first number entered determines how the PGM1 terminal will operate the second number entered determines how the PGM2 terminal will operate Valid entries are from 1 to 9 do not enter 0 1 Utility Output When activated by entering 7 the PGM output switches to ground for 5 seconds and the keypad buzzer will sound 2 Keypad Sounder Follow Mode The PGM output switches to groun...

Страница 14: ...ttings Notes on P Key Operation If the P Key is programmed as a silent alarm it is suggested that one of the Programmable Outputs be programmed with Option 3 Option 4 or Option 8 so that an output is activated when the P Key is pressed The Programmable Output may be used to activate special lighting or a bell or siren other than the one connected to the control panel If the P Key is not to activat...

Страница 15: ...________________ Phone ________________________ Name ________________________________ Phone ________________________ ZONE INFORMATION Zone Type Protected Area 1 ____________________ _______________________________________________________ 2 ____________________ _______________________________________________________ 3 ____________________ _______________________________________________________ 4 __...

Страница 16: ... Output 1 7 activates PGM 2 Keypad sounder follow mode 3 Latched alarm 4 Steady Alarm P Key 5 24 Hour Pulsed Alarm F Key 6 PGM activates on A Key alarm 7 PGM activates on Trouble alarm 8 PGMactivatesonany F A or P Keyalarm 9 Arm Disarm Status 5 1st System Option Code Page 12 Default Zone Light ON Zone Light OFF OFF Zone Light 1 Momentary Keyswitch Arming Maintained Keyswitch Arming ON Zone Light 2...

Страница 17: ... NO NC NC END OF LINE RESISTOR 5600Ω 0 5W END OF LINE RESISTOR 5600Ω 0 5W EOL RESISTOR LOOPS USING NO NC DEVICES EOL RESISTOR LOOPS USING NC DEVICES ONLY TRANSFORMER 16VAC 20VA MIN DO NOT CONNECT TRANSFORMER TO SWITCHED RECEPTACLE RECOMMENDED TRANSFORMER BASLER ELECTRIC BE 116240CAA 0002 120VAC 60Hz GRN YEL BLK RED LOAD 50mA MAX LOAD 50mA MAX TO AUX TO AUX PROGRAMMABLE OUTPUT 2 PROGRAMMABLE OUTPUT...

Страница 18: ...and which may be revised from time to time will be charged for each unit repaired Products which Digital Security Controls Ltd determines not to be repairable will be replaced by the nearest equivalent product avail able at that time The current market price of the replacement prod uct will be charged for each replacement unit Digital Security Controls Ltd warrants the original purchaser that for ...

Страница 19: ...ly alert occupants of a fire for a number of reasons some of which follow The smoke detectors may have been improperly installed or positioned Smoke may not be able to reach the smoke detectors such as when the fire is in a chimney walls or roofs or on the other side of closed doors Smoke detectors may not detect smoke from fires on another level of the residence or building Every fire is differen...

Страница 20: ... 1997 2002 Digital Security Controls Ltd Toronto Canada Printed in Canada 29000864 R1 1 800 387 3630 firealarmresources com ...

Отзывы: