The following is a list of the default DVAC reporting and identifier codes:
Rep #
Title
FB
RC
Printed Message
0000 - 007F
Zone Alarms/Restore
*
001 - 128
(See Zone Events Section)
0080 - 00FF
Zone Troubles/Restore
*
001 - 128
(See Zone Events Section)
0100 - 017F
Zone Faults/Restore
*
001 - 128
(See Zone Events Section)
0180 - 01C9
Module (1-74) Tampers/Restore
17/97
131 - 204
Tamper Zn#
01CA
Fire Key
00
129
Fire Zn#129
01CB
Aux. Key
04
129
Medical Zn# 0129
01CC
Panic Key
02
129
Panic Zn#129
01CD
Duress Code
03
129
Holdup Zn#129
01CE - 024D
Open/Close by users
76/F6
001 - 128
Open/Close User#
024E
Quick Arm
F6
130
Close User#130
024F
Partial Close
7E
004
PartClos
0250
Auto Arm Abort
7E
011
Late to Close
0251
Automatic Arming
7E
001
Automat Closing
0252
Keypad Lockout
7E
029
User cd Tamper
0253
Open/Close second Master
76/F6
131
Close User#131
0254 - 0256
For Future Use
00
—
Not Transmitted
0257
Opening after Alarm
7E
017
Disarm from alm
0258
Auto Disarm
7E
002
Automatic Open
0259 - 0260
Partition Open/Close
77/F7
001 - 008
Open/Close Group#
0261
For Future Use
00
—
Not Transmitted
0262
System Battery Trouble/Restore
3D/BD
001
SysLBat
0263
System AC Trouble/Restore
3A/BA
001
AC Cut
0264
System Bell Trouble/Restore
32/B2
135
System trb
0265
System Aux. Supply Trouble/Restore
3C/BC
001
PwSuply
0266
Combus Trouble/Restore
32/B2
131
System trb
0267 - 0268
TLM Line 1 & 2 Trouble/Restore
3E/BE
001 - 002
Line
0269
FTC Restoral
00
—
Not Transmitted
026A
System Periodic Test
00
—
Not Transmitted
026B
Event Buffer %75 Full
32
132
System trb
026C
System Test
00
—
Not Transmitted
026D
LINKS Periodic Test
00
—
Not Transmitted
026E
Periodic UL Test
7A
002
Test
026F
DLS Lead In
7E
047
Remote P. Begin
0270
DLS Lead Out
7E
049
Remote P. Success
0271
Installer Lead In
7E
039
Local Prg Begin
0272
Installer Lead Out
7E
043
Local Prg Ended
0273
Automation Fault/Restore
32/B2
133
System Trb
0274 - 0277
For Future Use
00
—
Not Transmitted
0278 - 02A7
PC4204 Battery Trouble/Restore
3D/BD
011 - 026
SysLBat
PC4204 AC Trouble/Restore
3A/BA
011 - 026
AC Cut
PC4204 Aux. Supply Trb/Restore
3C/BC
011 - 026
PwSuply
02A8
For Future Use
00
—
Not Transmitted
02A9
Fire Alarm 2-wire Smoke
00/80
130
Fire
02AA
Water Flow Alarm
01/81
130
Sprnklr
02AB
2-wire Smoke Trouble
20/A0
130
Fire Trb
02AC
Water Flow Trouble
21/A1
130
Sprnklr Trb
02AD
Ground Fault
32/B2
130
System Trb
02AE - 02ED
Wireless Zone Low Batt. Alarm
3B/BB
151 - 214
WirLBat
The above events apply to PC40x0 v2.1x