The following wiring diagrams (Figures 5 to 8) are examples of ULC Listed Fire Monitoring Installation
connections.
GS3060 Wiring Diagrams
RED (
R
)
G
REEN (
T
)
GR
A
Y
(
R
)
BRO
W
N (
T
)
RJ-31X
RIN
G
TI
P
CONTROL PANEL
Incoming
Phone line
Handset
RI
TI
TI
RI
TI
P
RIN
G
4
3
2
1
5
GS3060
TIP
T1 R1
RNG
(BLK/WHT) +13.8VDC
(BLK ) GND
Control
Panel
EOL
Resistor
See Note 3
DSC
RM-2
RELA
Y
NC
C
NO
ZONE
TERMINALS
(See Note 1)
- +
+12VDC
GND
CONTROL PANEL
Aux Power
+ -
DSC
Supervision
Relay
See Note 2
19
18
17
16
14
20
15
12
11
10
9
7
13
8
6
19
Z4
Z3
Z2
COM
20
Z1
12
AUX
+
PGM
3
PGM
1
13
PGM
4
COM
TAMPER
GS3060
PGM
3
DC IN
+ -
KSAD
1380100
W
1
US
Power Adaptor
NOTES
1.
Program the Zone/Point as “Supervisory” type
with keypad only annunciation when in Alarm.
Do
NOT use a point that is normally used for
2-Wire Smoke detectors.
2.
The power Supervision relay,
RM-2
is only used
when the GS3060 is
not
powered by the control
panel. When the Radio is powered by the control
panel the relay is not required since a loss of input
power will generate a signal to the CMC.
3.
Output 4 on the GS3060 must be set as “Active
High” (default).
4.
When powering the GS3060 Radio by an
Auxiliary Power supply that has its own backup
battery, insert JP3 jumper on the radio and remove
the 1.2AH battery that came with the radio.