DryGair Dehumidification Unit
Appendices
Ver. 06/2020
81
Appendix E. Climate Control System
This section describes how to connect the DryGair dehumidifier to a climate
control system, for operating and controlling the unit by computer software.
Note
All settings in the climate control system should be performed by a climate
control expert, with an understanding of communication.
E.1.
DryGair Systems for Dehumidification (only)
This configuration requires connecting 24 VAC cables to the relays, located at
the bottom right corner of the electrical compartment.
Figure 9-15. Climate control relays
•
Terminals 40 and 41
: Remote start and stop command to the unit
(digital output from the computer).
Turning the unit on turns the unit's fans on.
The start parameter is generally set by a defined operating hour. The
unit receives a signal to operate between the required operating hours
(usually from sunset to sunrise).
•
Terminals 42 and 43
: Remote drying command to start and stop
dehumidification (digital output from the computer).
This signal turns the dehumidification on/off, based on the humidity
sensor data and the humidity setpoint in the climate control system.
Drying on
: When dehumidification is required (e.g., high humidity),
the unit will receive a signal to turn on dehumidification. This turns
the unit's compressor on, and moisture is removed from the air.
Note:
To operate the dehumidification, the signals must be sent to
both the compressor and the fans.
Drying off
: When drying is not required (e.g., low humidity), the
dehumidification will turn off and the circulating fans will continue
operating (circulating air) while the compressor is off. This is also the
option for using the fans during the day when the greenhouse is open.
•
Terminals 44 and 45
: Output fault indications feedback to the software
(digital input to the computer).
40
45
Содержание DG12
Страница 8: ......
Страница 58: ...Appendices Standard Units Specifications R507 Refrigerant DryGair Energies Ltd 50 A 2 DG 6 Small Unit ...
Страница 59: ...DryGair Dehumidification Unit Appendices Ver 06 2020 51 A 3 DG 12 Standard Split Unit ...
Страница 60: ...Appendices Standard Units Specifications R507 Refrigerant DryGair Energies Ltd 52 A 4 DG 6 Small Split Unit ...
Страница 61: ...DryGair Dehumidification Unit Appendices Ver 06 2020 53 A 5 DG 12 Standard Unit with Heating Cooling ...
Страница 63: ...DryGair Dehumidification Unit Appendices Ver 06 2020 55 A 7 DG 12 Standard Split Unit with Heating Cooling ...
Страница 65: ...DryGair Dehumidification Unit Appendices Ver 06 2020 57 A 9 DG 13 Warm Climate Unit ...
Страница 67: ...DryGair Dehumidification Unit Appendices Ver 06 2020 59 B 2 DG 6 EU Small Unit ...
Страница 68: ...Appendices EU Models Specifications R513a Refrigerant DryGair Energies Ltd 60 B 3 DG 12 EU Standard Split Unit ...
Страница 69: ...DryGair Dehumidification Unit Appendices Ver 06 2020 61 B 4 DG 6 EU Small Split Unit ...
Страница 71: ...DryGair Dehumidification Unit Appendices Ver 06 2020 63 B 6 DG 6 EU Small Unit with Heating Cooling ...
Страница 73: ...DryGair Dehumidification Unit Appendices Ver 06 2020 65 B 8 DG 6 EU Small Split Unit with Heating Cooling ...
Страница 96: ...Appendices Climate Control System DryGair Energies Ltd 88 ...
Страница 97: ...DryGair Dehumidification Unit Appendices Ver 06 2020 89 ...
Страница 98: ...Appendices Climate Control System DryGair Energies Ltd 90 ...
Страница 101: ...DryGair Dehumidification Unit Comments and Notes Ver 06 2020 93 ...
Страница 102: ......