background image

cause drafts. Return air grilles must be properly sized to carry air back to the blower. If they are too small, they also cause

15 

Table 7-2 Bottom Duct Application 

* The above airflow data for reference only. 

Ɣ

 The air distribution system has the greatest effect on airflow. The duct system is totally controlled by the contractor. For this 

reason, the contractor should use only industry-recognized procedures. 

Ɣ

 Heat pump systems require a specified airflow. Each ton of cooling requires between 350 and 450 cubic feet of air per minute 

(CFM), or 400 CFM nominally. 

Ɣ

 Duct design and construction should be carefully done. System performance can be lowered dramatically through bad 

planning or workmanship. 

Ɣ

 Air supply diffusers must be selected and located carefully. They must be sized and positoined to deliver treated air along the 

perimerter of the space. If they are too small for their intended airflow, they become noisy. If they are not located properly, they 

noise. 

Ɣ

 The installers should balance the air distribution system to ensure proper quiet airflow to all rooms in the home. This ensures a 

comfortable living space. 

Ɣ

 An air velocity meter or airflow hood can give a reading of system CFM. 

Ɣ

 When installation, installer should select the air speed according to the actual setting static pressure. Please refer to the 

Table

7-1, 7-2

 AIRFLOW PERFORMANCE DATA.   

0[0]  0.1[.02] 0.2[.05]  0.3[.07]  0.4[.10] 0.5[.12] 0.6[.15] 0.7[.17] 

CFM(L/S) 1341(633) 1286(607)  1242(586)  1193(563)  1134(535)  1063(502)  895(425)  775(366) 
RPM 630 

676 720 764 809 854 

927 960 

Watts 361 355 348  340  331 319 298 284 
Amps 1.57 

1.55 1.52  1.51 1.46 1.41 1.34 1.29 

CFM(L/S) 1510(713) 1468(693)  1420(671)  1369(647)  1292(610)  1218(575)  1128(533)  934(441) 
RPM 701 

741 779 814 854 892 

928 987 

Watts 447 438 428  419  408 394 377 347 
Amps 1.95 

1.92 1.88  1.84  1.8 1.75 1.69 1.59 

CFM(L/S) 1705(805) 1658(783)  1604(758)  1549(731)  1489(703)  1416(669)  1321(624)  1179(557) 
RPM 781 

815 849 880 908 938 

969 

1006 

Watts 558 547 536  524  511 493 474 445 
Amps 2.45 

2.41 2.36  2.32 2.26 2.21 2.14 2.04 

CFM(L/S) 1658(783) 1603(757)  1546(730)  1491(704)  1427(674)  1354(639)  1265(598)  1125(531) 
RPM 747 

779 811 843 871 903 

932 972 

Watts 510 500 489  478  464 449 431 405 
Amps 2.33 2.3 2.26  2.23 2.19 2.14 2.09 2.02 
CFM(L/S) 1837(868) 1776(839)  1724(814)  1647(778)  1576(744)  1502(709)  1413(667)  1295(611) 
RPM 816 

845 869 894 918 942 

964 992 

Watts 615 602 587  575  558 542 522 498 
Amps 2.84 2.8 2.76  2.72 2.67 2.63 2.58 2.51 
CFM(L/S) 2019(954) 1954(923)  1892(893)  1819(859)  1745(825)  1656(782)  1565(739)  1459(689) 
RPM 891 

910 931 949 968 986 

1002 

1020 

Watts 756 741 723  706  689 672 649 627 
Amps 3.54 3.5 3.45  3.41 3.35 3.3 3.23 3.16 
CFM(L/S) 2064(975) 2004(946)  1942(917)  1875(886)  1806(853)  1726(815)  1643(776)  1538(726) 
RPM 

905 929  953  974  993 1011 

1028 1045 

Watts 731 712 687  666  643 618 595 570 
Amps 3.19 

3.11 3.03  2.94 2.86 2.77 2.69 2.61 

CFM(L/S) 2177(1028) 2111(997)  2041(964) 

1971(931)  1886(891)  1806(853)  1704(804)  1604(758) 

RPM 

955 973  992  1007 1021 1036 

1052 1065 

Watts 807 779 751  730  703 679 651 624 
Amps 3.54 

3.43 3.34  3.26 3.16 3.08 2.98 2.89 

CFM(L/S) 2277(1075) 2209(1043) 2135(1008)  2056(971)  1974(932)  1881(888)  1781(841)  1668(788) 
RPM 

998 1012 1023  1036 1049 1060 1071 1082 

Watts 878 852 828  801  777 747 719 687 
Amps 3.92 

3.81 3.72  3.64 3.53 3.43 3.33 3.22 

Motor 

Speed 

Model 

Number 

36 

Low 

Middle 

High 

External Static Pressure-Inches W.C.[kPa] 

 CFM(L/S)(Watts) 

60 

Low 

Middle 

High 

48 

Low 

Middle 

High 

Содержание MRB-36HWN1-X14B

Страница 1: ...INSTALLATION INSTRUCTIONS PACKAGE 14 SEER HEAT PUMP 3 5 TONS R 410A Refrigerant MAN I IDP14HP 1115 MRB 36HWN1 X14B MRB 48HWN1 X14 MRB 60HWN1 X14 3Ph...

Страница 2: ...ng installation or operation Failure to follow these instructions may result in improper installation adjustment service or maintenance possibly resulting in fire electrical shock property damage pers...

Страница 3: ...0 TROUBLE SHOOTING 21 LIST OF TABLES TABLE 2 1 UNIT CLEARANCE 6 TABLE 6 1 14 SEER HEAT PUMP W WITHOUT ELECTRIC HEAT 12 TABLE 6 2 14 SEER COOLING ONLY W WITHOUT ELECTRIC HEAT 12 TABLE 6 3 14 SEER PHYS...

Страница 4: ...e use of unauthorized components accessories or devices may adversely affect the operation of the heat pump and may also endanger life and property The manufacturer disclaimer any responsibility for s...

Страница 5: ...Manufacturer or distributor will not accept the claims from dealer for any transportation damage 1 1 INSPECTION Refer to Fig 2 2 2 3 for unit physical data and to Table 7 1 for electrical data If comp...

Страница 6: ...AUTION Before lifting make sure the unit weight is distributed equally on the rigging cables so it will lift evenly Units may be moved or lifted with a forklift Slotted openings in the base rails are...

Страница 7: ...ection Distance in Top Front Rear Right Left Bottom 30 60 18 12 24 0 Duct clearance 1 inch clearance for all sides of air supply duct 1 Units must be installed outdoors Over hanging structure or shrub...

Страница 8: ...supply air opening Bottom supply air opening Do not drill or install screw in this area Side return air opeing Bottom return air opening Bottom power entry 7 8 and 1 31 32 dia knockout Bottom control...

Страница 9: ...f second connection is not used 4 Use a sealing compound on male pipe threads Install the condensate drain line NPT to spill into an open drain A closed return duct system shall be used This shall not...

Страница 10: ...be kept clean When filter become dirt laden insufficient air will be delivered by the blower decreasing your units efficiency and increasing operation costs and wear and tear on the unit and controls...

Страница 11: ...it breakers installed within the unit do not provide over current protection of the supply wiring and therefore may be sized larger than the branch circuit protection Supply circuit power wiring must...

Страница 12: ...isconnect Field supplied disconnect T h r e e phase power supply Fig 6 2 Typical Field Power Wiring Diagram R G Y W C R G Y W1 W2 C 24 volt transformer THERMOSTAT UNIT CONTROL BOARD THERMINAL STRIP B...

Страница 13: ...ons 2 45A 1 08A 24 9A 048 4 0 208 230 3 60 13 7A 83 1A 060 5 0 21 4A 73A 10 4A 208 230 3 60 036 3 0 MCA 1 Amps Electric Heat Option Max Fuse 2 Breaker 3 Size Amps 16 3A Compressors each OD Fan Motors...

Страница 14: ...croll 1 spd Scroll 1 spd 1 1 1 y t i t n a u Q CONDENSER COIL DATA Face area Sq Ft 14 49 17 39 17 39 3 3 7 2 s w o R Fins per inch 20 20 20 Tube diameter 9 32 9 32 9 32 Circuitry type interlaced inter...

Страница 15: ...531 RPM 747 779 811 843 871 903 932 972 Watts 510 500 489 478 464 449 431 405 Amps 2 33 2 3 2 26 2 23 2 19 2 14 2 09 2 02 CFM L S 1837 868 1776 839 1724 814 1647 778 1576 744 1502 709 1413 667 1295 61...

Страница 16: ...1 1 46 1 41 1 34 1 29 CFM L S 1510 713 1468 693 1420 671 1369 647 1292 610 1218 575 1128 533 934 441 RPM 701 741 779 814 854 892 928 987 Watts 447 438 428 419 408 394 377 347 Amps 1 95 1 92 1 88 1 84...

Страница 17: ...410 434 457 105 200 219 239 258 278 293 308 335 362 385 408 431 454 MRB 36HWN1 X14B Cooling Mode Cooling Charge Chart Outdoor Ambient Temperature F High Pressure Detected Valve psig Vanne D tect de P...

Страница 18: ...ling Charge Chart Cooling Mode Outdoor Ambient Temperature F 60 62 64 66 68 70 72 74 76 78 80 82 135 333 340 347 354 361 370 382 390 398 406 414 426 128 325 332 339 346 353 360 376 383 390 397 404 416...

Страница 19: ...g Mode Outdoor Ambient Temperature F 60 62 64 66 68 70 72 74 76 78 80 82 135 341 353 364 376 388 400 404 408 414 420 426 432 128 337 349 360 372 384 396 400 404 408 412 416 428 121 329 340 351 362 373...

Страница 20: ...e compressor will be off When discharge temp is 194 F the compressor will start running High pressure protection When high pressure is 638PSIG the compressor and the outdoor fan motor will stop runnin...

Страница 21: ...FF Blower fan delay 90 sec OFF Compressor and outdoor fan instant OFF Heater 1 instant OFF 4 way valve instant ON Blower instant ON Compressor and outdoor fan instant ON Heater 1 instant ON Heater 2 i...

Страница 22: ...es 2 Turn thermostat setting above room temperature Unit should run in HEATING mode After unit has run for a while check the following 1 Are fans running properly 2 Is compressor running correctly 3 C...

Страница 23: ...N O G N I N R A W E B T S U M T E N I B A C Y L T N E N A M R E P O T G N I R I W L L A D N A D E D N U O R G O T M R O F N O C C E I C E N C E C D N A C L C E L B A C I L P P A S A S E D O C L A C O...

Отзывы: