5/29
STEP 6
– You can now power on the VIP5 and enter setup programming mode
When you turn on the device, you can check the firmware version loaded: rel. 3.00
Press and hold the
MODE
key for 5 seconds to the setup programming menu
The VIP5 will display the first parameter
LUBE Type
and the default value
SEP
Now configure the parameters
STEP 7
–
Select the type of system: SEP, TIMER, PS, DUAL
By default, the system will be configured a
SEP
Progressive controller.
To change the configuration press the
MODE
key for
per 5 seconds,
and use the arrow
UP
and
DOWN
keys to select the type of system parameter.
Select LUBE TYPE accounting to the type of system you have:
SEP
:
select this option for
PROGRESSIVE SYSTEM
with the end cycle switch ( eg. Dropsa
Ultrasensor). The VIP5 Controller will activate the pump and compete the cycle when the
cycle switch has changeover two times (0 -
> 1 -> 0, or 1 -> 0 -> 1)
.
The pump is then switched off until the next lubrication cycle.
DUAL
:
select this option for more complex
DUAL LINE SYSTEM
. You should refer to the
advanced setting in section 8.
TIMER
:
select this option when you have
NO CYCLE SENSOR
. The VIP5 Controller will
activate the pup for the duration of the
LUBE TIME
. After this, the pump is switched off
until next lubrication cycle.
PS
:
select this option when have a pressure switch configuration in a
33V INJECTOR
SYSTEM
. The VIP5 Controller will switch on the pimp and wait for pressure to be achieved. The
pup is the switched off until the next lubrication cycle.
When the correct type of system is selected, press
OK
key to set the next parameter.