SYSTEM MESSAGES 

The Control Panel will display the following messages based on system performance and environmental conditions. User 
action, if any is required, is indicated in the third column. 

 

C O N T R O L   P A N E L  

M E S S A G E

 

E X P L A N A T I O N

 

U S E R   A C T I O N

 

INITIALIZING 

Unit is powering up. 

None 

FIRMWARE VERSION 

XXX 

Indicates control board firmware version number. 

None 

FXXX-XXX 

Model number. 

None 

OFF 

Unit has finished powering up and is operating. 

None 

PLEASE WAIT 

COMP. DELAY XX 

60s delay before compressor turns on. Allows system 
pressure to equalize. 

None 

UNIT ON XXXX HRS 

INLET XXX°F / XX% 

First line: indicates total operating hours.  
Second line: Toggles between inlet temperature and in-
let RH every 2 seconds. 

None 

HUMIDISTAT 

INLET XXX°F / XX% 

First line: indicates unit is in humidistat mode  
Second line: Toggles between inlet temperature and in-
let RH every 2 seconds. 

None 

LOW TEMP 

INLET XXX°F/ XX% 

F515 only. Unit shuts off if inlet temp below 45° F. Turns 
back on when inlet reaches 50° F.  

None 

HI TEMP CYCLE 

REMAINING XX MIN 

Unit overload limit reached. Cool-down initiated. 

None 

--- 

DEFROST XX 

Unit is defrosting, with countdown in seconds. 

None 

WAIT FOR 

DEFROST XXX 

Unit turned off when coil is cold or already in a defrost 
cycle. Proceeds to finish cycle or initiate one to clear the 
coils of ice before storage. 

None 

WAIT FOR 

UNIT DRYING XXX 

Occurs when unit is turned off and coil is not frozen. 
Clears the coils of water before storage.  

None 

CLEAN FILTER > 

--- 

Prompt to clean or change filter. 

Change or clean filter. Press 
the > key to reset 

CLEAN COILS > 

--- 

Prompt to clean coils and interior. 

Clean coils. Press the > key 
to reset 

 
 

 

Содержание F571-115V

Страница 1: ...plug not the cord to unplug Insert three prong plug on power cord into a match ing electrically grounded outlet Do not use adapter Never cut off third prong Do not use an extension cord The unit must...

Страница 2: ...20 ft 6 m above the bottom of the unit Also check for kinks or other obstruc tions that might restrict the flow of water Obstructions may cause a water backup and result in overflows Plug in electrica...

Страница 3: ...he unit completes the compressor delay the display shows UNIT ON XX HRS and cycles between INLET XX F and INLET XX NOTE If no compressor delay countdown is displayed a delay is not necessary and the m...

Страница 4: ...T OUTLET 100 80 115 30 For information only 3 GRAIN DPR XX GPP XX X g kg for 230V models 4 FILTER CLEANED XXX HRS 5 FILTER CLEANED 0 HRS Press to clear filter hours 5 COIL CLEANED XXX HRS 5 COIL CLEAN...

Страница 5: ...ensure any water re maining on interior surfaces falls into the sump area 3 Press the PURGE key When the purge cycle is complete turn the unit off 4 Remove the external drain hose drain it carefully c...

Страница 6: ...ck valve and pump basin may need to be cleaned Remove grills and cover as shown in Fig B Remove screws from pump base and lift out pump Wipe out pump basin with a damp cloth Inspect the pump base for...

Страница 7: ...ture and in let RH every 2 seconds None HUMIDISTAT INLET XXX F XX First line indicates unit is in humidistat mode Second line Toggles between inlet temperature and in let RH every 2 seconds None LOW T...

Страница 8: ...or ER4 OUTLET SENSOR CONNECT Temp sensor is open missing or shorted Check that temp sensors are installed cor rectly on control panel If error persists contact service ER5 SENSOR CONNECTION ON BD Inl...

Страница 9: ...essary Check coils Clean as necessary If the problem you are experiencing is not listed here call your local distributor or contact our Service Department toll free at 800 932 3030 for further assista...

Отзывы: