aerosmart - Operation, Maintenance and Commissioning

Page 12  

Changing the Fine Particle Air Filter

The fi ne particle air fi lter is located in the outside air unit and not in the compact unit. De-
pending on the composition of the ventilation system, numerous fi lter types can be used. If 
the error message 'Change fi ne particle air fi lter' is displayed, replace the dirty fi ne particle 
air fi lter (within 2 - 4 weeks) with a new fi lter of the same 

type. For some 

fi lter types, the ventilation direction must be taken into 

consideration 

(marked by an arrow). The fi lter change must be ac-

k n o w l e d g e d 

on the controller. 

Acknowledge Fine Particle Air Filter 

Change to the Technician Level on the main menu of the control.
(The English text in the following tables is for representation only and will not be displayed 
on the control.)

 

 

b

<TECHNIKEREBENE>

Technician Level

Bitte beachten Sie

Please consider the

bei Aenderung die

manufacturers details

Herstellerangaben!

when making changes!

Press the '

' (up) arrow button once.

 

b

The operating hours counter for the fi ne particle air fi lter appears.
Press the 'Enter' button. 

<BETRIEBSSTUNDEN>

Operating Hours

FEINSTAUBFILTER

fi ne particle air fi lter

Summe: ######

sum

Reset: N

Reset: No

The cursor jumps to the  

'Reset' 

indicator.. 

 

b

Press an arrow button.
The 

'Reset': N 

indicator

 

changes to 

Y

 and the 

'Summe' 

indicator is set to zero.

 

b

Press '

' (Enter) to confi rm.

 

b

Note the fi lter change date in your in the logbook at the back of this manual.

Spare fi lter for the outside air system:

Please order the fi lters for the outside air system from your authorised technician 
directly.

y

,

p

y

type. Fo

consid
k n o w l

Fig.: 
Examples of 
external fi lters

Содержание aerosmart L

Страница 1: ...aerosmart S M L Operating Maintenance and Commissioning...

Страница 2: ......

Страница 3: ...__________________ 10 Safety Instructions for Filter Changes 10 Changing Coarse Particle Filters 10 Changing the Fine Particle Air Filter 12 Commissioning _____________________________________________...

Страница 4: ...quantity 120 m3 h Minimum air quantity 105 m3 h Maximum air quantity at 100 Pa external 180 m3 h Sound power level at nominal air quantity and 100 Pa external Housing 45 dB A Air inlet 37 dB A Air ve...

Страница 5: ...units are operated via a micro processor controller Although the unit types differ in terms of their appearance weight and managed air quantities these differences do not affect their operation Proper...

Страница 6: ...r Micro Processor Controller The micro processor controller is located on the ventilation module It manages the ven tilation room heating and the heating of the domestic hot water Alarm button this bu...

Страница 7: ...D BY SOMMER ventilation and heating are deactivated in this operating mode The heat pump and the two fans are only activated if the domestic water is heated An external switch can be used to switch on...

Страница 8: ...C dial fully to the left to 24 5 C dial fully to the right Note Do not turn the dial too far The left stop point is at approx 8 o clock the right hand stop point is at approx 4 o clock What room tempe...

Страница 9: ...edetermined period Once this period has passed the fan level automatically returns to the currently set level On delivery of the system the default period is 60 minutes but this can be adjusted on the...

Страница 10: ...umps to the Akt Sollwert b Use the and arrows to set your desired room temperature b Press Enter to save your settings What room temperature is right for me The setting basically depends on your needs...

Страница 11: ...vel On delivery of the system the default period is 60 minutes but this can be adjusted in the technician level Press Esc to go from the main display to the main menu Statusebene Technikerebene Herste...

Страница 12: ...oarse particle filter Note The filter should be changed within 2 4 weeks of the Filter change message appearing Safety Instructions for Filter Changes Caution The filter change intervals are only vali...

Страница 13: ...ivated b Unit starts automatically b After changing the filter press the Alarm button to acknowledge the Filter or Filter change message on the micro processor controller b Press Enter to confirm b No...

Страница 14: ...text in the following tables is for representation only and will not be displayed on the control b TECHNIKEREBENE Technician Level Bitte beachten Sie Please consider the bei Aenderung die manufacturer...

Страница 15: ...ime the controller initially performs a self test The main display then appears 12 11 DI 09 12 03 Time Weekday date AUTOMATIK automatic Akt Sollwert 21 5 C set point temperature Akt Raumtemp 20 3 C cu...

Страница 16: ...Raumtemperatur Current room temperature measured by the gauge in the ana logue room operating panel or in the external gauge housing Temp Boiler Unten Domestic water temperature in the lower region of...

Страница 17: ...berwachung The boiler is monitored for overheating Temperature above 68 C level 1 temperature above 73 C level 2 see error messages bertemperatur Boiler WP aus Excess tem perature boiler heat pump of...

Страница 18: ...t at 42 0 C domestic water heating is enabled as soon as the temperature in the lower area of the boiler actual value falls below this point On reaching 47 0 C i e 5 C above the set point the domestic...

Страница 19: ...achtabsenkung der Raumsolltemperatur This can be used to reduce the room set point temperature for a freely definable period of the day Default set point by up to 5 C Von Bis 22 00 6 00 Enter the time...

Страница 20: ...necessary to enter the nominal air quantity for fan level 2 The air quanti ties for levels 1 and 3 are automatically defined with 30 level 1 and 30 level 3 Timeframe for Fan Control There are two ava...

Страница 21: ...60 minutes values between 10 and 99 minutes can be entered Ein On Aus Off External Filters TECHNIKEREBENE Technician Level Aussenfilter Ja Outside air filter Yes Use this window to enter whether your...

Страница 22: ...EBSSTUNDEN Operating Hours Raumheizungsstufe 1 Room heating level 1 Summe 00000 STD Sum 00000 hours Reset N Reset No BETRIEBSSTUNDEN Operating Hours Raumheizungsstufe 2 Room heating level 2 Summe 0000...

Страница 23: ...nsor Tb Temperature on the heat pump evaporator register Tu Current temperature in the lower area of the boiler Depending on this temperature the heat pump is activated Tm Current temperature in the m...

Страница 24: ...e Enter button 2 sec please contact your customer service technician Blocktemperatur zu tief The following operating conditions are not permissible for the heat pump room temperature too low outside a...

Страница 25: ...he new value by pressing The following message appears DISPLAY ADDRESS CHANGED b The room operating panel now has the correct address and operates alongside the micro processor controller in the venti...

Страница 26: ...he unit to you with the following settings Please keep this data handy in case of queries Customer Location Unit type version Serial number Initially commissioned on Installation com pany Authorised t...

Страница 27: ...aerosmart Operation Maintenance and Commissioning Page 25...

Страница 28: ...rgieeffiziente haustechniksysteme gmbh Achstrasse 42 6922 Wolfurt T 05574 47895 0 F 05574 47895 4 E mail office drexel weiss at www drexel weiss at ATU 35542007 FN 192604t Company Accounts Registrar F...

Отзывы: