background image

- 10 -

 

 

2.3

 

PLUMBING FIXTURE 

Power water connects to pipes with ¾“ thread in the bottom part of the reservoir. Blue - cold 
water supply, red – hot water outlet. For potential disconnection of the tank, utility water inlets 
and  outlets  must  be  provided  with  Js  3/4“  screw  coupling.  The  safety  valve  is  mounted 
on the cold water inlet identified with a blue ring. 
 
Every hot utility water pressure tank shall be equipped with membrane spring loaded with safety 
valve.  Nominal  clearance  of  safety  valves  is  defined  by  standard.  Tanks  are  not  equipped 
with safety valve. Safety valve shall be easily accessible, fitted as close as possible to the tank. 
The inlet pipes must have at least the same clearance as the safety valve. Safety valve is placed 
high enough to secure dripping water drain by gravity. We recommend mounting the safety 
valve onto a branch pipe. Easier exchange without the necessity of draining water from the tank. 
Safety valves with fixed pressure settings from the manufacturer are used for the assembly. 
The starting pressure of the safety valve must be identical to the maximum allowed pressure 
of the tank, and at least 20 % higher than the maximum pressure in the water main (Table 4). 
If the water main pressure exceeds such value, a reduction valve must be added to the system. 
No closing armature may be mounted between the tank and the safety valve. During assembly, 
follow the guide provided by the safety equipment manufacturer. 
 
It is necessary to check the safety valve each time before putting it into operation. It is checked 
by manual moving of the membrane from the seat, turning the make-and-break device button 
always in the direction of the arrow. After being turned, the button must click back into a notch. 
Proper function of the make-and-break device results in water draining through the safety valve 
outlet pipe. In regular operation, such a check needs to be carried out at least once a month, 
and after each shutdown of the tank longer than 5 days. Water may be dripping off the drain 
pipe  of  the  safety  valve;  the  pipe  must  be  open  into  the  air,  pointed  down;  environment 
temperatures must not drop below zero. When draining the tank, use the recommended drain 
valve. First of all, close water inlet in the tank. 
 

Find necessary pressure values in the below Table 4. For proper safety valve operation, a backflow valve shall 
be  mounted  on  the  inlet  pipes,  preventing  spontaneous  heater  draining  of  the  tank  and  hot  water 
penetration back into the water main. We recommend that the hot water distribution from the tank was as 
short as possible to minimise heat losses. At least one demountable joint must be mounted between the tank 
and every supply pipe. Adequate piping and fittings with sufficiently dimensioned maximum temperature 
and pressure values must be used. 
 
 
 
 
 
 
 
 
 

Table 4 

 

SAFETY VALVE START-

UP PRESSURE [MPa]

 

ACCEPTABLE 

OPERATING OVER-

PRESSURE OF WATER 

TANK [MPa]

 

MAXIMUM PRESSURE 

IN COLD WATER PIPES 

[MPa]

 

0,6 

0,6 

to 0.48

 

0,7 

0,7 

to 0.56

 

to 0.8

 

Содержание OKC 400 NTRR/HP/SOL

Страница 1: ...ECT WATER TANKS OKC 400 NTRR HP SOL OKC 500 NTRR HP SOL Dru stevn z vody Dra ice stroj rna s r o Works Cooperative Dra ice Machine Plant Ltd Dra ice 69 294 71 Ben tky nad Jizerou tel 420 326 370 911 f...

Страница 2: ...FITTING INSTRUCTIONS 8 2 1 COMMISSIONING THE RESERVOIR 8 2 2 CONNECTING THE RESERVOIR TO HOT WATER DISTRIBUTION 9 2 3 PLUMBING FIXTURE 10 2 4 CONNECTION OF TANK TO HOT WATER DISTRIBUTION SYSTEM 11 2 5...

Страница 3: ...onsible person or unless properly instructed by such responsible person The manufacturer reserves the right for engineering modification of the product The product is designed for permanent contact wi...

Страница 4: ...heating circuit lower tubular heat exchangers is designed for solar system The tank is placed on the ground next to the heating water source or in its vicinity All connecting distributions must be pro...

Страница 5: ...SURE IN THE VESSEL MPa 1 MAXIMUM OPERATING OVERPRESSURE IN THE EXCHANGER MPa 1 MAXIMUM HEATING WATER TEMPERATURE C 110 MAXIMUM OPERATING TEMPERATURE IN THE VESSEL C 80 HEATING SURFACE OF UPPER LOWER E...

Страница 6: ...KC 400 NTRR HP SOL Figure 1 Table 2 OKC 400 NTRR HP SOL A 1644 B 812 C 857 D 700 E 55 F 1521 G 973 I 723 J 288 L 208 M 648 N 812 O 1348 P 355 R 1073 S 1173 1 outer 3 4 inner 5 4 inner 1 2 inner 6 4 in...

Страница 7: ...KC 500 NTRR HP SOL Figure 2 Table 3 OKC 500 NTRR HP SOL A 1914 B 812 C 857 D 700 E 55 F 1790 G 1023 I 773 J 288 L 228 M 609 N 818 O 1618 P 473 R 1123 S 1409 1 outer 3 4 inner 5 4 inner 1 2 inner 6 4 i...

Страница 8: ...he way in first the operating and then the safety thermostat b open the hot water valve on the combination faucet c Open the cold water inlet valve to the tank d when the water starts flowing through...

Страница 9: ...ssel The safety valve does not replace the safety valve on the cold water inlet No closing return armature and filter may be mounted between the heater and the safety valve T fixtures with discharge v...

Страница 10: ...e guide provided by the safety equipment manufacturer It is necessary to check the safety valve each time before putting it into operation It is checked by manual moving of the membrane from the seat...

Страница 11: ...way valve backflow flaps and the exchanger from sedimentation It is recommended to flush the heating circuit before the assembly All wiring connections must be properly insulated from heat If the sys...

Страница 12: ...rease the temperature of hot service water HSW periodically for a transitional period of time to at least 70 It is also possible to make use of another way of disinfecting HSW PROCEDURE OF EXCHANGING...

Страница 13: ...t the receptacle s flange connection nuts are tightened 3 2 INSTALLATION REGULATIONS Both the electric and water installation must follow and meet the requirements and regulations relevant in the coun...

Отзывы: