Positioning the HTS3

The HTS3 should be installed approximately one

third of the way up the hot water cylinder, and at

the front for ease of access.With pre-insulated

cylinders, mark the position and size, and remove

just enough insulation to allow the HTS3 to

t

against the metal of the cylinder in the recess

formed.

Wiring Connections

From the wiring centre or junction box, run

suf

cient 3-core electrical connecting cable to

reach the HTS3 installation position without being

under tension.

Remove the HTS3 cover by undoing the

central retaining screw. Make wiring connections in

accordance with the diagram below and the

manufacturers instructions for associated

equipment such as motorised valves, boiler,

programmers etc. Replace and secure the cover.

The HTS3 is double insulated and no Earth

connection is necessary.The circuit should be

protected with a 3A fuse.

Fixing to the Cylinder

The base of the HTS3 should be held in good

contact with the metal of the hot water cylinder.

The plastic covered spring

xing cable should

be cut to an unstretched length of

approximately 2 1/2” – 3” less than the

circumference of the cylinder and the hook and

eyelet screwed into the ends. Stretch the cable

round the cylinder, above the insulation, and

position it in the groove across the front of the

HTS3. Engage the hook and eyelet.

Common

heat

Satisfied

Cylinder

Insulation

Fixing cable

HTS3

cylinder

HTS3

height

Commissioning

The two setting marks outside the

temperature scale on the HTS3 provide max

temperature and OFF positions to assist with

commissioning or checking the system

operation. Rotate the setting arrow fully max

and anticlockwise for OFF.

Setting

With a screwdriver, position the setting arrow

at the desired nominal hot water temperature.

A popular setting is 60°C but if this is not

exactly suitable, simply adjust up or down as

appropriate.

WARNING

Disconnect mains supply before

tting or removing the cover.

A switch having contact

separation of at least 3mm in all

poles must be incorporated in the

xed wiring as a means of providing

full disconnection of the mains

supply.