background image

E

NCORE

 S

ERIES

TM

 

61000 System

INSTALLATION GUIDE

DRANETZ - BMI
1000 New Durham Road
Edison, New Jersey 08818-4019

Содержание Encore 61000

Страница 1: ...ENCORE SERIESTM 61000 System INSTALLATION GUIDE DRANETZ BMI 1000 New Durham Road Edison New Jersey 08818 4019...

Страница 2: ...ety training on the hazards involved Qualified personnel who work on or near exposed energized electrical conductors must follow applicable safety related work practices and procedures including appro...

Страница 3: ...iquement par un personnel qualifi Selon le National Electrical Code une personne est qualifi e si elle conna t bien la construction et l utilisation de l quipement ainsi que les dangers que cela impli...

Страница 4: ...anual Direct current DC operation of the terminal or device Power Switch Definiciones Las ADVERTENCIAS informan al usuario de ciertas condiciones o pr cticas que podr an producir lesiones mortales o d...

Страница 5: ...ent ce manual Fonctionnement du terminal ou de l unit en courant continu CC Interrupteur de tension Definitionen WARNUNGEN informieren den Benutzer dar ber da bestimmte Bedingungen oder Vorgehensweise...

Страница 6: ...use inspect all cables for breaks or cracks in the insulation Replace immediately if defective Set the 61000 power switch to Off Before connecting to electric circuits to be monitored open their relat...

Страница 7: ...ssumed for any inaccuracies All material is for informational purposes only and is subject to change without prior notice Notice regarding FCC compliance This device has been tested and found to compl...

Страница 8: ...r translated into any language or computer language in any form by any means electronic mechanical magnetic optical chemical manual or otherwise without the prior written consent of Dranetz BMI 1000 N...

Страница 9: ...rent Input Pods 2 22 Connecting Digital Input Connectors 2 24 CHAPTER 3 Circuit Diagrams for Power Monitoring Connecting Power to the Voltage Current Connections 3 1 Single Phase 3 6 Split Phase 3 7 3...

Страница 10: ...Accessories List A 2 Enclosure Hardware Options A 5 Software Accessories A 7 APPENDIX B Technical Specifications General Specifications B 1 Interfaces B 2 Measurement Parameters B 3 APPENDIX C Connec...

Страница 11: ...xi Dranetz BMI Encore SeriesTM 61000 System...

Страница 12: ......

Страница 13: ...on module connected to the Encore Series Software Local operation with optional user interface As a stand alone unit the 61000 can be outfitted with optional liquid crystal display LCD as user interfa...

Страница 14: ...cept of separating the various stages of acquisition characterization communications and visualization with clearly defined interfaces that decouple one from the other The instrument can monitor power...

Страница 15: ...Customer Service Department can be reached at 732 287 3680 or 1 800 372 6832 Repacking for return shipment If the unit must be returned to Dranetz BMI for service or repair wrap the unit securely in h...

Страница 16: ...x B External dc power source To connect to an external dc power source refer to Appendix C Encore Series 61000 firmware upgrade Refer to Appendix D for instructions on how to upload the latest availab...

Страница 17: ...weighs 5 pounds and has an 8 depth Optional display panel The optional user interface is a 1 4 VGA LCD panel with touch screen menus for local operation and configuration Connector panel The backplan...

Страница 18: ...1 6 This page intentionally left blank...

Страница 19: ...61000 front panel display may look different depending on the enclosure options specified Front panel without the local LCD User Interface See below for description of the 61000 front display without...

Страница 20: ...ic data entry and has a compact fluorescent CCFL backlighting that is on for low light level viewing The following are some basic care instructions for the LCD monitor Use and store the unit within th...

Страница 21: ...leave adequate working space for rear panel connections to the 61000 This rear clearance space is necessary for proper installation of the measurement cables probes and pods as well as external commu...

Страница 22: ...tated on the unit nameplate can cause damage to the unit PRECAUCION Siempre fije el interruptor de encendido en la posici n apagada antes de conectar o desconectar el cable de energ a de entrada La op...

Страница 23: ...Push for on push for off NOTE The on off power switch shuts the unit down but allows the battery to continue to charge even with the switch in the Off position 3 Power input decal and connector The d...

Страница 24: ...ut decal Note For source voltages outside the range of the unit a Phase Power Adapter is available as an optional accessory It converts the selected source voltage to the output voltage needed to oper...

Страница 25: ...data and information collected by the 61000 WARNING To avoid the risk of electric shock do not remove communications instrument until all power is de energized to all power and measurement circuits A...

Страница 26: ...n of the external communications device and software applications necessary for remote computer operation of 61000 Part Function 1 10 100BaseT RJ45 Allows connection via Ethernet cable 2 USB Not activ...

Страница 27: ...MDOH and 61MDOL Transducer input module Models 61MXVS and 61MXAS can record and trigger on analog signal levels in either the 0 24V and 4 20mA range respectively Input channels Input channels for the...

Страница 28: ...o del empleado ANSI NFPA 70E 2004 de los E E U U y cualquier requisito de seguridad adicional del lugar de trabajo aplicable a su instalaci n AVERTISSEMENT Si l instrument est mal connect la mort des...

Страница 29: ...gener Arbeit Praxis und Verfahren einschlie lich passende pers nliche sch tzende Ausr stung gem dem Standard f r elektrische Sicherheitsauflagen f r Angestellt Arbeitspl tze ANSI NFPA 70E 2004 der Ver...

Страница 30: ...le see Appendix A Optional Accessories but are not shown in photo Parts table Continued on next page Part Function 1 AC Voltage Module with Safety Jack Connectors Model No 61MVB 1 1 CH A Differential...

Страница 31: ...n line connection See page 2 15 for more information voltage cable connections Current Probes for Current Input Module Model No 61MAC A variety of current cables and probes are available for connectin...

Страница 32: ...urrent input pod connection The next pages describe the possible voltage and current assembly connections to the input connectors in the rear panel of 61000 NOTE VOLTAGE AND CURRENT PROBES ARE NOT SHO...

Страница 33: ...e red and black for each of the four channels One cable each of red channel A yellow channel B blue channel C and grey channel D and four each of white are provided A pouch for storage of the cables a...

Страница 34: ...st risk of fire or shock hazard replace only with same type and rating of recommended fuse Use only fast blow type fuse which is rated 600V Recommended fuse type is Littelfuse part number KLKD0 30 rat...

Страница 35: ...dules one for single phase voltage connections designated VOLTAGE INPUTS CH D the other for three phase connections designated VOLTAGE INPUTS CH A CH B CH C See the voltage cable connections diagram b...

Страница 36: ...nstance TR25xx clamp on current probes that provide a broad range of current measurements Multiple probes and adapter cables that are currently used with Dranetz BMI equipment i e Flex Core models and...

Страница 37: ...ction Current probes TR2500 can be used interchangeably with TR2500A TR2510 with TR2510A and TR2520 with TR2520A Refer to Appendix A for descriptions and part numbers of probes and adapter cables Refe...

Страница 38: ...les noyaux courants non isol s de sonde autour d un fil non isol Des sondes de ce type sont concues pour l usage autour des fils isol s seulement L utilisation seulement a compl tement isol des noyaux...

Страница 39: ...ed to measure the return current when checking for load current leakage loop current relationships etc If measuring power position the probe with the arrow pointing towards the load Note The connectio...

Страница 40: ...tively to the same Voltage Current Input Module Model No 61MZP with 25 PIN interface cable connector The inputs are attenuated to low voltage signals that can be measured by the 61000 Pod assembly dia...

Страница 41: ...terface cable connector Part Function 1 Voltage Module Accepts four 5 600 Vrms AC or DC 1000 Vpk channels A B C voltage plus neutral and ground Neutral to ground voltage range 0 5 20 Vrms AC or DC 2 C...

Страница 42: ...elow 1 0 volts Maximum input signal level is 135Vac or 200Vdc If the inputs are configured for AC instead of DC signals it is the rms value of the ac signal that is used to determine the state This wi...

Страница 43: ...Death serious injury or fire hazard could result from improper connection of this instrument Read and understand this manual before connecting this instrument Follow all installation and operating ins...

Страница 44: ...de trabajo del empleado ANSI NFPA 70E 2004 de los E E U U y cualquier requisito de seguridad adicional del lugar de trabajo aplicable a su instalaci n AVERTISSEMENT Si l instrument est mal connect la...

Страница 45: ...ogener Arbeit Praxis und Verfahren einschlie lich passende pers nliche sch tzende Ausr stung gem dem Standard f r elektrische Sicherheitsauflagen f r Angestellt Arbeitspl tze ANSI NFPA 70E 2004 der Ve...

Страница 46: ...re making any other connections WARNING To reduce the risk of fire electrical shock or physical injury it is strongly recommended to fuse the voltage measurement inputs Fuses must be located as close...

Страница 47: ...n accordance with good practice and local codes Connect the ground wire first before making any other connections Connect power source to the Voltage and Current Input Modules Attach phase A B and C v...

Страница 48: ...with all safety requirements applicable to your installation NOTE Connections of CT leg to ground is recommended but not required for proper operation SF 301 LINE LOAD A N Fuses Switchgear Chassis Gr...

Страница 49: ...d in compliance with all safety requirements applicable to your installation NOTE Connections of CT leg to ground is recommended but not required for proper operation LINE LOAD A B N Fuses Switchgear...

Страница 50: ...ormed in compliance with all safety requirements applicable to your installation NOTE Connections of CT leg to ground is recommended but not required for proper operation LINE LOAD A B C N Fuses Switc...

Страница 51: ...ust be performed in compliance with all safety requirements applicable to your installation NOTE Connections of CT leg to ground is recommended but not required for proper operation LINE LOAD A B C Fu...

Страница 52: ...performed in compliance with all safety requirements applicable to your installation NOTE Connections of CT leg to ground is recommended but not required for proper operation LINE LOAD A B C Fuses Sw...

Страница 53: ...Delta CAUTION Connections must be performed in compliance with all safety requirements applicable to your installation NOTE Connections of CT leg to ground is recommended but not required for proper o...

Страница 54: ...a CAUTION Connections must be performed in compliance with all safety requirements applicable to your installation NOTE Connections of CT leg to ground is recommended but not required for proper opera...

Страница 55: ...the 61000 can have a maximum of 4 modules with separate and independent connection for each input output module The user can configure up to four virtual analyzers depending on module types installed...

Страница 56: ...transformer PT Scale factors are entered into the 61000 from the Encore Series Software or local user interface and then multiplied automatically by the measured voltage and current so that the correc...

Страница 57: ...decide if an event occurs For example on a circuit with a nominal voltage of 120V rms the high and low limits could be set to 132V and 108V respectively If the input voltage exceeds 132V rms or falls...

Страница 58: ...backup 61000 uses an internal 4M non volatile flash memory for program storage Data will not be lost if the battery pack is removed Flash memory data storage The 61000 hardware has a flash memory sto...

Страница 59: ...is using Ethernet the computer must likewise be using Ethernet Communications interface There are five types of connectors in the rear panel of the 61000 for remote comunication to a computer RJ 45 f...

Страница 60: ...61MDM external modem is available in Dranetz BMI as an optional accessory for the 61000 Modem communication is also possible through an optional GSM service for wireless communication This service is...

Страница 61: ...ector into the COM 1 RS232 port located on the rear panel of the 61000 Connect the other end of the RS232 connector to any available serial COM port on your computer The COM 1 RS232 port can also be u...

Страница 62: ...ing 100 feet may result in undesired interference Shielded cables and shielded connectors must be used when connecting external devices to the GPS antenna port of the 61000 Reference guide Remote oper...

Страница 63: ...ault Reference guide Refer to the 61000 Optional User Interface Guide check with Dranetz BMI for availability for detailed instructions on how to set up and operate the 61000 with the LCD panel Safety...

Страница 64: ...ppropriate outlet Turn on procedure Follow these steps to turn on the 61000 and display the Home screen Home screen is frequently referenced as the starting point for all major functionalities of 6100...

Страница 65: ...the instrument and the Dranetz BMI software applications used to download and view event data in a computer Ordering information To order accessories contact Dranetz BMI Customer Service Department a...

Страница 66: ...pe CTs contact the Dranetz BMI factory 3PHASEFLEX RR 3035A 24 RR 3035A 36 RR 3035A 48 RR 6035A 24 RR 6035A 36 RR 6035A 48 Clamp On AC Probes Current Probe Assembly 1 to 300A RMS Current Probe Assembly...

Страница 67: ...kage LF PSP Input Ouput Modules Input Module 600V Safety Connectors 61MVB Input Module Voltage Current External Pod 61MZP Input Module 600V Screw Terminals 61MVS Input Module Current Probe Interface 6...

Страница 68: ...ttery 61PSDC SB Power Supply 48 VDC Input 61PSDC 48 Mainframes 61000 Series Mainframe with Overlay 61STD 61000 Series Mainframe without Overlay 61ST Host Modules Host Comm Module with GPS 61HCG Host C...

Страница 69: ...IX A Optional Accessories Enclosure Hardware Options Rack Mount Panel with Display Diagram below shows the rack mount panel with provision for optional screen display P N 61RMTD showing distance speci...

Страница 70: ...gram below shows the rack mount enclosure without provision for screen display P N 61RMT in unassembled view Rack mount panel and handle facing back Diagram below shows the same rack mount enclosure a...

Страница 71: ...ion of 61000 The user inteface is a conventional Internet browser with access restricted only to authorized users The Encore Series Software program requires that the proper Dranetz BMI computer hardw...

Страница 72: ...A 8 This page intentionally left blank...

Страница 73: ...non condensing Altitude 2000m 6560 ft maximum System Time Clock Crystal controlled 1 second resolution for display Event time clock displays to 1 msec resolution Time displayed in analog or digital 12...

Страница 74: ...rystal Display LCD with compact fluorescent CCFL backlighting Programmable backlight time out to reduce power consumption Reactivates with touch Resolution 360 x 240 dot matrix Viewing Area 3 75 x 4 7...

Страница 75: ...rations Crest factor Maximum 2 0 at full scale RMS accuracy 0 1 of Reading 0 05 Full Scale over 7KHz bandwidth 1 second rms readings for low medium frequency module 0 1 of Reading over the nominal ope...

Страница 76: ...s A B C D Input Range 1 5V rms Connection Hypertronics connectors to interface to TR25xx clamp on current probes Model 61MAC Flex core models via external cable adapter Hall effect probe models via ex...

Страница 77: ...ading 0 05 Full Scale plus transducer accuracy Digital Input Type Digital Input Module Model 61MDIN Connectors Phoenix connector type with screw terminal Digital Input Range High state 3 Vdc Low state...

Страница 78: ...B 6 Measurement Parameters continued Digital Ouput continued Type Digital Output Module Model 61MDOL Contact Form C Voltage Type AC DC Max Voltage 25 Vpk Max Current 0 1A Response Time 2 msec...

Страница 79: ...conexiones incorrectas Siempre observe la polaridad correcta Efect e primero las conexiones al 61000 y luego haga las conexiones a la fuente de energ a de corriente continua externa AVERTISSEMENT Des...

Страница 80: ...h den am Ger t kommen Vor dem Fortfahren berpr fen ob alle Anschl sse ordnungsgem vorgenommen wurden External power source The external power source is 12Vdc Connecting the cable Follow these steps wh...

Страница 81: ...and the computer connecting to the IP address provided by Dranetz BMI uploading the firmware to the unit verifying firmware update and preparing the Encore Series Software for monitoring Follow the i...

Страница 82: ...the IP field 2 3 Type in 255 255 255 0 in the Network Mask field 2 4 Click on the Set button 2 5 The following message is displayed under Select a Unit window if the procedure was done correctly MOD52...

Страница 83: ...ocedure continued 3 2 After typing in the user name and password click on the OK button The Summary Information screen will appear 3 3 Click on the icon found on the left side bar The Factory Debug Op...

Страница 84: ...tion to open the Firmware Upload screen shown below 3 5 Select the Host Module radio button and click on Continue to proceed The following screen will appear 3 6 Select the file to upload Click on Bro...

Страница 85: ...page is displayed repeat the process from Step 3 1 NOTE If several attempts fail turn the power switch OFF then turn back ON and repeat the process from Step 3 1 3 10 If the file was loaded properly...

Страница 86: ...select filename MeasCode b4u from the files supplied by Dranetz BMI 3 15 When done selecting the file to upload click on Continue and wait until the following screen appears 3 16 Click on Continue to...

Страница 87: ...The Factory Debug Options screen will appear 3 20 Click on the Upload Firmware option and the following screen will appear 3 21 Select the Communications Module radio button and click on Continue to p...

Страница 88: ...rogram to exit STEP 4 Verify the firmware update 4 1 Restart the unit by turning the power switch to OFF then turn back to ON 4 2 The Status LED should blink every 16 seconds if the firmware upload pr...

Страница 89: ...ate and time should indicate the actual time and date when the firmware was updated 4 5 Click on the icon found on the left side bar and then select Dump the Input Module 1 The following screen will a...

Страница 90: ...ress bar Press return and the following screen will appear Type in admin for User name and password for Password NOTE Use lowercase characters when entering user name and password 5 2 Click on OK and...

Страница 91: ...me and password Click to open the Setup tab Scroll down to DataNodes folder and select 61000 Power Quality DataNode Right click to display the Add Datanode command Click to add DataNode1 where a setup...

Страница 92: ...D 12 This page intentionally left blank...