Quick Reference Guide for PowerXplorer / Power Guide / Power Visa
pg 28
Example of Power Quality setup using the Wizard
Current Probe
Select the current probes you are going to use from the list. If you are using LEMFlex make sure the
probe and list match exactly. Full scale current should not exceed probe rating and nominal current
should not be less than 10% of full scale.
Scale Factors
Set Scale factors if working with the secondary of PTs or CTs. If your Probe is in the list and selected,
Amps Scale Factor should be 1 if not connected to a secondary of another CT.
Circuit Type
Select the circuit type. If you see a mismatch while connected you may not be connected properly or
your current probes are reading <10% of full scale or could be V or I imbalance. You can choose to
override and monitor anyway although not recommended if connection is wrong.
Nominal Values
If connected the unit will show values it is reading. If you are not connected, then you can set your values
by pressing the blue bordered box.
Mode of Operation
Select
Continue
Monitoring Mode
Select
Standard Power Quality
Advanced Options
Six Sub-categories
1) Transient – Leave defaults as long as Nominal Values were correct.
2) RMS Variation – Leave defaults as long as Nominal Values were correct.
3) Waveform Capture – Easiest thing to do is set all boxes with a check mark.
4) Characterizer Options – Verify IEEE 1159.
5) Journal Limit – Select
Disable
, then disable All
Note that this will disable alarming functions on the annunicator panel status report. Activate only
those that you specifically need.
6) Journal Interval – Leave defaults.
Memory Card
Name your survey. The Site Name will be your data file name. Format your memory card as long as
other data files are saved on your PC.
Finish
then
Start Now.
Example of Energy/Demand setup using the Wizard
Same as above, except:
Monitoring Mode
Select
Long Term Timed
Advanced Options
Select
Journal Limits
, then
Disable ALL
. Note that this will disable alarming functions on the annunicator
panel status report. Activate only those that you specifically need.