13. Alarm relay
13.1. Settings
Select the symbol ALARM in the main menu.
In the submenu, select the symbol SETTINGS.
Here you can set the following parameters:
Delay
This defines a delay time
– in case of an event, the alarm relay switches only after a
specified interval. Display of the text message on the desktop and output of 22mA
error current are not affected by this setting and will occur immediately.
Function
Here you can turn the normally open contact into a normally closed contact. That
means that the relay is actively closed in case of normal operation and opens in case
of alarm
– with the advantage that power failure also leads to an alarm.