46
The Provisioning > Analogs menu
Basic Analog Configuration
ID
Analog ID number.
Enab
Check this box to enable the analog.
Description
User-definable description for the analog channel.
Notification Devices
Check which notification device(s), 1 through 8, you want to send alarm
notifications for that alarm point.
Advanced Analog Configuration (Details>>)
Record Freq
The amount of time, in minutes (min) or seconds (s), between each log of
each analog value to history.
Deadband
The amount (in volts) that the channel needs to go above or below a
threshold in order to cause an alarm.
On Set
User-definable description (condition) that will appear for the temperature
alarm on Set. Example: "Alarm".
On Clear
User-definable description (condition) that will appear for the temperature
alarm Clear. Example: "Alarm Cleared".
Qual. Time
(Qualification Time)
The length of time that must pass, without interruption, in order for the
condition to be considered an Alarm or a Clear.
Qual. Type
(Qualification Type)
Allows you to choose whether you want to apply the Qualification Time to the
alarm Set, Clear, or Both.
Units
User-definable display units or optional choice between Fahrenheit and
Celsius temperatures. The most common are:
VDC = Voltage
%H = Humidity
F = Fahrenheit
C = Celsius