5. By default, all jumpers are in the unjumpered/open position, which corresponds to voltage
operation, as shown in figure above. To reset an analog alarm input to current operation, reset its
jumper in the closed position.
Note:
Each jumper inserts a 250-ohm shunt resistor across the input. This must be taken into
account when defining the analog input reference scale.
6. Slide the top cover of the case back into position and replace the screws.
7. Reconnect and power up the RPS AB6.
D-Wire Sensor Input
4.3
The port on your RPS AB6 labeled, "
D-Wire
" supports the connection of up to
16 D-Wire sensors
. The
RPS AB6 powers and communicates with your D-Wire sensors via straight-through RJ-11 cables.
Connecting D-Wire Sensors
Using a
6P4C,
straight-through RJ-11 cable
(part #D-PR-045-10A-01, pinout below), connect the D-
Wire sensor port on the RPS AB6 to the
In
jack on a D-Wire sensor. Chain additional sensors to the
RPS AB6 (using the same straight-through cables) from the
Out
jack on the previous sensor to the
In
jack on the next (i.e. Out on sensor 4 to In on sensor 5).
Pinout for D-Wire RJ-11 jacks
For details about configuring your sensors though the web interface, see the
Provisioning > Sensors
section of this manual.
Control Relay Connectors
4.4
The RPS AB6's control relay inputs
A 6-pin connector for two control relays is located on the RPS AB6's back panel.