DPS Telecom NIA Card Скачать руководство пользователя страница 3

June 14, 2002

UM026.14100

www.dpstele.com

(800)622-3314

NIA Configuration

1.

Before configuration can begin, power must be connected to the main KDA shelf.

2.

Connect a DB9 download cable to the female DB9 C1.

3.

Connect the other end of the DB9 cable to a PC running terminal emulation software.

4.

Set your computer’s serial port to match the NIA card’s default data rate and word format settings (9600 N, 8, 1). In
your terminal emulation software, be sure to set the Flow control to “None.”

5.

Press and hold the “MOD” button on the front panel of the NIA card. As you hold the button down, insert the fuse into
the front panel. Continue holding the “MOD” button until the front panel LEDs stop flashing (approx. 10 seconds).

6.

When a connection is established, hit any key to bring up the first configuration menu. 

IP Address

1.

To edit the IP Address information, type “E” for E)dit and then “I” for I)P Parameters.

2.

Enter the IP Address, the Subnet Mask, and Default Gateway.

NIAT v2.2F Configuration
E)dit  W)rite  e(X)it ? E

I)P Parameters  P)ass-thru Port ? I

Unit Address :126.010.230.102
SubNet Mask

:255.255.255.000

Default Gateway

:126.010.230.001

U)nit Address  S)ubnet Mask  D)efault Gateway ?

Pass-thru Port

1.

To edit the Pass-thru Port information, type “E” for E)dit and then “P” for P)ass-thru Port.

2.

Type “P” to set the P)rotocol (either Telnet or UDP).

3.

Type “B” to set the B)aud rate (300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, or 115200).

4.

Type “M” to set the Pro(m)pt configuration. This will toggle between yes and no. Yes means a prompt will appear
when you connect to the NIA and no means that no prompt will appear.

NIAT v2.2F Configuration
E)dit  W)rite  e(X)it ? E

I)P Parameters  P)ass-thru Port ? P

Protocol

:UDP

Baud Rate

:9600

Prompt

:YES

P)rotocol  B)aud  Pro(m)pt ?

Writing to the NIA

1.

To write the configuration information to the NIA, type “W” for W)rite from the main menu.

NIAT v2.2F Configuration
E)dit  W)rite  e(X)it ? W

Содержание NIA Card

Страница 1: ...r 19 or 23 equipment racks while occupying only one rack unit of space 19 or 23 Rack 5 Projection 19 or 23 Rack Flush Front 19 or 23 Rack 5 1 2 Projection 19 or 23 Rack 1 2 Projection SIDE VIEW REAR NOTE Use wide ears for 23 19 or 23 Rack 7 Projection Mounting Instructions The unit can be mounted in a 19 or 23 rack by using the reversible rack ears for either size provided Several rack ear locatio...

Страница 2: ...ed with the unit connect black to GND and red to BATT Standard gauge is 20AWG which varies from 18 24AWG 5 4 3 2 1 9 8 7 6 DSR GND RX TX RTS CTS Female PIN Signal Description 1 2 3 4 5 6 7 8 9 NC TX RX DSR GND NC CTS RTS NC Not connected Transmit data Receive data Data set ready Ground Not connected Clear to send Request to send Not connected 1 2 3 4 5 6 7 8 9 DSR GND RX TX RTS CTS Male PIN Signal...

Страница 3: ...type E for E dit and then I for I P Parameters 2 Enter the IP Address the Subnet Mask and Default Gateway NIAT v2 2F Configuration E dit W rite e X it E I P Parameters P ass thru Port I Unit Address 126 010 230 102 SubNet Mask 255 255 255 000 Default Gateway 126 010 230 001 U nit Address S ubnet Mask D efault Gateway Pass thru Port 1 To edit the Pass thru Port information type E for E dit and then...

Страница 4: ... that allow users to monitor larger more complicated networks with a smaller less trained staff Your Partners in Network Alarm Management www dpstele com 4955 E Yale Avenue Fresno CA 93727 559 454 1600 800 622 3314 559 454 1688 fax ...