55
Basic Sensor Configuration
ID
Sensor ID number.
ROM ID
The ID number found on the sticker of the temperature sensor node. Your
NetGuardian will automatically detect the sensor ID when you plug a sensor into the
unit. The color of the sensor ID field will tell you the status of the connected sensor.
Green
- The sensor is connected and properly configured.
Yellow
- The sensor is connected but has not yet been configured (fill in your
configuration fields and click
Save
to configure the sensor).
Red
- The sensor is not detected and configured (i.e. a previous configured sensor is
no longer connected).
Blue
- The sensor is not supported by the NetGuardian.
To reconfigure or disable the Sensor ID, simply delete any data in this field and click
Save
.
The unit will refresh the sensor ID on that channel.
Description
User-definable description for the sensor channel.
Notification Devices
Check which notification device(s), 1 through 8, you want to send alarm notifications
for that alarm point.
Advanced Sensor Configuration (Details>>)
Record Freq
The amount of time, in minutes (min) or seconds (s), between each recorded sensor
value.
Deadband
The amount (in native units) that the channel needs to go above or below a threshold
in order to cause an alarm.
On Set
User-definable description (condition) that will appear for the temperature alarm on
Set. Example: "Alarm".
On Clear
User-definable description (condition) that will appear for the temperature alarm Clear.
Example: "Alarm Cleared".
Qual Time (Qualification
Time)
The length of time that must pass, without interruption, in order for the condition to be
considered an Alarm or a Clear.
Qual. Type (Qualification
Type)
Allows you to choose whether you want to apply the Qualification Time to the alarm
Set, Clear, or Both.
Thresholds
These settings are set to indicate the severity of the alarm depending on which
threshold values have been passed. Enter values for Major Under (MjU), Minor Under
(MnU), Minor Over (MnO), and Major Over (MjO).
Analog Gauge Type
Select the color-coded gauge that best represents your data. Selecting
None
will
disable the analog gauge and only a numerical representation of the value will be
displayed under
Monitor
>
Sensors
.
Note:
Before plugging in any additional D-Wire Sensors, set up the internal sensor.
Содержание D-PK-C16V2
Страница 5: ...Technical Support 18 82 End User License Agreement 19 83...
Страница 6: ......
Страница 15: ...9 Amphenol connector pinout...
Страница 17: ...11 Optional 66 block connector pinout for controls...
Страница 51: ...45 The Provisioning Phone List menu...
Страница 53: ...47 you will have to enter the relevant authentication information the fields below...
Страница 90: ...84...
Страница 91: ...85...
Страница 92: ......