Q. How can I associate descriptive information with a point for the RTU granular traps?
A.

The BVM 48 alarm point descriptions are individually defined using the Web Browser.

Q. My SNMP traps aren't getting through. What should I try?
A.

Try these three steps:

1. Make sure that the Trap Address (IP address of the SNMP manager) is defined. (If you changed

the Trap Address, make sure you saved the change to NVRAM and rebooted.)

2. Make sure all alarm points are configured to send SNMP traps.
3. Make sure the BVM 48 and the SNMP manager are both on the network. Use the unit's ping

command to ping the SNMP manager.

Содержание BVM 48

Страница 1: ...USER MANUAL BVM 48 October 21 2011 Visit our website at www dpstelecom com for the latest PDFmanual and FAQs D OC UM103 05100 Firmware Version 1 0A...

Страница 2: ...rivative work by either mechanical electronic or any other means in whole or in part without prior written consent fromDPS Telecom except as required by United States copyright laws The material in th...

Страница 3: ...k Start How to Connect to the BVM 48 8 10 via Craft Port using TTY Interface 8 1 10 via LAN 8 2 12 TTY Interface 9 13 Set DCP Parameters 9 1 13 Calibrating Battery Harness 9 2 14 BVM Web Browser 10 14...

Страница 4: ...Monitoring User Analogs 12 10 2 36 Monitoring Battery Strings 12 10 3 37 Firmware Upgrade 13 38 Reference Section 14 39 Front and Back Panel LED 14 1 39 Display Mapping 14 2 40 System Alarms Display...

Страница 5: ...ipment wiring and tools for damage prior to use Be aware of unsafe wiring conditions Do not work with exposed electrical equipment in wet or damp areas where risk of electric shock is greatly increase...

Страница 6: ...s and offers both instant readings and trending to track battery voltages over time Monitors 24 individual cell voltages Reports threshold events on a threshold basis to your SNMP manager Built in web...

Страница 7: ...uld occur without the external harness and could void your warranty Contact DPS Telecom support team if you require assistance regarding the battery harness options Protocols SNMPv1 SNMPv2c DCPx TELNE...

Страница 8: ...part numbers listed and call DPS Telecom at 1 800 622 3314 BVM 48 D PK BATVM BVM 48 User Manual BVM 48 Resource CD D OC UM103 05100 6 ft DB9M DB9F Download Cable 14 ft Ethernet Cable D PR 045 10A 04...

Страница 9: ...cell 2 2 Heads per cell 3 3 Heads per cell 4 4 Heads per cell Voltage 02 2V 12 12V 48 48V Bundle Length 1 1ft 2 2ft 9 9ft Overall Length 010 10ft 020 20ft 250 250ft Table 5 1 Harness item part number...

Страница 10: ...rack ear can be mounted on the left or right side of the unit The BVM 48 mounts in a 19 or 23 rack and can be mounted on the right or left in the flush mount or rear mount locations as shown in Fig 4...

Страница 11: ...1 BVM 48 back panel connections Power Connection 48 VDC 6 1 The BVM 48 is powered by two screw terminal barrier plug power connectors Fig 5 2 Screwterminal barrier plugs To connect the BVM to a power...

Страница 12: ...Ethernet cable into the 10BaseT Ethernet port on the back of the unit If the LAN connection is OK the LNK LED will light SOLID GREEN Serial Connection 6 3 The BVM has one RS 232 expansion port located...

Страница 13: ...e If a battery harness is not used for the battery cell input it can cause a short resulting in a fire hazard BVM 48 Front Panel 7 Fig 6 1 BVM 48 Front panel connections Craft Port 7 1 Use the front p...

Страница 14: ...onnection between your PC s COM port and the unit s craft port Note You must be connected via craft port or Telnet to use the TTY interface Make sure you are using the straight through 1 to 1 Male to...

Страница 15: ...he cable provided Additional cables can be ordered from DPS Telecom Part number D PR 045 10A 04 7 The BVM 48 s main main menu will appear Type C for C onfig then E for E thernet Configure the unit s I...

Страница 16: ...PC s current IP address and subnet mask and write this information down 3 Reset your PC s IP address to 192 168 1 200 Contact your IT department if you are unsure how to do this 4 Reset your PC s subn...

Страница 17: ...e established at port 2002 not the standard Telnet port as an added security measure Menu Shortcut Keys The letters before or enclosed in parentheses are menu shortcut keys Press the shortcut key to a...

Страница 18: ...ell harness type 3 Enter Cell Number 4 Measure applied voltage and input value to calibrate BVM Web Browser 10 Fig 9 1 Web browser welcome page Introduction 10 1 The BVM 48 features a built in Web Bro...

Страница 19: ...r It may be helpful to bookmark the logon page to avoid entering this each time 2 After connecting to the unit s IP address enter your login information and click OK NOTE The factory default username...

Страница 20: ...ogon password 1 From the Edit menu select System 2 Enter the new user name in the User field 3 Enter the new password in the Password field 4 Click the Save button Fig 9 3 Global System Settings secti...

Страница 21: ...Descriptions How to Send Email Notifications 11 1 1 Click on the System button in the Edit menu and enter a valid email address in the From Email Address field You may need to check with your IT depar...

Страница 22: ...le screen you ll select the exact days and times you want to receive email notifications You can set 2 schedules per notification For example you may want to receive notifications at certain times dur...

Страница 23: ...ign Notification Device 1 to Power A alarm This means that you would receive an email notification when an alarm for SERVER ROOM occurs Remember that Notification 1 in the Notifications menu is the sa...

Страница 24: ...ations button in the Edit menu You can setup as many as 8 different notifications Begin the setup wizard by clicking on a notification number In this example we ll setup Notification 4 to send SNMP tr...

Страница 25: ...ect the Send SNMP Notification button and click Next Fig 10 10 4 At the SNMP Notification screen you ll enter your network s SNMP settings Enter the IP address of your SNMP Trap Server the Trap Port N...

Страница 26: ...ime from the drop down menus Click Finish To try a test notification click the Test button See next step Fig 10 12 6 If you chose to test the SNMP notification you will see the popup below Click OK to...

Страница 27: ...when the temperature rises above or drops below these set levels In this example we are selecting the following values Major Under Temp 45 F Minor Under Temp 55 F Minor Over Temp 78 F Major Over Temp...

Страница 28: ...X 250 Ohms 0 004 X 250 1VDC AND 20mAX 250 Ohms 0 020 X 250 5VDC The documentation that came with this sensor explains how 4 20 mA translates temperature In this case 4mA or 1VDC 32 F AND 20mA or 5VDC...

Страница 29: ...ging into the unit case sensitive DCP Responder Settings For use with T Mon NOC DCP Unit ID User definable ID number for this unit DCP Address Listen DCP Choose to listen DCP over LAN or serial May al...

Страница 30: ...26 After clicking Export you are prompted to save your CSV Comma Separated Values File Sample CSV file opened in Microsoft Excel You can now display charts for your analog values...

Страница 31: ...ed an IP address from your DHCP server The IP you ve already assigned to the unit becomes inactive Using DHCP means the unit will NOT operate in a T Mon environment Unit IP IP address of the unit Subn...

Страница 32: ...of the notifications to begin configuration Fig 11 5 The Edit Notifications menu Once you ve chosen which notification you want to setup check the Enable Notification to turn it on Then choose a noti...

Страница 33: ...able from this screen To E mail Address The email address of the person responsible for this unit who will receive email alarm notifications SNMP Notification Fields Fig 11 8 Editing SNMP notification...

Страница 34: ...o only send alarm notifications during certain hours on the day s you ve selected Multi Purpose User Analogs 12 4 Each of the BVM s user defined analog channels may be individually configured to monit...

Страница 35: ...analog alarm Check the box in the green bar top to have a notification device send an alarm for all analog channels Detailed Analog Editing Record freq The period after which the current value of the...

Страница 36: ...in the green bar top to have a notification device send an alarm for all analog channels Detailed Battery String Editing Cells Defines which group of cell inputs make up this particular string Record...

Страница 37: ...Report Check this box to choose to report this alarm Check the box in the green bar top to have all System Alarms reported Leave unchecked to ignore Notification devices Check which notification devic...

Страница 38: ...er Address or Host Name Enter the NTP server s IP address or host name then click Sync Example north america pool ntp org If using Host Name make sure DNS servers are defined under Ethernet settings T...

Страница 39: ...k The hearbeat function that can be used by masters who don t perform integrity checks Sound on time How long the unit s speaker will sound when reportable alarms occur or clear Reboot 12 9 Click on t...

Страница 40: ...in green when the alarm condition is not present See Display Mapping in the Reference Section for a complete description of system alarms Fig 11 22 View the status of System Alarms from the Monitor Sy...

Страница 41: ...llows you to see live unit readings and see which ones have crossed your thresholds 12 10 3Monitoring Battery Strings From the Monitor Battery Strings menu you will see the sum and thresholds for the...

Страница 42: ...creen click the firmware link located in the System Controls section Fig 12 1 The clickable link to upgrade firmware from the Edit System menu At the Firmware Load screen simply browse for the firmwar...

Страница 43: ...shold crossed 1 Cell Solid Red A single cell threshold has been crossed Off No cell threshold crossed 2 Cells Solid Red Two cell thresholds have been crossed Off No cell threshold crossed 3 or more Ce...

Страница 44: ...99 1 5 6 Cell 3 average Major Under Major Over 99 1 7 8 Cell 3 Range 99 1 9 11 Cell 3 Polarity 99 1 13 Cell 3 16 Bit Voltage Data 99 1 17 32 Cell 4 Minor Under Minor Over 99 1 33 34 Cell 4 Major Under...

Страница 45: ...10 16 Bit Voltage Data 99 1 49 64 Display 8 Cell 11 Minor Under Minor Over 99 1 1 2 Cell 11 Major Under Major Over 99 1 3 4 Cell 11 average Minor Under Minor Over 99 1 5 6 Cell 11 average Major Under...

Страница 46: ...1 45 Cell 18 16 Bit Voltage Data 99 1 49 64 Display 12 Cell 19 Minor Under Minor Over 99 1 1 2 Cell 19 Major Under Major Over 99 1 3 4 Cell 19 average Minor Under Minor Over 99 1 5 6 Cell 19 average...

Страница 47: ...play 16 Analog 1 Minor Under Minor Over 99 1 1 2 Analog 1 Major Under Major Over 99 1 3 4 Analog 1 Range 99 1 9 11 Analog 1 Polarity 99 1 13 Analog 1 Value 99 1 17 32 Temp 1 Minor Under Minor Over 99...

Страница 48: ...String 5 Major Under Major Over 99 1 3 4 String 5 Range 99 1 9 11 String 5 Polarity 99 1 13 String 5 Value 99 1 17 32 String 6 Minor Under Minor Over 99 1 1 2 String 6 Major Under Major Over 99 1 3 4...

Страница 49: ...3 event such as a page or email was unsuccessful Use RPT filter debug to help diagnose notification problems 36 Notification 4 failed A notification 4 event such as a page or email was unsuccessful U...

Страница 50: ..._OV_Traps points _OV_vTraps 1 3 6 1 4 1 2682 1 4 0 PointSet 20 PointClr 21 SumPSet 101 SumPClr 102 ComFailed 103 ComRestored 014 P0001Set 10001 through P0064Set 10064 P0001Clr 20001 through P0064Clr...

Страница 51: ...ion 0 Version Public Request Trap Request 1 3 6 1 4 1 2682 1 4 Enterprise 126 10 230 181 Agent address Enterprise Specific Generic Trap 8001 Specific Trap 617077 Time stamp 1 3 7 1 2 1 1 1 0 Object BV...

Страница 52: ...ld read Bits per second 9600 9600 baud Data bits 8 Parity None Stop bits 1 Flow control None Important Flow control must be set to none Flow control normally defaults to hardware in most terminal prog...

Страница 53: ...should be compiled on your SNMP manager Note MIB versions may change in the future The unit supports 2 SNMP managers which are configured by entering its IP address in the Trap Address field of Ether...

Страница 54: ...ting through What should I try A Try these three steps 1 Make sure that the Trap Address IP address of the SNMP manager is defined If you changed the Trap Address make sure you saved the change to NVR...

Страница 55: ...rmation when you call our Technical Support representatives can assist you in gathering it Please write the information down for easy access Please have your user manual and hardware serial number rea...

Страница 56: ...old it harmless for and against any and all claims damages losses costs expenses obligations liabilities fees and costs and all amounts paid in settlement of any claim action or suit which may be asse...

Страница 57: ...53...

Страница 58: ...54...

Страница 59: ...r lightning unless and to the extent that the product specification provides for resistance to a defined disaster e damage caused by unauthorized attachments or modifications f damage during shipment...