7 Commissioning/Start-up/Shutdown
7.1 Ambient conditions for commissioning and operation
Table 17:
Ambient conditions for operation
Condition
Value
Ambient temperature
0 ... 60 °C
Relative humidity
Min. 5 % to max. 90 %
Non-condensing
Installation altitude
Max. 2000 m above MSL
(higher installation altitudes are subject to a reduction factor)
7.2 Commissioning
A checklist can be used for commissioning. [
7.2.1 Starting up the system
See system documentation.
7.2.2 Configuring parameters
Observe the general configuration instructions.
1. Press the turn/push button of the control unit for five seconds until the symbol for
wireless connection starts flashing.
2. Open the app.
3. Establish a connection between the app and the control unit.
4. Tap the
spanner
symbol to access the Service level.
5. Tap the second symbol to configure the parameters.
If 15 minutes pass without the app being used, the connection ends automatically. If the
control unit does not receive any signals via the wireless connection for 2 minutes, it ends
the connection automatically (factor setting).
7.2.3 Selecting the language
When the app is opened for the first time, a language has to be selected.
1. Click on the globe symbol on the first page of the app.
2. Select the required language.
7.2.4 Setting the time/date
The control unit does not automatically adjust to daylight saving time.
1. To set the time of day, select parameter 1-7-1.
2. To set the date, select parameter 1-7-2.