A draught/vacuum of 15 - 20 Pa during normal
operation is ideal.
Starting from the flue spigot, the flue must run as
vertically as possible. Changes in direction and
horizontal pieces disrupt the outward flow of
combustion gases and may cause soot deposits.
To prevent combustion gases from cooling down
too much, which reduces the draught, ensure that
the interior diameter is not too big.
The flue or chimney should ideally have the same
diameter as the connection collar.
For the nominal diameter: see the appendix
"Technical data". If the smoke channel is well
insulated, the diameter may be slightly bigger
(up to 2x the section of the connection collar).
The section (area ) of the smoke channel must be
constant. Wider segments and (in particular)
narrower segments disrupt the outward flow of
combustion gases.
When using a cover plate or exhaust hood : make
sure that the cover does not restrict the flue outlet
and that the cap does not impede the outward flow
of combustion gases.
The flue must end in a zone that is not affected by
surrounding buildings, trees or other obstacles.
The flue outside the house must be insulated.
The chimney must be at least 4 metres high.
As a rule of thumb: 60 cm above the ridge of the
roof.
If the ridge of the roof is more than 3 metres away
from the flue: stick to the measurements in the
following figure. A = the highest point of the roof
within a distance of 3 metres.
Ventilation of the area
For good combustion, the stove needs air (oxygen).
This air is supplied via adjustable air inlets from the
area in which the stove is installed.
The combustion will be incomplete in case of
insufficient ventilation, which results in toxic
gases being produced and spread through the
area.
As a rule of thumb, the air supply should be 5,
5 cm²/kW. Extra ventilation is needed when:
The stove is in an area that is well-insulated.
There is mechanical ventilation, for example a
central extraction system or an extraction hood in
an open kitchen.
You can provide extra ventilation by having a
ventilation louvre fitted on the outside wall.
Make sure that other air consuming appliances (such
as tumble-driers, other heating appliances or a
bathroom fan) have their own supply of outside air, or
are switched off when you use the appliance.
You can also connect the appliance to an
outside air supply. A connection kit is supplied
for this purpose. This makes additional
ventilation unnecessary.
Floors and walls
The floor on which the appliance is placed must have
sufficient bearing capacity. For the weight of the
appliance, see the appendix "Technical data".
Protect flammable flooring from heat radiation
by means of a fireproof protective plate. See
the appendix "Distance from combustible
material".
Remove combustible material such as
linoleum, carpets/rugs and similar materials
below the fireproof protective plate.
Keep sufficient distance between the
appliance and combustible materials such as
wooden walls and furniture.
The connecting tube also radiates heat. Ensure
that there is sufficient distance or a shield
between the connecting tube and combustible
Subject to change because of technical improvements