background image

 

Please visit OPW’s website:

 

www.opwglobal.com

 for further 

information or contact OPW Customer 

Service at 

+44 (0) 1756 799 773

 

(EU) 

or 

1-800-422-2525

 

(US) 

 

 

opwglobal.com 

 

 

DEFINING

 | WHAT’S NEXT

 

214916 revision A 

September 2019 

DAILY INSPECTION 

  Visually inspect the dispensing 

equipment for excessively worn, 

abused, mistreated or leaking 

equipment. Replace equipment 

immediately.  

MONTHLY INSPECTIONS 

  Inspect the nozzle spout for wear and deformation. 

Replace the spout assembly as necessary. 

  If the nozzle spout is bent, the shut-off hole is blocked, or 

the end of the spout is rolled over, the nozzle spout or 

the entire nozzle should be replaced immediately. 

Failure to replace the spout may result in a hazardous 

spill. 

  Replace spout if tip is worn. Do not cut off spout tip. This 

will lead to nuisance shut offs, or non-shut off, which 

could lead to a hazardous spill and/or injury or death. 

  Inspect nozzle for evidence of leakage; confirm that 

nozzle is leaking and replace nozzle if necessary. 

  Check for broken attendant clip 

spring and replace nozzle if 

necessary.  

  Verify that the minimum flow rate 

greater than specified. See testing 

instructions. 

  Perform shut-off test. See testing instructions. 

  All maintenance and inspection activity on the nozzle 

must be documented. This includes replacement parts, 

drive-off or other testing.  

ANNUAL INSPECTIONS 

  Perform continuity test.  See testing instructions. 

 WARNING

 

FIRE HAZARD/SPILL HAZARD/  

CHEMICAL EXPOSURE 

Replace the nozzle if the nozzle fails any of the above 

tests or inspections. Failure to comply could result in 

property damage, injury or death. 

REPLACEMENT PARTS 

  DO NOT reuse O-rings or screws when replacing 

components. 

  Only use authorized OPW replacement kits from the 

distributor. All other modifications may result in nozzle 

failure and create a hazardous condition, resulting in 

personal injury, property damage, or death, and will void 

the warranty. 

IN CASE OF DRIVE-OFF OR SUSSPECTED 

CUSTOMER ABUSE 

  Immediately lock hose point out of 

service until a thorough inspection by 

a qualified service technician can be 

made. Inspect the nozzle, hose, 

breakaway, dispenser outlet casting, 

and piping.  

  Even if there is no separation of the breakaway or 

breakage of the nozzle spout, damage can be done that 

may cause leaks. Inspect and replace any damaged 

components, as necessary, prior to returning the hose 

point to service. 

  Check for leaks and other damage. 

  Check nozzle for liquid shut-off. See shut-off test 

instructions. 

  Check for continuity. See continuity test instructions. 

  DO NOT replace spout without OPW replacement kits 

and instructions. (See OPW’s website for replacement 

kits). Improper parts or assembly may result in leakage 

or a hazardous condition.  If the spout is removed or 

replaced for any reason, the nozzle must be retested in 

accordance with this manual. 

 

Make sure to comply with any requirements of 

authorities having jurisdiction

.

 

 
 
 
 

 

 

 

Содержание OPW 21 Series

Страница 1: ... on file for future reference This manual contains material that may be required by authorities having jurisdiction to be on site at all times Carefully observe all warnings precautions and instructions for this equipment and in the operating instructions and adhere to them THIS MANUAL MUST BE LEFT WITH FACILITY MANAGEMENT Models 21AG 21AGV 21BG 21BGV EN 13012 2012 Type I 0530 II 1G Sira 19ATEX910...

Страница 2: ... electricity can ignite petrol vapours and cause a fire Fill approved portable containers on the ground It is dangerous to put petrol into an unapproved container Keep nozzle in contact with the container until finished filling to discharge any static generated during fueling When filling an approved portable container flow fuel at low flow rate to prevent static build up DO NOT put trigger in rac...

Страница 3: ... grounded vented metal test container and megohmmeter CONTINUITY TEST After installation of hanging hardware and prior to flow test check continuity following EN 60204 1 for proper test equipment and method of testing WARNING Fueling equipment is designed to operate in a pressure range of 0 5 to 3 5 bar If the pressure exceeds 6 bar the nozzle will open regardless of lever position Exceeding maxim...

Страница 4: ...ed for fuel on the ground prior to and during test Nozzle must be in contact with the container until the testing is complete to discharge any static generated during the test 7 Dispense approximately 20 litres of fuel into an approved test container with the nozzle lever held in the full open position 8 Calculate A L ratio by dividing the volume of vapour collected by the volume of fuel dispensed...

Страница 5: ...djusting vapour flow rates Retest and verify that adjustments now bring the A L ratio into compliance 8 Reseal the UST vapour system after the A L ratios are set for all fueling points WARNING Static electric spark could ignite fuel causing a fire Place a container approved for fuel on the ground prior to and during test Nozzle must be in contact with the container until the testing is complete to...

Страница 6: ... Perform continuity test See testing instructions WARNING FIRE HAZARD SPILL HAZARD CHEMICAL EXPOSURE Replace the nozzle if the nozzle fails any of the above tests or inspections Failure to comply could result in property damage injury or death REPLACEMENT PARTS DO NOT reuse O rings or screws when replacing components Only use authorized OPW replacement kits from the distributor All other modificat...

Страница 7: ...laims must be made in writing and delivered during the applicable warranty period to OPW at OPW 9393 Princeton Glendale Road Hamilton Ohio USA 45011 Attention Customer Service Manager No products may be returned to OPW without its prior written authority This limited warranty shall not apply to any FlexWorks or VAPORSAVER product unless it is installed by an OPW attested installer This limited war...

Страница 8: ...bmitting a warranty claim OPW NOZZLE WARRANTY TAG SITE Phone Number City Contact Country Distributor Branch Customer RGA Number Nozzle Model Serial Number Replacement Serial Number WARRANTABLE DEFECTS CHECK ONLY ONE Leaks Fuel Around Spout 200 Dispenses Fuel Without Pulling Lever 200 Leaks Fuel in Trigger Area 200 Fails Pressure Decay Test 300 Leaks Fuel at Hose Inlet 200 Fails Air to Liquid Test ...

Отзывы: