Please visit OPW’s website:
information or contact OPW Customer
Service at
+44 (0) 1756 799 773
(EU)
or
1-800-422-2525
(US)
opwglobal.com
6
DEFINING
| WHAT’S NEXT
214916 revision A
September 2019
DAILY INSPECTION
•
Visually inspect the dispensing
equipment for excessively worn,
abused, mistreated or leaking
equipment. Replace equipment
immediately.
MONTHLY INSPECTIONS
•
Inspect the nozzle spout for wear and deformation.
Replace the spout assembly as necessary.
•
If the nozzle spout is bent, the shut-off hole is blocked, or
the end of the spout is rolled over, the nozzle spout or
the entire nozzle should be replaced immediately.
Failure to replace the spout may result in a hazardous
spill.
•
Replace spout if tip is worn. Do not cut off spout tip. This
will lead to nuisance shut offs, or non-shut off, which
could lead to a hazardous spill and/or injury or death.
•
Inspect nozzle for evidence of leakage; confirm that
nozzle is leaking and replace nozzle if necessary.
•
Check for broken attendant clip
spring and replace nozzle if
necessary.
•
Verify that the minimum flow rate
greater than specified. See testing
instructions.
•
Perform shut-off test. See testing instructions.
•
All maintenance and inspection activity on the nozzle
must be documented. This includes replacement parts,
drive-off or other testing.
ANNUAL INSPECTIONS
•
Perform continuity test. See testing instructions.
WARNING
FIRE HAZARD/SPILL HAZARD/
CHEMICAL EXPOSURE
Replace the nozzle if the nozzle fails any of the above
tests or inspections. Failure to comply could result in
property damage, injury or death.
REPLACEMENT PARTS
•
DO NOT reuse O-rings or screws when replacing
components.
•
Only use authorized OPW replacement kits from the
distributor. All other modifications may result in nozzle
failure and create a hazardous condition, resulting in
personal injury, property damage, or death, and will void
the warranty.
IN CASE OF DRIVE-OFF OR SUSSPECTED
CUSTOMER ABUSE
•
Immediately lock hose point out of
service until a thorough inspection by
a qualified service technician can be
made. Inspect the nozzle, hose,
breakaway, dispenser outlet casting,
and piping.
•
Even if there is no separation of the breakaway or
breakage of the nozzle spout, damage can be done that
may cause leaks. Inspect and replace any damaged
components, as necessary, prior to returning the hose
point to service.
•
Check for leaks and other damage.
•
Check nozzle for liquid shut-off. See shut-off test
instructions.
•
Check for continuity. See continuity test instructions.
•
DO NOT replace spout without OPW replacement kits
and instructions. (See OPW’s website for replacement
kits). Improper parts or assembly may result in leakage
or a hazardous condition. If the spout is removed or
replaced for any reason, the nozzle must be retested in
accordance with this manual.
•
Make sure to comply with any requirements of
authorities having jurisdiction
.