
UIC-DX270 Series
User’s Manual Rev 1.0
- 26 -
4) RUN INFORMATION
Item
Description
Units
Step
Min
Max
Default
View
Access
000
Inlet Temp.
℃
0.1
-40.0
70.0
View only USER 1
-
001
Outlet Temp.
℃
0.1
-40.0
70.0
View only USER 1
-
002
Discharge Gas Temp.
℃
1
0
180
View only USER 1
-
003
Run hour
h
1
0
99999
0
USER 1
SVC 2
004
Comps run hour
h
1
0
99999
0
USER 1
SVC 2
005
Comps on/off
number
1
0
99999
0
USER 1
SVC 2
1)
Over 99999 Operation Time or Number, it is initialized ‘0’ automatically.
2)
Operation Time or Number could be changed over Service Level 2.
5)
OPERATION
Item
Description
Units
Step
Min
Max Default
View
Access
100
Set value
℃
0.1
-99.9
99.9
7.0
USER2
USER2
Bar
2.0
%
20.0
101
Run differential
℃
0.1
+0.1 +50.0
+5.0
USER2
USER2
Bar
+2.0
%
+30.0
102
Stopping differential
℃
0.1
-50.0
0.0
0.0
USER2
USER2
Bar
0.0
%
0.0
103
50% cap.differential
℃
0.1
0.0 +50.0
+1.0
SVC1
SVC1
Bar
+0.5
%
+10.0
104
75% cap.differential
℃
0.1
0.0 +50.0
+2.0
SVC1
SVC1
Bar
+1.5
%
+20.0
105
○
+ D.Band differential
℃
0.1
0.0 +20.0
+0.2
SVC1
SVC1
Bar
+0.1
%
+2.0
106
○
- D.Band differential
℃
0.1
-20.0
0.0
-0.2
SVC1
SVC1
Bar
-0.1
%
-2.0
107
Injection set value.
℃
1
0
180
100
SVC1
SVC1