DOTECH FX3DH Скачать руководство пользователя страница 4

- 4 -

R20160613

Parameter

Push for 3 sec.

ST  1

50.0

FX3DH

OUT1
OUT2

Run Mode

Select Control Type #1

Function of control output #1

Control Deviation Value #1

Select deviation type #1

ON Delay Time #1

Minimum OFF Time #1

E V  1

T Y  1

Select Control Type #2

Control Deviation Value #2

E V 2

T Y 2

D F  1
T P  1
D T  1
N T  1

Output #1 setup value

ST 2

50.0

Output #2 setup value

Push 

for 3 sec.

Push 

for 3 sec.

Menu move

Setup value

Run Mode

Select Lock Function

Select Sensor Type

Correct PV (Temperature value)

Decimal Point Display

Correct PV (Present value)

Sensor Input Filter

L O C
 I  N
T C R
D P
C O R
S F T

Menu move

Setup value

reset

Push 

for 5 sec.

Push 

for 3 sec.

Humidity &  Temp. Setting Group

Humidity & Temp. Setting Group 

(SEL Button Push for 3 Sec.)

No

Menu

Code

Unit

Step

Min

Max

Default

Custom Setup

4 0001

Output #1 setup value

ST1

%, °C

0.1

UL1

UH1

50.0

4 0002

Output #2 setup value

ST2

%, °C

0.1

UL2

UH2

50.0

 If the set value of the 

IN

 is set to control the humidity 

HT ST1

,

 ST2

 are used as temperature control.

Setting 1 Group

Setting 2 Group

Содержание FX3DH

Страница 1: ...rovided 7 An output wire to be used for this product should be inflammable grade FV1 V 1 grade or above the thickness of the wire should be AWG No 20 or above 0 50mm2 8 In order to prevent it from an...

Страница 2: ...hen open 8 NTC Temp sensor input 9 COM Common signal 10 Vin Humidity sensor input 11 5V Humidity sensor power 5Vdc Accessories HTX20 FTS 502 DOTECH INC RH 10 95 RH 1 2 3 5V T NTC5K RH Temp Sensor 5V R...

Страница 3: ...iate Stop Automatic Reset T S T Temp Higher High Limit Higher High Limit Alarm than High Limit Alarm Value Immediate Stop Automatic Reset T L L Temp Lower Input Lower sensor input than measuring range...

Страница 4: ...ue Run Mode Select Lock Function Select Sensor Type Correct PV Temperature value Decimal Point Display Correct PV Present value Sensor Input Filter L O C I N T C R D P C O R S F T Menu move Setup valu...

Страница 5: ...99 5 4 0022 Minimum ONTime 3 NT 1 Sec 1 0 999 5 4 0023 Output at Sensor Error 4 SF 1 OFF 0 0N 1 OFF 0 4 0024 Alarm Deviation Value H Y 1 K 0 1 0 0 99 9 1 0 4 0025 Alarm Option A P 1 ALA 0 General alar...

Страница 6: ...A L 5 PV OFF 90 ON HY PV 70 OFF ON HY set DF to 70 set DF to 90 Absolute Value High Limit Alarm Output is ON when PV value is higher than or equal as control deviation setup value Alarm temperature i...

Страница 7: ...ans DIR 1 Humidification Heating proportional Control ReV 2 Dehumidification Cooling proportional Control ST 1 3 SV1 Set value Trans ST2 4 SV2 Set value Trans PV 4 0089 AnalogueTrans Output 20mA A1 mo...

Страница 8: ...ity Sensor disconnection short circuit Alarm Digital Bit 0 Normal 1 Alarm Bit 15 EEPROM alarm Digital Bit 0 Normal 1 Alarm 4 0107 Current humidity value PV Analog INT 16 0 100 0 1000 1 10 4 0108 Curre...