Product

Bracket 2ea

User's Manual

 Technical  Specifications

Power

100–240Vac, 50/60Hz

Current

MAX 6 VA

Connection

Screw Bolt Connector(1.5mm

2

 Wire Use Possibility)

Output

Relay Output 2 Point (250Vac / 5A)

Input

Humidity 1 Point (HTX20-FTS-502, HTX3515)
Temp. 1 Point (DPR-TH01-ET)

Dimensions

78(W)mm X 35(H)mm X 78(D)mm

Operation

Temperature: -10 ~ 50°C, Humidity: Below 90%RH

Storage

Temperature: -20 ~ 60°C, Humidity: Below 90%RH

Ordering guide

FX3DH-00

Basic Model 

FX3DH-A1

4~20mA Trans output model

FX3DH-R4

RS485 Comm. model 

FX3DH-A1R4

4~20mA Trans output & RS485 Comm. model

※ Specifications are subject to change without prior notice.

Components

User’s Manual

Digital Humidity & Temp. Controller 

User's Manual

FX3DH

DOTECH INC. 

   

6F, JOONGANG-ILBO B/D, 30, Dongsan-ro, Danwon-gu, Ansan-si, Gyeonggi-do, KOREA 

Cautions

1. This product may cause an electric shock in handling. Please do not attempt to open it with power turned on.

2. This product should be installed in a place fixed secured by a rack or panel.

3. This product can be used under the following environmental condition. 

 Indoor 

 Pollution Degree 2 

 At an altitude of 2000m or below

4. Power input must be within the designated ranges.

5.  To turn on or turn off power supply for this product, please the circuit breaker or switch of a standard product of IEC 60947-1 or IEC 60947-3 product 

and install it within a close distance allowing convenient operation by user.

6. Please be understood that if this product is dismantled or modified discretionary, after sales service will not be able to be provided.

7.  An output wire to be used for this product should be inflammable grade FV1 (V-1 grade or above), the thickness of the wire should be AWG No. 20 or 

above(0.50mm

2

).

8. In order to prevent it from an inductive noise, please maintain the high-voltage wire and power wire separated.

9. Please avoid installing the product in a place where a strong magnetism, noise, severe vibration and impact exist.

10. When extending the sensor wire, use a shield wire and do not extend it unnecessary long.

11. The sensor wire and signal wire should be away from the power and load wires using conduits separately installed.

12.  Please avoid using the product near a device generating strong high frequency noise (high-frequency welding machine, high-frequency sewing 

machine, high-frequency radiotelegraph, high capacity SCR controller)

13. Product’s damages other than those decribed in the guarantee conditions provided by the manufacturer shall not be respoinsible by us.

14.  If this unit is used to control machineries (Medical equipment, vehicle, train, airplane, combustion apparatus, entertainment, processing and 

transportation equipment, elevator and various safety device etc.) enabling to effect on human or property, it is required to install fail-safe device.

 The Aforementioned precautions must be observed, and if you fail to do so, it may cause a product’s breakdown.

 The specifications, dimensions, and etc. are subject to change for enhancement without a prior notice.

- Humidification(Heating)
   /Dehumidification(Cooling) Output
- Switching Display of Temperature and Humidity
- High/Low Limit Alarm
- Sensor Calibration
- Sensor Error Detection and On/Off Output Control
- Minimum On/Off Duration Time
- Manual Relay Control
- Analog Signal Output(4-20mA)
- Communication via RS485 MODBUS

Содержание FX3DH

Страница 1: ...rovided 7 An output wire to be used for this product should be inflammable grade FV1 V 1 grade or above the thickness of the wire should be AWG No 20 or above 0 50mm2 8 In order to prevent it from an...

Страница 2: ...hen open 8 NTC Temp sensor input 9 COM Common signal 10 Vin Humidity sensor input 11 5V Humidity sensor power 5Vdc Accessories HTX20 FTS 502 DOTECH INC RH 10 95 RH 1 2 3 5V T NTC5K RH Temp Sensor 5V R...

Страница 3: ...iate Stop Automatic Reset T S T Temp Higher High Limit Higher High Limit Alarm than High Limit Alarm Value Immediate Stop Automatic Reset T L L Temp Lower Input Lower sensor input than measuring range...

Страница 4: ...ue Run Mode Select Lock Function Select Sensor Type Correct PV Temperature value Decimal Point Display Correct PV Present value Sensor Input Filter L O C I N T C R D P C O R S F T Menu move Setup valu...

Страница 5: ...99 5 4 0022 Minimum ONTime 3 NT 1 Sec 1 0 999 5 4 0023 Output at Sensor Error 4 SF 1 OFF 0 0N 1 OFF 0 4 0024 Alarm Deviation Value H Y 1 K 0 1 0 0 99 9 1 0 4 0025 Alarm Option A P 1 ALA 0 General alar...

Страница 6: ...A L 5 PV OFF 90 ON HY PV 70 OFF ON HY set DF to 70 set DF to 90 Absolute Value High Limit Alarm Output is ON when PV value is higher than or equal as control deviation setup value Alarm temperature i...

Страница 7: ...ans DIR 1 Humidification Heating proportional Control ReV 2 Dehumidification Cooling proportional Control ST 1 3 SV1 Set value Trans ST2 4 SV2 Set value Trans PV 4 0089 AnalogueTrans Output 20mA A1 mo...

Страница 8: ...ity Sensor disconnection short circuit Alarm Digital Bit 0 Normal 1 Alarm Bit 15 EEPROM alarm Digital Bit 0 Normal 1 Alarm 4 0107 Current humidity value PV Analog INT 16 0 100 0 1000 1 10 4 0108 Curre...