DOTECH EVC10B Series Скачать руководство пользователя страница 8

-8-

 

EVC10B R20140821 

: TRIP / ALARM MESSAGE 

※  Alarm which is flickering needs to reset by manual.   
※  Press PRG/RST button two times quickly. Auxiliary relay (RL1) will be outputted if alarm is occurred. (In case of setting for alarm output relay) 

 

6.

 

Communication  Protocol  

Specifications of communication

  

Item 

Description  

Transmission line connection 

Multiple line 

Communications method 

RS485 (2-wire, half-duplex) 

Baud-rate 

BPS default 9600 BPS 

Parity, Data, Stop bit 

None, 8 Data, 1 Stop 

Protocol Type 

Modbus RTU MODE 

Function Code 

Read HOLD REGISTERS (0x03) / Preset Single Register (0x06) 

Maximum Read Word 

32 Word 

Media Type 

BELDEN 9841 / 9842, LG LIREV-AMESB 

Poll interval 

100msec 

STATUS - Communication Table

  

(※1) Manual control of EEV by communication  

Electronic expansion valve will be controlled manually regardless of superheat of present system just by using 0.0 to 100.0% of UCR (electronic expansion valve compulsory open ration) 
To lift a UCR (electronic expansion valve compulsory open ration), please input ‘1’ at 4 0073. Then it will be converted into automatic control mode. 
But, electronic expansion valve will be closed automatically at the status of stop or alarm  

(※2) Run / Stop by communication  

※ RMT(Run/Stop) : It will be run or stopped by input of 4 0101 only if run / stop method should be set to communication (2) 

Cods 

Description 

Parameter 

Conditions for occurrence 

Ways to clear 

POP 

Pressure sensor disconnection 

If pressure sensor is disconnected

 

If pressure sensor is normal

 

PST 

Pressure sensor Short circuit 

If pressure sensor is short circuited

 

TOP 

Pressure sensor disconnection 

If temperature sensor is disconnected

 

If temperature sensor is normal

 

TST 

Pressure sensor Short circuit 

If temperature sensor is short circuited

 

MOP 

Detect MOP temperature 

MP

= 1 

If present pressure remains higher than set value of MOP 
during MPD (MOP alarm detection delay time)

 

System check is needed

 

It becomes a clear condition if present pressure value is less 
than set value of MPF

 

MP

= 2 (

Flickering)

 

LOP 

Detect lower limit Pressure alarm 

LP

= 1 

If present pressure remains lower than set value of LOP 
during LDP (Low limit pressure alarm delay time)

 

It will be caused by lack of refrigerant. 
It becomes a clear condition if present pressure is more than 
set value of LPF

 

LP 

= 2 (

Flickering)

 

HSH

 

Detect high Superheat alarm 

HS

= 1 

If present super heat remains higher than set value of HSH 
during HSD (High superheat alarm delay time)

 

System check is needed

  

It becomes a clear condition if preset super heat is less than 
set value of HSF

 

HS

 = 2(

Flickering)

 

LSH

 

Detect low superheat alarm 

LS

= 1 

If present super heat remains lower than set value of LSH 
during LSD (Low superheat alarm delay time)

 

System check is needed

 

It becomes a clear condition if present super heat is more 
than set value of LSF

 

LS

 = 2(

Flickering)

 

FRE

 

Detect freezing Protection alarm 

FR

= 1 

If present temperature remains lower than set value of FRE 
during FRD (Freezing protection alarm delay time)

 

Evaporator temperature is low. System check is needed  It 
becomes a clear condition if present temperature is more 
than set value of FRF. 

FR

= 2(

Flickering)

 

Address 

Function 

Unit 

Type 

Size (Word) 

EVC10B 

MMI 

 

4 0073 

EEV compulsory open ratio(※1) 

Analog 

INT 16 

0.0 - 100.0 

X 10 

 

4 0099 

Reset command  

Analog 

INT 16 

0 : OFF 

1 : ON 

 

4 0101 

Run / Stop input (※2) 

Analog 

INT 16 

0 : Stop 

1 : Run  

 

4 0102 

Operation status  

Analog 

INT 16 

Refer to below bit  

 

Bit0 

Operation status of EEV 

Digital 

Bit 

0 : OFF 

1 : ON 

 

Bit1 

Aux. relay output 

Digital 

Bit 

0 : OFF 

1 : ON 

 

4 0110 

Alarm status  

Analog 

INT 16 

Refer to below bit 

 

Bit0 

Press. sensor disconnection 

Digital  

Bit 

0 : OFF 

1 : ON 

 

Bit1 

Press. sensor short circuit 

Digital 

Bit 

0 : OFF 

1 : ON 

 

Bit2 

Temp. sensor disconnection  

Digital 

Bit 

0 : OFF 

1 : ON 

 

Bit3 

Temp. sensor  short circuit 

Digital 

Bit 

0 : OFF 

1 : ON 

 

Bit4 

MOP alarm  

Digital 

Bit 

0 : OFF 

1 : ON 

 

Bit5 

Lower limit pressure alarm  

Digital 

Bit 

0 : OFF 

1 : ON 

 

Bit6 

High superheat alarm  

Digital 

Bit 

0 : OFF 

1 : ON 

 

Bit7 

Low superheat alarm 

Digital 

Bit 

0 : OFF 

1 : ON 

 

Bit8 

Freezing protection alarm  

Digital 

Bit 

0 : OFF 

1 : ON 

 

4 0111 

Present Superheat  

Analog 

INT 16 

 

X 10 

 

4 0112 

Present saturation temperature 

℃ 

Analog 

INT 16 

 

X 10 

 

4 0113 

Present pressure 

bar 

Analog 

INT 16 

-1.0 ~ 1.0 

X 10 

 

4 0114 

Present temperature  

℃ 

Analog 

INT 16 

-100.0 ㅤ 100.0 

X 10 

 

4 0116 

EEV open ratio 

Analog 

INT 16 

0.0 - 100.0 

X 10 

 

Содержание EVC10B Series

Страница 1: ...sed to control machineries Medical equipment vehicle train airplane combustion apparatus entertainment processing and transportation equipment elevator and various safety device etc enabling to effect...

Страница 2: ...40 120 Protection level IP65 Accuracy 1 0 F S Stability 0 5 Longterm Stability Connector Type 7 16 UNF FEMALE Wiring Black com Green out Red 5v 2 Installation Dimensions It can be installed with rail...

Страница 3: ...nsion valve First of all EVC10B needs to setup EEV mode to fit features of electronic expansion valve If EEV mode does not meet operation features of electronic expansion valve there can be malfunctio...

Страница 4: ...d save Display mode DIS parameter of parameter 2 group value will be changed Superheat Pressure of evaporator outlet Currentopenration ofEEV Temperature of evaporator outlet 4 Parameter Parameter chan...

Страница 5: ...g protection alarm is occurred caused by temperature of evaporator is getting low expansionvalveisfullyclosed 8Pumpdownfunction If input pumpdown delay time of 0 to 180 sec auxiliary relay RL1 outputs...

Страница 6: ...re shipment Setting 2 group table Menu 3 3 PR Users should input parameter which is suitable for characteristic of expansion valve In case of difference it may be caused by malfunction or valve and sy...

Страница 7: ...icexpansionvalve controller T sens Temp sensor of evaporatoroutlet Run Run Stopswitch TEV Thermostaticexpansion valve Application parameter Function CODE Min Max Default Setpointforcontroltarget SH 10...

Страница 8: ...sent pressure remains lower than set value of LOP duringLDP Lowlimitpressurealarmdelaytime Itwillbecausedbylackof refrigerant Itbecomesaclearconditionifpresentpressureismorethan setvalueofLPF LP 2 Fli...

Отзывы: