: Setting 1 group table

 (Menu 1 = 

1.PR

※1 Start open ration and start open ratio duration time 

If Run switch is turned on, valve will be opened by start open ratio. After that maintain it during 
start open ratio duration time and start to control. (Input optimum value as a start open ratio) 

 

※2 Setup of proportional gain 

In the majority of cases, use the result of auto tuning. Extra changes are unnecessary. 
Proportional gain makes a decision on control input of valve open ratio 
according to superheat change. If proportional gain is 3.0%, control input of 
valve open ratio is 3.0% per 1.0K of superheat.   
If change of valve open ratio is fickle, decrease proportional gain.   
If change of valve open ratio is slow, increase proportional gain more. 
Open ratio of valve [%] = Start open ratio + (Proportional gain X Tolerance) 

※3 Setup of integral time and derivative time 

In the majority of cases, use the result of auto tuning. Extra changes are unnecessary. 
Integral time: Input time which is applied to control for accumulated volume of tolerance. 
Derivative time: It is for controlling momentary reacting volume for tolerance 
 
If vibration time is longer than integral time, 

1. Integral time increases 1.5 times of vibration time.   

2. Wait until system is stable.   

3. If vibration is lasting, decrease integral time 30%.   

4. Wait until system is stable   

5. Repeat 3 and 4 until vibration is removed. 

 If vibration time is shorter than integral time 

1. Decrease proportional gain 30%.   

2. Wait until system is stable   

3. Repeat 1 and 2 until vibration is removed 

※4 Detect low superheat alarm 

This alarm is caused by superheat is low. Once superheat begins to low, expansion valve start 
to close more. If low superheat alarm is occurred, expansion valve is fully closed. 

※5 Maximum operating pressure alarm mode 

Once maximum operating pressure alarm is occurred, expansion valve is fully closed. 

※6 Detect high superheat alarm 

This alarm is caused by superheat is high. Once superheat begins to high, expansion valve 
start to open more. If high superheat alarm is occurred, expansion valve is fully closed. 

※7 Detect freezing protection alarm 

If freezing protection alarm is occurred caused by temperature of evaporator is getting low, 
expansion valve is fully closed 

※8 Pumpdown function 

If input pumpdown delay time of 0 to 180 sec, auxiliary relay (RL1) outputs it 
as compressor control purpose.   
Run switch turns on, RL1 start to run   
Run switch turns off, RL1 will be turned off. (Less than pumpdown finish pressure) 

※9 Detect low limit pressure alarm 

If pressure is dropping up to less than 

LOP 

for more than 

LPD

, low limit pressure alarm will 

be occurred and expansion valve is fully closed. 

 

Address 

Description 

Code 

Unit 

Step 

Min. 

Max. 

Default 

Custom 

4 0001 

Superheat set-point 

SH 

0.1 

0.5 

30 

6.0 

 

4 0003 

Start open ratio 

BIR 

100 

 

4 0004 

Start open ration duration time 

SDT 

Sec. 

300 

 

4 0005 

P: Proportional gain  

DFR 

0.1 

0.1 

99.9 

3.0 

 

4 0006 

I:Integral time 

I RT 

Sec. 

999 

120 

 

4 0007 

D:Derivative time 

DRT 

Sec. 

999 

30 

 

4 0008 

Low superheat alarm mode 

LS 

0=No use 

1=automatic return 

2= manual return 

 

4 0009 

Detect low superheat alarm 

LSH 

0.1 

0.5 

30.0 

0.5 

 

4 0010 

Low superheat alarm delay time 

LSD 

Sec. 

300 

15 

 

4 0011 

Clear low superheat alarm 

LSF 

0.1 

1.0 

30.5 

3.0 

 

4 0012 

Maximum operating pressure alarm mode (MOP) 

MP 

0=No use 

1=automatic return 

2= manual return 

 

4 0013 

MOP 

alarm detection pressure 

 

MOP 

bar 

0.1 

-1 

50 

9.0 

 

4 0014 

MOP 

alarm detection delay time 

 

MPD 

Min. 

15 

 

4 0015 

Clear MOP alarm 

MPF 

bar 

0.1 

-1 

50 

8.0 

 

4 0016 

High superheat alarm mode 

HS 

0=No use 

1=automatic return 

2= manual return 

 

4 0017 

Detect high superheat alarm 

HSH 

10 

40 

30 

 

4 0018 

High superheat alarm delay time 

HSD 

Sec. 

600 

 

4 0019 

Clear high superheat alarm 

HSF 

0.1 

37 

27 

 

4 0021 

Freeze prevention alarm mode 

FR 

0=No use 

1=automatic return 

2= manual return 

 

4 0022 

Detect freeze prevention alarm 

FRE 

℃ 

-40 

40 

 

4 0023 

Freezing protection alarm delay time 

FRD 

Sec. 

200 

30 

 

4 0024 

Clear freeze prevention alarm 

FRF 

℃ 

-37 

43 

 

4 0025 

Select pumpdown function and delay time 

PD 

Sec. 

180 

OFF

(-1) 

 

4 0026 

Pressure set-point for stopping pumpdown 

PDP 

bar 

0.1 

-0.5 

18.0 

0.5 

 

4 0027 

Pressure low limit alarm mode 

LP 

0=No use 

1=automatic return 

2= manual return 

 

4 0028 

Detect low limit pressure alarm 

LOP 

bar 

0.1 

-0.8 

17.7 

0.0 

 

4 0029 

Low limit pressure alarm delay time 

LPD 

Sec. 

200 

 

4 0030 

Clear low limit pressure alarm 

LPF 

bar 

0.1 

-0.5 

18.0 

0.3 

 

Содержание EVC10B Series

Страница 1: ...sed to control machineries Medical equipment vehicle train airplane combustion apparatus entertainment processing and transportation equipment elevator and various safety device etc enabling to effect...

Страница 2: ...40 120 Protection level IP65 Accuracy 1 0 F S Stability 0 5 Longterm Stability Connector Type 7 16 UNF FEMALE Wiring Black com Green out Red 5v 2 Installation Dimensions It can be installed with rail...

Страница 3: ...nsion valve First of all EVC10B needs to setup EEV mode to fit features of electronic expansion valve If EEV mode does not meet operation features of electronic expansion valve there can be malfunctio...

Страница 4: ...d save Display mode DIS parameter of parameter 2 group value will be changed Superheat Pressure of evaporator outlet Currentopenration ofEEV Temperature of evaporator outlet 4 Parameter Parameter chan...

Страница 5: ...g protection alarm is occurred caused by temperature of evaporator is getting low expansionvalveisfullyclosed 8Pumpdownfunction If input pumpdown delay time of 0 to 180 sec auxiliary relay RL1 outputs...

Страница 6: ...re shipment Setting 2 group table Menu 3 3 PR Users should input parameter which is suitable for characteristic of expansion valve In case of difference it may be caused by malfunction or valve and sy...

Страница 7: ...icexpansionvalve controller T sens Temp sensor of evaporatoroutlet Run Run Stopswitch TEV Thermostaticexpansion valve Application parameter Function CODE Min Max Default Setpointforcontroltarget SH 10...

Страница 8: ...sent pressure remains lower than set value of LOP duringLDP Lowlimitpressurealarmdelaytime Itwillbecausedbylackof refrigerant Itbecomesaclearconditionifpresentpressureismorethan setvalueofLPF LP 2 Fli...

Отзывы: