20
GB
Planning notes
General
Dornbracht must be consulted in advance about installations
that differ from the planning information.
Must not be combined with continuous-flow heaters heaters.
Flow pressure
Permissible flow pressure
250 – 400 kPa /
36 – 58 psi / 2.5 – 4 bar
Permissible flow pressure with
optional accessory EMBRACE
300 – 400 kPa /
44 – 58 psi / 3 – 4 bar
Recommended flow pressure
300 kPa / 44 psi / 3 bar
Fit a speed-controlled pressure booster in the main pipe, if
necessary.
Water hardness
Recommended water hardness:
6 – 7 °dH / 107 – 125 ppm CaCO3 / 7.5 – 8.8 °e /
10.7 – 12.5 °fH
If the water is harder, a water softener is to be installed in the
main cold water supply line.
Plumbing information
The pipework must be calculated in accordance with
EN 806-3, DIN 1988-300. To choose the perfect hot-water
supply – taking additional tapping points and simultaneous use
into consideration – an individual determination of requirements
(e.g. according to DIN 1988-200, DIN 4708-2, DIN 4753-7, VDI
6003) is absolutely necessary. The simultaneous use of all other
outlet points must be considered (simultaneity).
Drainage
Aquamoon
ATT
Drainage capacity / drain connection value [DU value]
0.8 l/s / 0.2 gps
Aquamoon
ATT
with optional accessory
Drainage capacity / drain connection value [DU value]
1.8 l/s / 0.5 gps
Recommended drain pipe size
DN 75 / NPS 3"
To choose the perfect drain – taking the flow rate of the entire
installation into consideration – an individual determination of
requirements is necessary. (e.g. in accordance with
EN 12056-1/-2, DIN 1986-100).
Electrical information
Observe the regulations for protection zones according to
DIN VDE 0100, Part 701 (IEC 60364-7-701). Please conform to
national statutory regulations, where different.
The following electrical components must be installed outside
safety zones 0 – 2:
–
fuse box,
–
fragrance modules.
As AQUAMOON
ATT
, complete hand shower set and SMART
TOOLS control elements are operated by safety extra-low
voltage (12 V), they can be installed in safety zone 1.
Space required for electrical components in the fuse box:
minimum 4 distributor rows with 12 division units each
(1 division unit = 18 mm / 5/8").
Space required for horizontally installed fragrance modules:
minimum 1,050 x 250 x 150 mm /
3 ft 5-3/8 " x 9-7/8 " x 5-7/8 " overall.
Space required for vertically installed fragrance modules:
minimum 350 x 750 x 150 mm /
1 ft 1-3/4 " x 2 ft 5-1/2 " x 5-7/8 " overall.
Provided by the customer:
–
Fuse box in accordance with planning requirements
–
Safety cut-out
–
Ground fault circuit interrupter
–
Circuit-breaker switch
–
4 x Rail mounting TS 35
–
Equipotential bonding rail
–
Network connection in accordance with TIA 568A, if
necessary
Observe:
–
Do not roll up excess cable lengths.
–
Shorten the excess cable lengths or fasten them in a
meandering pattern.