dormakaba MUTO M50 Ceiling Mount less Dormotion
Installation Instructions
MUTO Comfort
05-2018
936021
5
Track
Track
NOTE:
OVERHEAD REINFORCEMENT:
The overhead reinforcement must be a minimum of ¼”
[6] x 3” [76] steel angle, 16 gauge metal stud, or two
pieces of 1 1/2” [38] thick wood blocking (double
stacked), secured to studs or joists on a maximum 16”
[406] centers for the length of the track. The overhead
reinforcement may be flush on the overhead surface or
on the interior of this surface.
Track mounting screws must fully penetrate the steel
angle, metal stud, or at a minimum of 2” [51] into wood
blocking, utilizing the predrilled holes in the MUTO
track.
Consult with a structural engineer to determine if
reinforcement is adequate for your specific application
or to meet specific codes in your location.
2.2.1 Ensure the track is properly level and secure it to
the ceiling per the appropriate measurements on
the following page.
•
NOTE: SEE DIMENSION INSTRUCTIONS ON NEXT
PAGE FOR REFERENCE.
2.2.2 Use appropriate fasteners according to the
following recommendations.
2.2
Securing track to mounting surface
Fig 1