background image

4  Installation

The mounting of the slide rail system takes place 
directly on the door lintel or optionally with a 
mounting plate. 

4.1  Prepare the mounting of the 

slide rail

The slide rail can be mounted in 3 different options: 
Option 

= Mounting directly on the door lintel 

Option 

B

 = Mounting with mounting plate

Option 

C

 = Mounting with lintel casing angle

Mounting steps for options A, B and C

1. 

Prepare the power supply (24 V/48 V DC) from the 
smoke detection panel to the EMF in version with 
EMF.  

2. 

Take into account the mounting position on active 
leaf G and fixed leaf S.

3. 

Mark the fixing points for the closer and the slide 
rails according to the hole pattern.

4. 

Drill the holes.

5. 

Drill the hole for the connecting cable 
(24 V/48 V DC) Ø 8 mm in versions with EMF.

6. 

 Laying cables in versions with EMF.

Additional mounting steps for option B and C

7. 

Shorten the middle mounting plate or the middle 
lintel casing angle. 

8. 

Mount the mounting plate or lintel casing angle 
onto the door profile.

4.2  Mount the sliding rail of the 

fixed leaf

1. 

Insert the end caps connector into the slide rail.

2.  A

  Tighten the slide rail. 

B

  Tighten the slide rail  

 

on the pre‑installed mounting plate. 

C

  Tighten the slide rail  

 

on the pre‑installed lintel casing angle.

4.3  Mount the active leaf slide rail

1. 

Insert the end caps connector into the slide rail.

2.  A

  Tighten the slide rail. 

B

  Tighten the slide rail  

 

on the pre‑installed mounting plate. 

C

  Tighten the slide rail  

 

on the pre‑installed lintel casing angle.

4.4  Mount the door closer

ATTENTION

Risk of damaging the slide rail system

The dimensions on the drill template of the 
door closer are not suitable for the 
mounting of this product.
•  Use the dimensions from the drill pictures 

of the instruction of this product.

1. 

Mount the door closer and lever to the door leaf 
according to the enclosed instructions for the 
door closer. 

2. 

Adjust the door closer.

4.5  Shorten the connecting tube

1. 

Measure the dimension X.

2. 

Shorten the connecting tube to the dimension 
X‑41 mm.

4.6  Adjust the triggering roller on 

the door leaf

1. 

Close the fixed leaf.

2. 

Close the active leaf.

3. 

Unscrew the hexagon socket screw

4. 

Press on the lever of the triggering roller onto the 
door.

5. 

Tighten the hexagon screw.  
Pay attention to the torque 5 Nm.

6. 

Remove the screw.

4.7  Mount the connecting tube

1. 

Open of the active leaf. 

2. 

Open of the fixed leaf.

3. 

Screw in the adjusting sleeve up to marking.

4. 

Move the lever with the roll in direction to the 
opened active leaf until it clicks.

5. 

Insert of the connecting tube into the adjusting 
sleeve of the active leaf slide rail.

6. 

Insert the slide of the fixed leaf slide rail and fit 
the connecting tube into the retainer.

4

GSR XEA BG/GSR-EMF XEA BG

2017-10

dormakaba Mounting instructions

WN 059385 45532

Installation

Содержание GSR XEA BG

Страница 1: ...il 4 4 4 Mount the door closer 4 4 5 Shorten the connecting tube 4 4 6 Adjust the triggering roller on the door leaf 4 4 7 Mount the connecting tube 4 4 8 Set the sequential locking control 5 4 9 Check the sequential locking control 5 4 10 Connect the EMF 5 5 Start up 5 5 1 Set the fixture point 5 5 2 Set the release force 5 5 3 Mount the paneling 6 5 4 Check the EMF 6 5 4 1 Release EMF manually 6...

Страница 2: ... is authorized by dormakaba The operating of the slide rail system can be carried out by any person who is mentally and physically able 1 3 Provided documents Mounting instructions Additionally with GSR EMF XEA BG Data sheet about the use of catching devices 1 4 Symbols and abbreviations used 1 4 1 Safety instructions WARNING This statement indicates a situation of potential risk which could lead ...

Страница 3: ... for the use as fire and smoke protection closures in conjunction with the external RMZ and RM A separate verification of suitability is required for the respective fire smoke protection door 3 Product description The slide rail system ensures the correct order when closing 2 winged doors The slide rail system is intended for the mounting into the opposite hinge side The slide rail system is suita...

Страница 4: ...Insert the end caps connector into the slide rail 2 A Tighten the slide rail B Tighten the slide rail on the pre installed mounting plate C Tighten the slide rail on the pre installed lintel casing angle 4 4 Mount the door closer ATTENTION Risk of damaging the slide rail system The dimensions on the drill template of the door closer are not suitable for the mounting of this product Use the dimensi...

Страница 5: ... trigger the trigger must be moved 1 Close the fixed leaf 2 Loosen the screw 3 Push the trigger into the direction of the triggering roller 4 Tighten the screw 4 10 Connect the EMF Only for GSR EMF XEA 1 Lay the EMF connecting cables of the fixed leaf to the active leaf in a way that it is not resulting in jamming the connecting rod 2 Tighten the cable with zip ties 3 Insert the connection cable o...

Страница 6: ...ease of the RMZ etc The door leaves are released and close The active leaf closes only when the fixed leaf is closed 6 Operating Only for GSR EMF XEA 6 1 Open and lock door 1 Open door leaves to the fixture point The door leaves remain standing after letting go 6 2 Close door 1 Firstly press shut the fixed leaf then the active leaf against the resistance or press the optional manual release button...

Страница 7: ...7 GSR XEA BG GSR EMF XEA BG 2017 10 dormakaba Mounting instructions WN 059385 45532 ...

Страница 8: ...dormakaba Deutschland GmbH DORMA Platz 1 58256 Ennepetal Germany T 49 2333 793 0 F 49 2333 793 4950 www dormakaba com Translation of the original manual subject to change without notice ...

Отзывы: