dormakaba 9000 Delayed Egress Exit Device Installation
Instructions
95011817 (1135-88) IDE-20
01-2020
Exit Device
6
Key switch operation for device
1.6 Key switch operation for device
Delayed Egress Mode:
Unit is armed and touch bar will not activate the latchbolt.
(LED is solid green,
audible alarm is off)
. Initiated after power up, (DIP switch #2 in OFF position) authorized egress mode
or re-arm mode.
Nuisance Alarm Mode:
Unit is armed and touch bar will not activate the latch bolt.
(LED is solid green,
audible alarm sounds a short tone)
DIP switch selectable for 0, 1, 2 or 3 seconds. (See page 2) Initiated by
depressing touch bar.
Delay Mode:
Unit is armed and touch bar will not activate the latch bolt.
(LED is solid yellow, audible alarm
sounds intermittent tone)
. Unit remains in the delay mode for 15 seconds ( including nuisance time).
Initiated by holding the touch bar depressed past the nuidance alarm time (30 second delay mode option
available.) Once started, the delay mode is irreversible and automatically initiates the alarm mode.
Alarm Mode:
Unit is disarmed and touch bar will activate the latch bolt
(LED is solid red, audible alarm
sounds continous tone)
. Initiated automatically from the delay mode and is irreversible. Unit remains in
the alarm mode until manually reset with key.
By-Pass Mode:
From the delayed egress mode; unit is continuously disarmed and touch bar will activate
the latch bolt
(LED slowly flashes green, audible alarm is off). Initiated by rotating the key clockwise
(approximately 180 degrees), until switch engages, hold key until mode is activated.
DPS input is
disabled.
Re-arm Mode:
From alarm mode; unit goes to the delayed egress mode. Initiated by rotating the key
clockwise (approximately 180 degrees) until switch engages, hold key until mode is activated. From the
bypass mode; unit goes to the delayed egress mode. Initiated by rotating the key clockwise (approximately
180 degrees.) until switch engages, hold key until mode is activated.
The LED will return to solid green
.
Authorized Egress Mode:
Unit is disarmed for 5, 10, 15 or 20 seconds (DIP switch selectible) and touch bar
will activate the latch bolt
(LED quickly flashes green, audible alarm is off)
. After the authorized egress
time unit returns to the delayed egress mode automatically.
The authorized egress mode is initiated by
rotating the key counter-clockwise (approximately 180 degrees) until switch engages, hold key until
mode is activated.
DPS input will not initiate during the initial egress time, but will terminate the egress time if
the DPS closes before the end of egress time. DPS input will initiate an alarm after the egress time if the DPS
is opened.
NOTE:
The
By-pass
mode
and
Re-arm
mode
(orange wire) may be intiated externally from the terminal
connector. (Normally open dry contact to ground.) The
Authorized Egress mode
(white wire) may be
initiated externally from the terminal connector (Normally open dry contact to ground). See page 6 for
addtional details.
Bypass/Re-arm
Authorized Egress
Rotate Clock-wise
Rotate Counter Clock-wise