dormakaba 9000 Delayed Egress Exit Device Installation 
Instructions

95011817 (1135-88) IDE-20

01-2020

Exit Device

4

Cylinder specifications

DIP switch settings

1.3  Cylinder specifications

1.4  DIP switch setting

5/16" - 11/32"

Standard 1 1/8" mortise cylinder, randomly

keyed supplied by factory. Spacer required

for longer cylinder such as when using an

IC core.

1 1/8" Standard

21/32"

DE filler

    Cylinder

90J10SC118

    Actuator-DE

      95055525

 Cylinder nut

4000-167-501

Underside of filler

To Change Cylinder:

  Carefully remove filler from rail. Unscrew cylinder

nut, remove actuator and replace cylinder. Spacer required for cylinders

over 1 1/8". Insert cylinder as shown, re-install actuator & secure with

cylinder nut. Do not over tighten. Re-install filler in rail and reconnect the

small pigtail connectors. Use caution not to pinch or bind wires.

Note:

 If 

DIP

 switch settings are required to be changed, do it now prior to 

          re-installing filler in rail. (See Section below.)

(6310D)

  Cam

S3

S1

S3

S1

Underside of filler

OFF

ON

1

23

4

DIP switch settings should

be  completed at time of initial

installation; check local building 

code. Factory settings are as follows:

OFF

ON

1

23

4

Standard Factory Setting

OFF

ON

1

2

OFF

ON

3

4

  Factory

3 Seconds

    Factory

15 Seconds

1

2

3

4

1

2

3

4

1

2

3

4

 2 Seconds

5 Seconds

 1 Seconds

10 Seconds

  0 Seconds

20 Seconds

(1) Audible fire alarm:  

(On) Active

; (Off) Not active

(2) For future use.

(3) Power up state:  

(On) Locked

; (Off) Un-locked

(4) Door position switch:  

(On) In-Active

; (Off) Active

(1) Nuisance alarm time: (See chart below.)

(2) Nuisance alarm time: (See chart below.)

(3) Authorized egress time: (See chart below.)

(4) Authorized egress time: (See chart below.)

Содержание 9000DE Series

Страница 1: ...9000DE Series Delayed Egress Exit Device Installation instructions 95011817 01 2020 EN ...

Страница 2: ...Basic wire connection 5 1 6 Key switch operation for device 6 1 7 Cover end cap and label 7 1 8 Pair of doors 9100 DE Delayed Egress Exit Devices x YR09LFSC Electric Trim Fair Secure x ES100 Power Supply x ES105 Power Transfer x 3914W Sounder x MC 4 DPS x Card Readers 8 1 9 Single Door 9300 DE Delayed Egress Exit Device x YR09LFSC Electric Trim Fail Secure x ES100 Power Supply x ES105 Power Transf...

Страница 3: ...36 door opening withoutcutting Can be cutto fit a 32 minimum door opening 85 Decibel Alarm Standard LED Status Indicator Standard Nuisance Alarm Standard DIP Switch Settable Key Switch Control Standard Remote Authorized Egress Standard DIP Switch Settable Remote Re Arm Standard Remote Bypass Standard Door Position Input Standard DIP Switch Settable Auto Reset or Manual Reset DIP Switch Settable Au...

Страница 4: ...hten Re install filler in rail and reconnect the small pigtail connectors Use caution not to pinch or bind wires Note IfDIPswitch settings are required to be changed do it now prior to re installing filler in rail See Section below 6310D Cam S3 S1 S3 S1 Underside of filler OFF ON 1 23 4 DIP switch settings should be completed at time of initial installation check local building code Factory settin...

Страница 5: ... Specific project or custom wiring diagrams available on re quest consult the dormakabatechinical service department Product intended for indoor use NOTE Always disconnect power prior to making any connections or service It is recommended that the 120VAC power be supplied from an Uninterrupted Power Supply UPS to ensure proper operation during a power failure Always observe proper static discharge...

Страница 6: ...flashes green audible alarm is off Initiated by rotating the key clockwise approximately 180 degrees until switch engages hold key until mode is activated DPS input is disabled Re arm Mode From alarm mode unit goes to the delayed egress mode Initiated by rotating the key clockwise approximately 180 degrees until switch engages hold key until mode is activated From the bypass mode unit goes to the ...

Страница 7: ...uired order through Service Parts model number CBCLBL Consult with local code authority s having jurisdiction See CBC Secton 1003 1 10 Paragraph 6 KEEP PUSHING THIS DOOR WILL OPEN IN 15 SECONDS ALARM WILL SOUND LED light codes Solid Green Delayed Egress Mode Slow Flashing Green Bypass Mode Fast Flashing Green Authorized Egress Mode Solid Yellow Delay Mode Solid Red Alarm Mode This product meets or...

Страница 8: ...uctions 95011817 1135 88 IDE 20 01 2020 Exit Device 8 Pair of door template 1 8 Pair of doors 9100 DE Delayed Egress Exit Devices x YR09LFSC Electric Trim Fair Secure x ES100 Power Supply x ES105 Power Transfer x 3914W Sounder x MC 4 DPS x Card Readers dormakaba ...

Страница 9: ...tructions 95011817 1135 88 IDE 20 01 2020 Exit Device 9 Single door template 1 9 Single Door 9300 DE Delayed Egress Exit Device x YR09LFSC Electric Trim Fail Secure x ES100 Power Supply x ES105 Power Transfer x 3914W Sounder x MC 4 DPS x Card Readers dormakaba ...

Страница 10: ...www dormakaba us dormakaba DORMA USA Inc T 800 523 8483 ...

Отзывы: