background image

 

 

Stand  08.02.2012 

 

Technische Änderungen vorbehalten 

Software-Update_Ver1010_GB.doc 

DORMA KT-Systeme

 

Seite 14 von 14

 

 

KTC-2 (MS9) 

 
 
If all changes are carried out, please put the door system back into operation as 
follows: 

 
 

10. Initial operation of the door system 

 

  The emergency-stop is activated 

  The control system is switched on 

  Program switch KT on Automatic 1 

  The curved sliding door wings and the showcase doors are closed 

  The frequency converter and the CPU are parameterized 

  Door system is in summer position 

  Push Select push button and keep it pushed for 4 sec 

 Release emergency-stop 

 Learning cycle starts 

 

Indication of learning cycle and positioning drive 

During the learning cycle and positioning drive the display shows a gyro. 
 

 

  Door system rotates in positioning speed 

  The door system turns for min. 1 rotation  

  Afterwards the door system restarts with its regular function 

  Check all functions according to the original manual and/or the attached chart. 

  Check if the control system has learned the correct diameter. Check via parameter 

.  

 
 
 

11. Testing of changes 
 

-  Door systems with UPS: Revolving door has to rotate in program switch position 

Auto1 or Auto2 into summer position and stop there. 

-  Program switch position in „Summer“ and the sliding door is in operation (test all 

program switch positions of the sliding door), sliding door must stop in case the 
emergency-stop is activated and remain in this position as long as this is 
activated. 

-  Check all revolving door functions again. 

 

 

Done 

 
 
 
 
 

Содержание KTC-2

Страница 1: ...1 0 10 manual In order to keep your door systems updated please proceed with the following changes 1 Exchange CPU Z1 E60 0228 10 by the new one you already received Front view Relay K3 K7 Terminal block X101 X100 Microcell Three control unit N60 0685 Module for locking device E60 0120 Output module E60 0119 Input module E60 0118 CPU Z1 E60 0228 10 ...

Страница 2: ... view Frequency converter N60 0402 Mains filter N60 0405 Mains connection 230 V AC X103 24 V DC power supply unit N60 0583 Relay K1 N60 0560 Service power outlet max 300 W N60 0694 Collector 230VAC X105 Potentiometer for 24V DC adjustment Readout the parameter settings before exchanging in order to transfer these to the new CPU ...

Страница 3: ...itions in Automatic 1 or 2 2 5 2 U U C SlowStop canopy SlowStop time of canopy integrated sensors sec 0 15 sec 16 16 U U C SlowStop wing SlowStop time of wing sensor 0 1 sec 0 15 9 sec 16 0 16 0 U U C Hold after stop Time until the door starts after a safety stop 0 1 sec 0 9 9 sec 1 0 U U C Sec area stop Detection range of canopy integrated sensor in security area for SlowStop mm d pi 3 500 mm 700...

Страница 4: ...Stand 08 02 2012 Technische Änderungen vorbehalten Software Update_Ver1010_GB doc DORMA KT Systeme Seite 4 von 14 KTC 2 MS9 Z1 2 Reconnect NC at OUT4 to NO at the locking module IL1 OLD ...

Страница 5: ...Stand 08 02 2012 Technische Änderungen vorbehalten Software Update_Ver1010_GB doc DORMA KT Systeme Seite 5 von 14 KTC 2 MS9 Z1 NEW ...

Страница 6: ...rungen vorbehalten Software Update_Ver1010_GB doc DORMA KT Systeme Seite 6 von 14 KTC 2 MS9 3 Please check if terminals X101 59 and 60 are connected to IL1 see picture For doors with integrated sliding doors bridge X101 with 60 please ...

Страница 7: ..._GB doc DORMA KT Systeme Seite 7 von 14 KTC 2 MS9 4 Change the following in the UPS monitoring circuit New terminal strips X105 Additional relay K7 230VAC version Exchange the old terminal strip X105 by the new one and install the additional relay K7 Wiring as follows NEW K7 ...

Страница 8: ...Stand 08 02 2012 Technische Änderungen vorbehalten Software Update_Ver1010_GB doc DORMA KT Systeme Seite 8 von 14 KTC 2 MS9 ...

Страница 9: ...me Seite 9 von 14 KTC 2 MS9 5 Carry out the wiring as follows if the door system is furnished with UPS If a UPS is joined up in circuit put the inlet connector for non heating apparatus from X103 into the UPS and the other 230VAC adapter cable to be connected between UPS and control system at X103 ...

Страница 10: ...Stand 08 02 2012 Technische Änderungen vorbehalten Software Update_Ver1010_GB doc DORMA KT Systeme Seite 10 von 14 KTC 2 MS9 6 Is the door system without UPS please proceed with the wiring as follows ...

Страница 11: ...Stand 08 02 2012 Technische Änderungen vorbehalten Software Update_Ver1010_GB doc DORMA KT Systeme Seite 11 von 14 KTC 2 MS9 7 Re wire the inputs in the rotating part I1 here IN10 11 as follows ...

Страница 12: ...ysteme Seite 12 von 14 KTC 2 MS9 8 Adjust the crossover cable from the MS9 control system to ES200 Connect the delivered 2 wire cable 33 1 ES200 Not Halt with the terminals X101 33 34 and ES200 32 33 Remove bridge ES200 32 33 at ES200 beforehand New connection Terminal 47 is connected to 24VDC ...

Страница 13: ...T Systeme Seite 13 von 14 KTC 2 MS9 9 Change of emergency stop logic The ES200 drive will be stopped by emergency stop when activated The auxiliary contactor N60 0460 must be put on K1 contactor Normally open K1 53 and 54 to be connected to the terminals X101 33 and 34 as follows ES200 X101 ...

Страница 14: ... positioning drive During the learning cycle and positioning drive the display shows a gyro Door system rotates in positioning speed The door system turns for min 1 rotation Afterwards the door system restarts with its regular function Check all functions according to the original manual and or the attached chart Check if the control system has learned the correct diameter Check via parameter 11 T...

Отзывы: