4.2

Activators

Test all connected

activators

in the various program

switch settings.

Perform settings and adjustments

for

the activators

in accordance

with the corresponding

installation

instructions.

4.3

Emergency opening -

operation with back-up battery module

1.

Set the program switch to "OFF" and remove
mains plug.
Lock should not disengage and door should not

open.

?

Set program switch to "AUTOMATIC".
Door should unlock and open.

3.

Re-insert mains plug.

Door should close at creep speed.

4.

Leave program switch in "AUTOMATIC"

setting

and remove mains plug.

Door should open.

4.4

Emergency stop-

operation with backup battery module

1.

Set program switch to "AUTOMATIC"

and

during the closing cycle. operate the

emergency stop switch.

Door should stop and reverse.

4.5

Lock

Set program SWitch to "OFF".

• Door should be locked in closed condition.

In all other program switch settings.

• Door should be unlocked.

The lock can be adapted with the hand terminal

at the

request of the customer.

(See hand terminal

operating

instructions)

4.6

Night-bank

activator

1.

Set program switch to "OFF".

2.

Issue an opening signal uSing the

"NIGHT - BANK" activator.
The door should unlock and open.

The door should close and lock automatically

once

the user has passed through the door or, at the

latest, on expiry of the pre. set
"NIGHT - BANK hold.open

t,me",

3.

Remove mains plug

4.

Issue an opening SIgnal using the

"NIGHT.

BANK" activator.

Door should unlock and open as long as the
NIGHT.

BANK - signal remains live.

With the KT 8 key switch as the activator,

the

door can also be unlocked

if the power is

disconnected.

1.

Push the door closed by hand.

2.

Turn the key switch counter-clockwise.

Door should lock.

5. Further information

The door system performs a self-test

every 4 hours or

at appropriate

times after the system has been

switched on.

In this self-test, an emergency opening cycle is

performed under battery power and the control unit is

checked for integrity.

If the self-test should fail, the

door remains in the open position.

The door can be closed by setting the

program switch to "OFF".

At the next opening signal, a further self-test is

performed.

6. Optional functions

If the functions

described below have been

implemented,

they must be tested as follows.

6.1

Air lock (two doors in tandem)

Depending on the side from which the opening signal
is initiated.

the first door in the access sequence

should initially

open and then close.

Only after the first door has closed should the second
door open and close.

6.2

Presence detector (bell contact)

Check the bell contact by interrupting

the light

barriers.

6.3

Door status monitor

Check the audible or visual door status detectors.

6.4

Panic/emergency

closing

It'

The panic/emergency

closing function

is subject

ill

to special statutory regulations.

Consequently,

it

is imperative

to ensure compliance

with the

relevant national regulations.

The panic/emergency

closing function

must be set

using the DIP switches and hand terminal.

Initiate a NIGHT/BANK

signal in each of the program

switch modes "AUTOMATIC",

"EXIT ONLY", "PARTIAL

OPEN" and "PERMANENT

OPEN".

• The door should close immediately.

The door should not open either when the light barriers
are interrupted

or when a signal is issued

by

radar

detectors.

Cancelling the panic/emergency

closing function:

Set the program switch to

uOFF",

and then back to the

required mode.

Then test all the other functions.

Opening and reversing via the radar detector.

• Reversing via the light barriers.

Содержание ES 100

Страница 1: ...n DORMA ES 90 100...

Страница 2: ...UK training department1 2 25 20044 14 PM DORMA 6...

Страница 3: ...UKT aining Dcpartll1e nt UK training departmentl 2 25 20044 14 PM t A f DORM 7...

Страница 4: ...UK training department1 2 25 20044 14 PM DORMA 8...

Страница 5: ...UK training department1 2 25 20044 14 PM DORMP 9...

Страница 6: ...loses a short distance up to three times 8 Briefly depress the service pushbutton The door opens quickly the control unit stores the door parameters and then performs a back up battery test Ir When us...

Страница 7: ...2 Turn the key switch counter clockwise Door should lock 5 Further information The door system performs a self test every 4 hours or at appropriate times after the system has been switched on In this...

Страница 8: ...pliance with the standard and they can be adjusted using the hand terminal E5 901100 control units with molar type GR63x25 Opening speed 57 Creep speed CLOSE 53 DeeP speed distance ClOSE 100 Force lim...

Страница 9: ...eans unlocking successfully completed 3x flashes means lockmg successfully completed lights up when both limit switches are either open or closed In the idle state Continuous Itght signals fault Buzze...

Страница 10: ...v 8 controls The lock type must be programmed using the hand terminal If the enabled lock type is a concealed rod multipoint lock the Locking contact input on the EM 4 is converted to a disabling inpu...

Страница 11: ...recharged Check back up battery voltage door remains stationary in or now spent Check operating hours with HT OPEN posltion Change back up battery only in the case of control units with an expansion...

Страница 12: ...am switch in the sequence AUTOMATIC OFF AUTOMATIC Check the continuity from terminal 17 to terminal 20 Connect voltmeter to the terminals of the limit switch Initiate closing cycle During the closing...

Страница 13: ...lay Condition Function e Normal mode Normal mode Mains power available power supply unit energised 0 Off unit not receiving mains power C Flashing frequency 2 Hz Learning cycle parameters are being de...