HOLD OPEN SET SCREWS - 3/32 HEX

Hold open position is preset at approximately 90°.
Loosen set screws using 3/32 inch hex wrench. Slide hold open device to desired position.

 SD2 DETECTOR SENSITIVITY TEST (ULC REQUIREMENT ONLY)

Open door so slide shoe engages with hold open assembly.

16

15

Retighten set screws securely.

FINAL INSTALLATION AND TEST

14

13

OPEN ANGLE

GREATER HOLD 

rotate into possession. Insert (1) 4-40 screw 

DETECTOR

Slide tab of cover under end of detector and 

SCREW

and tighen.

ROTATE

Install detector cover.

18

17

TAB

HOLD OPEN DEVICE

OPEN ANGLE

LESS HOLD  

 HOLD OPEN FORCE ADJUSTMENT - 5/32 HEX

 CLOCKWISE = STRONGER

With power applied to the detector, connect a volt meter to the two test terminals.

Voltage output terminals are provided to measure the sensitivity of the smoke detector. 

The normal range is between 1.27 - 3.38 Vdc.

SENSITIVITY TEST TERMINALS

to ten (10) seconds to indicate the unit is

connections. The LED will blink every seven (7) 

After installation is completed, check all

LED

operating properly.

The LED should remain continually red and allow

Turn counterclockwise and hold for ten seconds.

into the slot in the light pipe of the detector.

To test the detector, insert a small screwdriver

the door to close.

Turn light pipe clockwise to reset the detector.

The LED will go off. Turn the light pipe to the

normal position and the unit will resume blinking  

every seven (7) to ten (10) seconds to indicate  

that it is reset and functioning properly.

INS NO.

PAGE

Rev.

08281010

12 of 14

08/13

Содержание 8600 EMR Series

Страница 1: ...unit double door applications is a companion to the main unit and its electromagnet de energizes along with the main unit A remote open area detector sensing smoke alarms the 8600 EMR to which it is c...

Страница 2: ...g Install track to frame Install with detector cut out toward latch edge of door using 2 1 4 20 x 2 metal or 2 No 14 x 2 3 4 wood screws C HINGE END CAP C HINGE 4 SURFACE CONDUIT END CAP 8600PT 8600T...

Страница 3: ...8 LEFT HAND DOOR 8600PT RIGHT HAND DOOR RIGHT HAND DOOR LEFT HAND DOOR 8600T AND 8600DE Install closer to door 7 QTY 4 INS NO PAGE Rev 08281010 3 of 14 08 13...

Страница 4: ...Attach main arm to door closer RIGHT HAND DOOR HINGE C 8600T 8600DE 3 0 914 2 6 762 Exterior 3 6 1067 3 0 914 2 6 762 Interior 0 11 5 4 3 5 100 125 150 3 6 1067 4 0 1219 13 6 200 3 16 HEX KEY 3 16 HE...

Страница 5: ...TE DETECTORS ARE USED IN THIS APPLICATION TERMINAL 3 14 1 2 6 9 8 7 15 4 5 13 10 N O 8 N C 9 COM 10 ELECTRICAL SPECIFICATIONS Voltage input Maximum input current Maximum output to Remote Contact ratin...

Страница 6: ...onnect terminal 3 of the first unit to terminal 3 of the second unit and connect terminal 14 of the first unit to terminal 14 of the second unit Continue this process for any subsequent units to be po...

Страница 7: ...ly to the first solenoid station D2 D3 D4 etc are the distances from the previous solenoid station to the next solenoid station in the run To determine the correct wire gauge multiply E1 times D1 Add...

Страница 8: ...4 6 1 9 10 11 12 13 14 5 7 15 SD2 8 2 3 4 6 1 9 10 11 12 13 14 5 7 15 SD2 1 Up to 5 SD2 detectors with or without connection to an auxiliary unit or remote area detector may be interconnected This lim...

Страница 9: ...iring section Perform wiring connections as illustrated below NOTE The SD2 is wired as the E O L end of line device for the remote detector Therefore it must act as the last item in the loop CONTROL U...

Страница 10: ...TING CIRCUIT CONNECTIONS FOR SIX 6 WIRE INSTALLATION RETURN LOOP ALARM RELAY EOL USED IN 4 WIRE APPLICATIONS ONLY REMOTE DETECTOR INITIATING CIRCUIT UL ULC LISTED 1 Make all connections as outlined pr...

Страница 11: ...The last unit in the run must be connected in the same manner as unit 3 5 More than three 3 SD2 detectors are connected by inserting additional units with connections to detector 3 in the same manner...

Страница 12: ...etector connect a volt meter to the two test terminals Voltage output terminals are provided to measure the sensitivity of the smoke detector The normal range is between 1 27 3 38 Vdc SENSITIVITY TEST...

Страница 13: ...SYSTEM THE END THE INITIAL INSTALLATION TEST IN CONJUNCTION WITH SYSTEM MUST ALSO BE TESTED PERIODICALLY AFTER WHEN THE ALARM SYSTEM IS ACTIVATED THE ENTIRE THAT THE DOOR CLOSER UNITS FUNCTION PROPER...

Страница 14: ...detector Signal processing is a feature that adds a time delay to each detector which effectively increases its stability If this is the case spray in repeated bursts of 1 second at approximately 5 t...

Отзывы: