GENERAL DESCRIPTION

Each 8600 EMR series unit contains a door closer, hold 

open electromagnet and smoke detector.  The unit can be 

used as a single installation or as a series of singles 

powered from one or more power supplies.  When a 

series of 8600 EMR units are wired together in a run, 

groups of up to 5 units may be interconnected.  

Interconnection is accomplished through terminals #4 

and #15 and results in all units alarming when any one 

of them senses smoke.  In turn, all associated hold 

open electromagnets are de-energized.  Within any run of 

detectored units, it is permissible to form as many 

interconnected groups as the total power supply 

amperage will allow; but, again no more than 5 units 

can be interconnected together. 

Any detectored 8600 EMR series unit can be connected 

to an auxiliary EMF non-detectored unit, or remote 

detector, or both.  It can be a single installation or part 

of any of the multiple  arrangements described above. 

An auxiliary unit (double door applications) is a 

companion to the main unit, and its electromagnet 

de-energizes along with the main unit.  A remote open 

area detector sensing smoke alarms the 8600 EMR to 

which it is connected and any other 8600 EMR to which 

it is interconnected.

Single installations or groups of installations can be 

connected to the alarm initiation circuit of a compatible 

UL/ULC listed fire alarm control  unit  in 4-wire or 6-wire 

configurations.

Additional  functions  are  provided  to separately power 

the hold open electromagnet directly from the alarm control 

panel as well as connections for a remote alarm 

indicator lamp. 

INSTALLATION

1. Read entire instruction sheet prior to installation

    and refer to NFPA 72E. Standards may be obtained

    from THE NATIONAL FIRE PROTECTION 

    ASSOCIATION, Batterymarch Park, Quincy,

    MA 02269. 

2. Reference unit carton for unit mounting type.

3. Prepare door and frame for fasteners using the 

    appropriate template.  Mark, drill, and tap holes as

    indicated.  If surface wiring is used, omit 7/8" hole

    for wire access.

8600 EMR SERIES

INSPK NO. 08280580 Rev.06/11

INS NO.

Rev.

08281010

08/13

PAGE

1 of 14

www.dorma-usa.com    1-800-523-8483

Содержание 8600 EMR Series

Страница 1: ...unit double door applications is a companion to the main unit and its electromagnet de energizes along with the main unit A remote open area detector sensing smoke alarms the 8600 EMR to which it is c...

Страница 2: ...g Install track to frame Install with detector cut out toward latch edge of door using 2 1 4 20 x 2 metal or 2 No 14 x 2 3 4 wood screws C HINGE END CAP C HINGE 4 SURFACE CONDUIT END CAP 8600PT 8600T...

Страница 3: ...8 LEFT HAND DOOR 8600PT RIGHT HAND DOOR RIGHT HAND DOOR LEFT HAND DOOR 8600T AND 8600DE Install closer to door 7 QTY 4 INS NO PAGE Rev 08281010 3 of 14 08 13...

Страница 4: ...Attach main arm to door closer RIGHT HAND DOOR HINGE C 8600T 8600DE 3 0 914 2 6 762 Exterior 3 6 1067 3 0 914 2 6 762 Interior 0 11 5 4 3 5 100 125 150 3 6 1067 4 0 1219 13 6 200 3 16 HEX KEY 3 16 HE...

Страница 5: ...TE DETECTORS ARE USED IN THIS APPLICATION TERMINAL 3 14 1 2 6 9 8 7 15 4 5 13 10 N O 8 N C 9 COM 10 ELECTRICAL SPECIFICATIONS Voltage input Maximum input current Maximum output to Remote Contact ratin...

Страница 6: ...onnect terminal 3 of the first unit to terminal 3 of the second unit and connect terminal 14 of the first unit to terminal 14 of the second unit Continue this process for any subsequent units to be po...

Страница 7: ...ly to the first solenoid station D2 D3 D4 etc are the distances from the previous solenoid station to the next solenoid station in the run To determine the correct wire gauge multiply E1 times D1 Add...

Страница 8: ...4 6 1 9 10 11 12 13 14 5 7 15 SD2 8 2 3 4 6 1 9 10 11 12 13 14 5 7 15 SD2 1 Up to 5 SD2 detectors with or without connection to an auxiliary unit or remote area detector may be interconnected This lim...

Страница 9: ...iring section Perform wiring connections as illustrated below NOTE The SD2 is wired as the E O L end of line device for the remote detector Therefore it must act as the last item in the loop CONTROL U...

Страница 10: ...TING CIRCUIT CONNECTIONS FOR SIX 6 WIRE INSTALLATION RETURN LOOP ALARM RELAY EOL USED IN 4 WIRE APPLICATIONS ONLY REMOTE DETECTOR INITIATING CIRCUIT UL ULC LISTED 1 Make all connections as outlined pr...

Страница 11: ...The last unit in the run must be connected in the same manner as unit 3 5 More than three 3 SD2 detectors are connected by inserting additional units with connections to detector 3 in the same manner...

Страница 12: ...etector connect a volt meter to the two test terminals Voltage output terminals are provided to measure the sensitivity of the smoke detector The normal range is between 1 27 3 38 Vdc SENSITIVITY TEST...

Страница 13: ...SYSTEM THE END THE INITIAL INSTALLATION TEST IN CONJUNCTION WITH SYSTEM MUST ALSO BE TESTED PERIODICALLY AFTER WHEN THE ALARM SYSTEM IS ACTIVATED THE ENTIRE THAT THE DOOR CLOSER UNITS FUNCTION PROPER...

Страница 14: ...detector Signal processing is a feature that adds a time delay to each detector which effectively increases its stability If this is the case spray in repeated bursts of 1 second at approximately 5 t...

Отзывы: