Upright refrigerators and freezers 

 

 

  In accordance with the EN378 standard it should be ensured that the room where the device 
with  R290  medium  is  to  be  located  has  the  proper  volume.  1  m

3

  is  required  for  8  g  of  R290 

refrigerant.  The  amount  of  R290  refrigerating  medium  is  specified  on  the  rating  place  of  the 
device. 

 

CONNECTION TO ELECTRIC SYSTEM 

 

The construction of the device is made according to the appropriate directives and harmonised standards: 
- low voltage directive 2006/95/EC, 
- electromagnetic compatibility directive 2004/108/EC, 
- PN-EN 60335-2-89:2012, PN-EN 60335-1:2012 standards, 
- PN-EN 55014-1:2012, PN-EN-55014-2:1999 standards, 
- PN-EN 61000-3-2:2007, PN-EN 61000-3-3:2009 standards. 
The device is adapted to be supplied from the 230V 50Hz line and should be supplied from a separate 

low voltage circuit. A grounded plug-in socket must be equipped with anti-shock protection selected, according 
to the requirements of local standards and regulations, in compliance with the parameters specified on the 
rating plate. The parameters of a residual current device should be selected according to the current value, 
specified on the rating plate. The devices are provided with a flexible power supply cable of HO5VV-F type 
(3x1,5mm²,  including  protective  conductor).  The  damaged  power  supply  cable  should  be  replaced  by  a 
specialist from technical service or by a skilled person with appropriate qualifications. 

The devices are equipped with a terminal to connect external equipotential bonding, marked by a symbol 

.  Before  connecting  the  device  the  installation  correctness  and  effectiveness  of  equipotential  bonding 

operation should be checked in accordance with PN-IEC-60364-4-41 
 

 
 The device can be started when effectiveness of anti-shock protection is confirmed by results 
of measurements carried out according to the regulations in force. 

 

 

The device can be connected to the electric system when it is stated that the electric system fulfils the 

afore-mentioned requirements. The device is connected by inserting a plug of connecting cable into the plug-
in socket. A device, prepared in such a way, is ready to operate. 

 

 

Because during transport the device could be inclined by more than 30

 from the vertical, wait 

about  1  hour  before  connecting  the  device  to  the  power  supply  system.  Otherwise,  the 
condensing unit can be damaged.   

 

 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 

 
 
 
 

Содержание DM-92601

Страница 1: ...601 BA DM 92621 DM 92621 BA DM 92602 BA DM 92622 DM 92622 BA DM 92603 BA DM 92624 DM 92624 BA DM 92604 BA DM 92625 DM 92625 BA DM 92609 BA DM 92612 BA DM 92614 BA DM 92615 BA DM 92616 BA UPRIGHT FREEZ...

Страница 2: ...EN DORA METAL Edition 28 06 2019...

Страница 3: ...nimum distance between the edge of the upright refrigerator or freezer and the ceiling of the room should be 400 mm In order to ensure the correct operation of the device and to obtain the parameters...

Страница 4: ...teel upright refrigerators of DM 926xx series 9 Table 2 Stainless steel upright refrigerators without compressor of DM 926xx BA series 9 Table 3 Stainless steel upright refrigerators of DM 9262x serie...

Страница 5: ...out by the operating personnel provided that the below mentioned recommendations are strictly observed The producer shall not take responsibility for any operation carried out on the device without ob...

Страница 6: ...ent device should be selected according to the current value specified on the rating plate The devices are provided with a flexible power supply cable of HO5VV F type 3x1 5mm including protective cond...

Страница 7: ...time it is recommended to stop the operation of the device to clean its interior defrost naturally the evaporator unit clean the condenser of the refrigeration unit and check the condition of the doo...

Страница 8: ...cer does not assume responsibility for the device that is damaged during the transport DISPOSAL Prior to the transport the device is protected by a packing crate which consists of the following recycl...

Страница 9: ...e Climatic class Type of refrigeration unit Type of refrigerant R290 Amount of refrigerant kg 0 075 GWP ODP 3 Table 2 Stainless steel upright refrigerators without compressor of DM 926xx BA series Dat...

Страница 10: ...late Climatic class Type of refrigeration unit Type of refrigerant R290 Amount of refrigerant kg 0 08 GWP ODP 3 Table 4 Stainless steel upright refrigerators without compressor of DM 9262x BA series D...

Страница 11: ...imatic class Type of refrigeration unit Type of refrigerant R290 Amount of refrigerant kg 0 13 GWP ODP 3 Table 6 Stainless steel upright freezers without compressor of DM 926xx BA series Data Catalog...

Страница 12: ...16 with controller LAE AT2 5BQ4E AG ST E4 Evaporation heater E3 Evaporation heater in cooler tray E2 Gasket heater E1 Defreezing heater W Bunch T Power supply S3 S4 Door switch S2 Rocker switch S1 Con...

Страница 13: ...E4 Evaporation heater E3 Evaporation heater in cooler tray E2 Gasket heater E1 Defreezing heater W Bunch T Power supply S3 S4 Door switch S2 Rocker switch S1 Controller Ez Electromagnetic valve M4 Mo...

Страница 14: ...vaporation heater E3 Evaporation heater in cooler tray E2 Gasket heater E1 Defreezing heater W Bunch T Power supply S3 S4 Door switch S2 Rocker switch S1 Controller Ez Electromagnetic valve M4 Monoblo...

Страница 15: ...ration heater E3 Evaporation heater in cooler tray E2 Gasket heater E1 Defreezing heater W Bunch T Power supply S3 S4 Door switch S2 Rocker switch S1 Controller Ez Electromagnetic valve M4 Monobloc M3...

Страница 16: ...E4 Evaporation heater E3 Evaporation heater in cooler tray E2 Gasket heater E1 Defreezing heater W Bunch T Power supply S3 S4 Door switch S2 Rocker switch S1 Controller Ez Electromagnetic valve M4 Mon...

Страница 17: ...ation heater E3 Evaporation heater in cooler tray E2 Gasket heater E1 Defreezing heater W Bunch T Power supply S3 S4 Door switch S2 Rocker switch S1 Controller Ez Electromagnetic valve M4 Monobloc M3...

Страница 18: ...5 BA DM 92616 BA with controller LAE AT2 5BQ4E AG ST E4 Evaporation heater E3 Evaporation heater in cooler tray E2 Gasket heater E1 Defreezing heater W Bunch T Power supply S3 S4 Door switch S2 Rocker...

Страница 19: ...G ST E4 Evaporation heater E3 Evaporation heater in cooler tray E2 Gasket heater E1 Defreezing heater W Bunch T Power supply S3 S4 Door switch S2 Rocker switch S1 Controller Ez Electromagnetic valve M...

Страница 20: ...4 Evaporation heater E3 Evaporation heater in cooler tray E2 Gasket heater E1 Defreezing heater W Bunch T Power supply S3 S4 Door switch S2 Rocker switch S1 Controller Ez Electromagnetic valve M4 Mono...

Страница 21: ...oration heater E3 Evaporation heater in cooler tray E2 Gasket heater E1 Defreezing heater W Bunch T Power supply S3 S4 Door switch S2 Rocker switch S1 Controller Ez Electromagnetic valve M4 Monobloc M...

Страница 22: ...B E4 Evaporation heater E3 Evaporation heater in cooler tray E2 Gasket heater E1 Defreezing heater W Bunch T Power supply S3 S4 Door switch S2 Rocker switch S1 Controller Ez Electromagnetic valve M4...

Страница 23: ...ation heater E3 Evaporation heater in cooler tray E2 Gasket heater E1 Defreezing heater W Bunch T Power supply S3 S4 Door switch S2 Rocker switch S1 Controller Ez Electromagnetic valve M4 Monobloc M3...

Страница 24: ...controller LAE AT2 5BQ4E AG ST E4 Evaporation heater E3 Evaporation heater in cooler tray E2 Gasket heater E1 Defreezing heater W Bunch T Power supply S3 S4 Door switch S2 Rocker switch S1 Controller...

Страница 25: ...vaporation heater E3 Evaporation heater in cooler tray E2 Gasket heater E1 Defreezing heater W Bunch T Power supply S3 S4 Door switch S2 Rocker switch S1 Controller Ez Electromagnetic valve M4 Monoblo...

Страница 26: ...ation heater E3 Evaporation heater in cooler tray E2 Gasket heater E1 Defreezing heater W Bunch T Power supply S3 S4 Door switch S2 Rocker switch S1 Controller Ez Electromagnetic valve M4 Monobloc M3...

Страница 27: ...ation heater E3 Evaporation heater in cooler tray E2 Gasket heater E1 Defreezing heater W Bunch T Power supply S3 S4 Door switch S2 Rocker switch S1 Controller Ez Electromagnetic valve M4 Monobloc M3...

Страница 28: ...27 BA with controller LAE AT2 5BQ4E AG ST E4 Evaporation heater E3 Evaporation heater in cooler tray E2 Gasket heater E1 Defreezing heater W Bunch T Power supply S3 S4 Door switch S2 Rocker switch S1...

Страница 29: ...4 Evaporation heater E3 Evaporation heater in cooler tray E2 Gasket heater E1 Defreezing heater W Bunch T Power supply S3 S4 Door switch S2 Rocker switch S1 Controller Ez Electromagnetic valve M4 Mono...

Страница 30: ...ration heater E3 Evaporation heater in cooler tray E2 Gasket heater E1 Defreezing heater W Bunch T Power supply S3 S4 Door switch S2 Rocker switch S1 Controller Ez Electromagnetic valve M4 Monobloc M3...

Страница 31: ...ration heater E3 Evaporation heater in cooler tray E2 Gasket heater E1 Defreezing heater W Bunch T Power supply S3 S4 Door switch S2 Rocker switch S1 Controller Ez Electromagnetic valve M4 Monobloc M3...

Страница 32: ...ater in cooler tray E2 Gasket heater E1 Defreezing heater W Bunch T Power supply S3 S4 Door switch S2 Rocker switch S1 Controller Ez Electromagnetic valve M4 Monobloc M3 Condenser fan M2 Compressor M1...

Страница 33: ...heater in cooler tray E2 Gasket heater E1 Defreezing heater W Bunch T Power supply S3 S4 Door switch S2 Rocker switch S1 Controller Ez Electromagnetic valve M4 Monobloc M3 Condenser fan M2 Compressor...

Страница 34: ...defreezing In such a case the only possibility of defreezing the cooler is turn off the device and wait for the natural ice melting on the cooler Call the service in order to remove the defect dEF De...

Страница 35: ...nsor 3 Messages from controller INFO Messages available in menu INFO after pushing info buton t1 Temperature of sensor 1 thi Maximum saved temp T1 t2 Temperature of sensor 2 tLo Minimum saved temp T1...

Страница 36: ...n the control panel Mode ECO The advanced controller used in the device detects automatically the operating conditions of the mode ECO When the proper conditions are detected the controller switches t...

Страница 37: ...al pl E mail info dora metal pl serwis dora metal pl serwis tel 602 286 179 Information included in this document may be changed by DORA METAL without prior notification of the user Any part of this d...

Отзывы: