SL4750183 -EN

 

Fig 3. Location of Connection Port on Back Side of 
DSE 4510MKII  
 

 

 

 

Once connected from DSE controller to PC/Laptop- 
proceed to open DSE Configuration Suite. 
On the startup page click “read configuration from a 
module” (See Fig 4). 
 

Fig 4. DSE Configuration Suite- Startup Page. 
 

 

 

3. Edit Controller Profile. 

 
With the profile from the controller open in DSE 
Configuration Suite- Click “inputs” 
 

Fig 5. DSE Configuration Suite “Inputs” 

 

 

 
 
Proceed to next menu by clicking “Coolant Temperature” 

 
 
 
 
 

Fig 6.

 

DSE Configuration Suite “Coolant Temperature” 

 

 

 
Once in “Coolant Temperature” Menu- proceed by 
unchecking the “Temperature Sensor Open Circuit Alarm”. 
 

Fig 7. DSE Configuration Suite “Temperature Sensor 
Open Circuit Alarm”. 
 

 

 
4. Write profile to controller 

 
With the “Temperature Sensor Open Circuit Alarm” 
disabled-  the profile is now ready to be written to 
controller.  
Click the “write to module” icon in top left corner of DSE 
Configuration Suite.  You will be prompted “Write this 
Configuration?” Select yes. Controller is programmed. 
   

Fig 8.

 

DSE Configuration Suite- Write to controller

 

 

 

 

 
 
 