 Loop  Info-Q-2-16

7

Loop Detector Cross-Talk and False Calls 

The actual loop operating frequency (in KHz) is a function of the frequency DIP-switches on the loop 
detector. A common problem with loops are when they are positioned too close to each other and 
their detection fields overlap. If the loops are on similar frequencies, this can cause “cross-talk” 
between the loops and “false calls” can occur in the loop detector. Changing the frequency of 

one

 

loop (switching it’s frequency as far away from the other loop’s frequency as possible) will eliminate 
the “false calls”. Switching the frequency of a loop 

WILL NOT

 affect the loop’s detection height. 

Detection Field Around Loops

It is important that the loops are installed far enough away from all moving metal 
objects (gate) to keep the loop’s detection fields clear. The 1/2 to 2/3 the length 
of the short leg of the loop will determine a detection field limit. Do not install the 
loop closer to the gate than the short leg of the loop otherwise the movement of 
the gate will interfere with the loop’s detection field and the loop detector will 
give a “false call” and reverse the gate’s direction in mid-cycle. 

A simplified 

solution is to place loops AT LEAST 4 feet away from each other or the gate.

Frequency 

DIP-switches 

9410

L1

Reverse

 Loop

Short Leg

Length

1/2 to 2/3rd Short Leg Length Detection Field

1/2 to 2/3rd Short Leg Length Detection Field 

When loop detection fields do not overlap, 
loop detectors can be on similar frequencies. 

When loop detection fields overlap, loop detectors 

MUST

 be on 

different frequencies or they will “cross-talk”. (See below) 

Reverse

 Loop

Slide Gate

Swing Gate 

Loop Detection Field Interference and Loop Placement

Reverse 

 Loop 

Short Leg

Length

Reverse 

 Loop 

Shadow Loop

See page 12 for

more information.

Optional 

Automatic 

Exit Loop 

Optional

Automatic

Exit Loop

Short Leg

Distance

Short Leg

Distance

Short Leg

Distance

or 4 ft Min.

from Gate

Drawings not to scale

or 4 ft Min.

from Gate

Loop Detection Field

Loop Detection Field

Loop Detection Field

Loop Detection Field

or 4 ft Min.

from Gate

Содержание 9409 Dual Channel

Страница 1: ...DoorKing Inc All rights reserved Underground Loops and Loop Detectors Underground Loops and Loop Detectors DoorKing Plug In Loop Detectors and Loop Accessories 9409 Dual Channel 9410 Single Channel 9...

Страница 2: ......

Страница 3: ...cellation Effect Field Enhancement Effect Loop Phasing Electrically Reverse the Phase of a Loop Loop Detection Field Interference and Loop Placement Saw Cut Loop Guidelines DoorKing Preformed Loop Gui...

Страница 4: ...with a loop measuring 6 on the short leg Loops can be saw cut into concrete or asphalt They can be placed under brick pavers and asphalt or be imbedded in a poured concrete road surface Design Facts U...

Страница 5: ...ne to its environment Stationary or static metal objects such as conduits pipes metal grates etc will not affect the loop field High voltage electrical power lines either underground or overhead can a...

Страница 6: ...e height than a passenger car The height of detection above and below the loop is determined by the shortest leg of the loop The height of detection is equal to 1 2 to 2 3 the length of the SHORT LEG...

Страница 7: ...ops in the opposite direction Clockwise or Counter Clockwise electrically creates the effect of the electrical current passing through the closest edges of the loops in the same direction Since the el...

Страница 8: ...they must be the same size same number of turns and the same distance from the gate They must be connected in series and the direction in which each loop is wound is important for proper door or gate...

Страница 9: ...ser to the gate than the short leg of the loop otherwise the movement of the gate will interfere with the loop s detection field and the loop detector will give a false call and reverse the gate s dir...

Страница 10: ...od spaced approximately one 1 foot apart along the entire length of the saw cut and exit slot Make certain to press the backer rod tightly into the slot Use a wooden stick or other blunt instrument to...

Страница 11: ...on Straight saw cut 45 corner saw cut Twist wire from this point to loop detector Exit Slot NO Sharp Angles Watertight J Box Sweep Loop Lead In Wire or Cable to Operator in PVC Conduit Tape on end to...

Страница 12: ...and Gravel Base 1 Minimum Depth Hold Down Stakes Hold Down Stakes Styrofoam Blocks T connector accepts 1 2 PVC conduit Poured Concrete Asphalt 2 to 3 Depth Loop Lead In Wires T connector accepts 1 2 P...

Страница 13: ...up to it Typically a loop lead in cable will need to be installed Pages 2 and 6 Loop should to be far enough away from the reverse loop to avoid any cross talk or on a different loop detector frequenc...

Страница 14: ...detector frequency if detection fields overlap Page 7 Reverse Loop Optional Automatic Exit Loop Reverse Loop Shadow Loop Loop Lead In Wire Primary Operator Secondary Operator Loop Lead In Wires Loop L...

Страница 15: ...er capable of testing up to 500 megohms 500 million ohms such as a DoorKing meter P N 9401 045 A typical ohms meter will not read units as small as micro henries Disconnect the loop wires from the loo...

Страница 16: ...ate operators Manufactured by DoorKing Inc Megohm meter Checks integrity of ground loops Reads up to 500 megohms Asphalt sealant flat black 10 oz tube Concrete sealant gray 10 oz tube Two channel plug...

Страница 17: ...Loop Detectors Underground Loops and Loop Detectors DoorKing Plug In Loop Detectors and Loop Accessories DoorKing Inc 120 S Glasgow Avenue Inglewood California 90301 U S A Phone 310 645 0023 Fax 310 6...

Отзывы: