[CHAPTER 7 CAUSE OF FAULT AND REACTION]
7-2
|
DOOCHPUMP
7.2 Reset of fault and alarm
ㆍ
In case of fault or alarm, FND shows Pr-80.
ㆍ
To reset in Pr-group, Press
twice.
ㆍ
To reset in St-group, Press
once.
In case of Er-01, Er-02, Er-04(Low Level Sensor Alarm), If cause is resolved, it reset and
restart automatically.
In case of reset without resolving cause, it alarm again.
7.3 Cause of Fault and Reaction
Er-01
(Pressure Sensor Error-tSF)
Cause
ㆍ
Sensor Error
ㆍ
Drive Error
ㆍ
Sensor Terminal Wiring
ㆍ
In case of multi-drive operation, Comm. ID not set up
Reaction
ㆍ
Replace sensor.
ㆍ
Replace drive.
ㆍ
Check sensor terminal wiring or comm.. ID setup incase of interoperation.
Related Function
Function Name
Ref. Page
Pr-50 CAN
Communication
Mode
6-10
Pr-51 Communication
ID
Pr-52 CAN
Communication
Speed
6-10~11
Er-02
(High Pressure Alarm-tOP)
Cause
ㆍ
In case the current pressure increases more than 2bar than the pressure setting during
operation, operation will stop after elapsed High Pressure Alarm Time (Pr-72) and the alarm
lamp will be turned on.
(It may occur on temporary installation site or trial run test.)
Reaction
ㆍ
Check setup pressure and high pressure alarm level.
When the current pressure goes down under the high pressure alarm setting, the drive will be
recovered automatically.
Related Function
Function Name
Ref. Page
Pr-70
High Pressure Alarm Level
Pr-72 High
Pressure
Alarm
Time
6-12
6-13
Содержание Q-Drive NQ-0075-S
Страница 1: ...User Guide Model AC Drive V F D 3 Phase input www doochpump com...
Страница 2: ......
Страница 8: ...SAFETY PRECAUTIONS 6 DOOCHPUMP...
Страница 16: ...CHAPTER 3 EXTERNAL DIMENSION 3 2 DOOCHPUMP 3 2 NQ 0400T H W D W1 D1 Weight NQ 0400T 162 151 229 133 217 3 3kg...
Страница 20: ...CHAPTER 3 EXTERNAL DIMENSION 3 6 DOOCHPUMP...
Страница 22: ...CHAPTER 4 INSTALLATION 4 2 DOOCHPUMP 4 2 Wiring Diagram of Terminals 3 380V 440 AC Input 50 60 Hz...
Страница 27: ...CHAPTER 4 INSTALLATION 4 7 DOOCHPUMP Power Range 5 5 22kW...
Страница 44: ...CHAPTER 5 OPERATION 5 14 DOOCHPUMP...